Specifications:
The document outlines the specifications for remote control contact in surge protective devices. For AC systems, the maximum voltage (U) is ≤250V with a current (I) of ≤0.5A, using single-core wire with a maximum diameter of 1.5mm. For DC systems, the maximum voltage is ≤60V with a current of ≤0.1A, using multi-core wire with a maximum diameter of 1.3mm. If the model number lacks an 'S', it does not include remote control contact functionality.
Components and Features:
The device consists of a base part and MOV pluggable protection modules, designed for use in lightning protection zones at boundary 1-2. It features metal oxide varistor components with high discharge capacity, low residual voltage, and quick response. The device includes a Thermo Dynamic Control disconnector for reliable control, a remote signaling contact for control devices, and a fault indication via a red mark in the inspection window. The protection mode covers L1, L2, L3, N-PE.
Model Information:
Models include FV10D/4-150(S), FV10D/4-275(S), FV10D/4-320(S), FV10D/4-385(S), and FV10D/4-440(S). They are tested under IEC/EN/VDE Class II+III/C+D standards and are suitable for TT and TN network types. Nominal voltage ranges from 110/220V~ to 220/380V~, with rated voltages (UC) from 150V~ to 440V~.
Performance Parameters:
The maximum discharge current (Imax) is 20kA, and the nominal discharge current (In) is 10kA. The voltage protective level (Up) ranges from ≤0.6kV to ≤2.0kV. The open circuit voltage (Uoc) is 20kV, with a response time (tA) of ≤25ns. A recommended back-up fuse is 63A, and isolation resistance is greater than 10 MΩ.
Installation and Environmental Conditions:
The device supports multi-core wire connections from 4mm to 25mm and mounts on a 35mm symmetrical rail (EN50022/DIN46277-3). It operates within a temperature range of -40℃ to +80℃, humidity of 30% to 90%, and altitude up to 3000m. The degree of protection is IP20, with housing material rated UL94 V-0. A mechanical indicator shows green for OK and red for replacement. Remote control contact is optional.