Group: Gilbarco Veeder-Root
Catalog excerpts
The Automatic Monitoring System for Active Vapour Recovery Sensors & Systems Worldwide: www.fafnir.com
Open the catalog to page 1FAFNIR GmbH: Innovation with Tradition. Quality and Satisfaction – made in Germany Company The FAFNIR GmbH, based in Hamburg, Germany, develops and manufactures since 1965 filling s afety devices, overfill prevention devices, limit signal controllers and continuous level gauging solutions for all types of liquid. The optimisation of process controls, improvements in cost efficiency and the protection of p eople and the environment are at the heart of our business. Our close and trusting relationship with our customers is a key factor in the practice-oriented implementation of innovative...
Open the catalog to page 2The Automatic Monitoring System for active Vapour Recovery FAFNIR As an automatic monitoring system for the active vapour recovery VAPORIX serves as protection for people and environment. Product information The VAPORIX automatic monitoring system provides information about the functional state of the active vapour recovery and thus complies with the legal requirements. Application The VAPORIX automatic monitoring system is especially designed for use in petrol stations. Due to its modular structure VAPORIX can be used in all known active vapour recovery systems and fuel dispensers. ■...
Open the catalog to page 3Function The flow sensor VAPORIX-Flow is based on the calorimetric measuring principle. The medium which flows past a heated sensor element absorbs the energy and thus cools it. The volume flow can be concluded from the absorbed heat energy. The incoming media parameters (HC and air) are adjusted by the simultaneous coverage of the HC concentration, i.e. the measured volume flow is captured independently of the media. System design Installation instructions VAPORIX-Flow is installed in the vapour recovery pipe before the pump and before any existing control valve and/or...
Open the catalog to page 4Technical data Sensor VAPORIX-Flow Connections »» Connection to the VAPORIX-Control »» Connecting thread: G ⅜“ Operating data »» Explosion protection: II 1 G Ex ia IIB T3 Ga »» Approvals: TÜV 99 ATEX 1509, IECEx TUN 08.0008 »» Index of protection IP68 »» Perm. ambient temp.: - 40 °C to + 65 °C Dimensions »» Installation length: 269 mm Edition 05.16 Technical changes reserved
Open the catalog to page 5Technical data Control unit VAPORIX-Control Connections »» Power supply: 230 V ~ … »» Pulse inputs: rectangular signal with 5…24 V pulse height, max. 1 kHz, duty factor 20…80 % »» Pulse valency: 100 pulses / litre default setting; Optional: 33 / 50 / 132 / 200 pulses / litre default setting »» Outputs: 2 x galvanically isolated transistor outputs max. 30 V, 100 mA 6 | VAPORIX-Control – Technical data »» Interfaces: 1 x RS-232 (service), 1 x RS-485 4-wire (dispenser computer), 1 x RS-485 2-wire (SECON, DOMS, POS) Edition 05.16 Technical changes reserved Operating data »» Explosion...
Open the catalog to page 6Edition 05.16 Technical changes reserved FAFNIR VAPORIX - Order code VAPORIX Control - Order Code 7
Open the catalog to page 7Condensate Separator The Condensate Separator for Vapour Recovery Systems Features of the FAFNIR technology Product information The condensate separator is designed for fuel dispensers to be retrofitted with decentralized active vapour recovery systems. The condensate separator collects large quantities of condensate and converts it back into a gaseous state. It is designed for the requirements of vapour recovery systems at petrol stations. ■ Ideal for retrofitting existing equipment ■ Robust construction ■ Maintenance-free The application of the condensate separator increases the lifetime...
Open the catalog to page 8Condensate separator Edition 05.16 Technical changes reserved FAFNIR Installation instructions The condensate separator is integrated into the vapour recovery system between the nozzle and the vapour recovery pump. In order to guarantee a proper operation the following installation instructions should be observed: » The installation position of the condensate separator must always be vertical, i. e. in an upright position (see the drawing). » The supply connections must not be interchanged. » To fasten the condensate separator standard pipe clamps can be used, if necessary. » After...
Open the catalog to page 9The pulse correction module for vapour recovery systems VAPORIX PCM (Pulse Correction Module) extends and improves the function of pulsecontrolled vapour recovery systems. Function With the help of its micro-controlled electronics VAPORIXPCM reverts to the established history data base inside the VAPORIX-Control. This historybased knowledge enables a highly effective corrective control of the vapour recovery. All influences that could affect the vapour recovery are included. The result is an excellent corrective control that exactly diagnoses failures of the vapour recovery. Features of...
Open the catalog to page 10Process flow Corrected control pulses Side A VAPORIX-PMC - Technical data 11
Open the catalog to page 11FAFNIR GmbH Schnackenburgallee 149 c 22525 Hamburg, Germany Phone: Fax: E-Mail: info@fafnir.com Internet: www.fafnir.com Sensors & Systems Worldwide: www.fafnir.com
Open the catalog to page 12All FAFNIR catalogs and technical brochures
-
TORRIX M12 MOBILE
2 Pages
-
TORRIX XTS
2 Pages
-
TORRIX 6
1 Pages
-
LPG Sensors
8 Pages
-
SEPARIX
8 Pages
-
Process Automation
28 Pages
-
O²-PID
4 Pages
-
COMS Leaflet
4 Pages
-
VAPORIX Flow and Control
40 Pages
-
Wallmounting Typ 907
4 Pages
-
QE 200
4 Pages
-
UM 2.1/2.2/2.3
20 Pages
-
TORRIX HART
28 Pages
-
TORRIX RS485 Modbus
16 Pages
-
TORRIX M12
40 Pages
-
FAFNIR Hart Setup
9 Pages
-
LS 300 / 500
7 Pages
-
76 A / NB 220
5 Pages
-
76 / NB 220
2 Pages
-
SECON-X
4 Pages
-
PRESSURIX
12 Pages
-
Insite360
4 Pages
-
Plugs
12 Pages
-
UM 2.1/UM 2.2/UM 2.3
20 Pages
-
TORRIX-HART
28 Pages
-
DIVELIX
8 Pages
-
CONDURIX-HART
28 Pages
-
CONDURIX
24 Pages
-
VISY-X
24 Pages
-
Accessories
3 Pages
-
VISY-Command Web
4 Pages
-
VISY-Reed
4 Pages
-
VISY-RF
2 Pages
-
VISY-Stick
15 Pages
-
VISY-TD Display
2 Pages
-
VISY-View Touch
2 Pages
-
VPI - VISY-Power Interface
1 Pages
-
TORRIX
10 Pages
-
TORRIX CI
1 Pages
-
TORRIX RS485
3 Pages
-
UM-X Transducer
3 Pages
-
TEMPERIX
8 Pages
-
HPH Ex d
3 Pages
-
VISY-Monitor
2 Pages
-
VISY-Input VISY-Output
4 Pages
-
VISY-Command
5 Pages
-
LPG-Sensoren
8 Pages
Archived catalogs
-
2019 VISY-Stick Flex
2 Pages
-
2016 VISY-Stick Flex
2 Pages
-
VISY-X LON
10 Pages
-
SEPARIX
23 Pages
-
VAPORIX Flow/Control
32 Pages
-
VISY-Setup V 3.1.0
40 Pages
-
VISY-Setup V2.10
42 Pages
-
VISY-View
24 Pages
-
VISY-Stick and VISY-Command
24 Pages
-
Overfill Prevention (GWG)
12 Pages