Specifications:
The document outlines the specifications for remote control contact and signal access. For AC, the maximum voltage is 250V with a current of 0.5A, using single-core wire with a maximum diameter of 1.5mm. For DC, the maximum voltage is 60V with a current of 0.1A, using multi-core wire with a maximum diameter of 1.3mm. Models without 'S' do not have remote control contact functionality.
Model Information:
The models listed include FV25B/2-150(S), FV25B/2-255(S), FV25B/2-275(S), FV25B/2-320(S), and FV25B/1-385(S). These models are tested under IEC/EN/VDE Class I/B and are suitable for TT and TN network types. They offer protection modes L-PE and N-PE.
Electrical Characteristics:
Nominal voltage is 50(60)Hz with options for 110/220V~ and 220/380V~. The rated voltage (UC) ranges from 150V to 385V. Impulse current (Iimp) and nominal discharge current (In) are both 25kA. Voltage protective level (Up) is ≤1.6kV or ≤1.8kV, with a response time (tA) of ≤100ns. Recommended back-up fuse is 315A, and isolation resistance is greater than 10 MΩ.
Installation and Operation:
I/O connections for L-N use multi-core wire of 10mm to 25mm, and PE uses multi-core wire greater than 16mm. The device mounts on a 35mm symmetrical rail (EN50022/DIN46277-3). It operates in temperatures from -40℃ to +80℃, humidity from 30% to 90%, and altitudes up to 3000m. The degree of protection is IP20, and the housing material is UL94 V-0. A mechanical indicator shows the disconnection status (Green: OK, Red: replace).
Additional Features:
The device features a unique seal construction with a multilayer spark gap, preventing spark emission outside the housing. It includes a working status indication window and optional remote control contacts. It is mainly used in lightning protection zones (LPZ) 0 to 1, suitable for building entrance lines, elevators, and mineral applications. The device is a 1-phase, 2-pole surge protective device for low-voltage power systems.