UM 2.1/2.2/2.3

UM 2.1/2.2/2.3
1 / 20 PagesView full catalog

UM 2.1/2.2/2.3

Product catalog summary
Characteristic Features: The measurement evaluation units UM 2.1, UM 2.2, and UM 2.3 are designed for evaluating and displaying liquid levels in tanks. UM 2.1 uses a bar display and outputs two limit values. UM 2.2 provides outputs proportional to the filling level. UM 2.3 U/I uses a microprocessor and LED numeric display, also allowing two limit values to be set.
Safety Instructions: These units are intended solely for measuring tank filling levels. Unauthorized modifications or improper use can lead to damage. Only trained personnel should handle installation and maintenance, adhering to all safety regulations.
Structure and Operation: Each unit contains power supply and signal evaluation components. UM 2.1 features a light-strip indicator and potentiometers for setting limit values. UM 2.2 offers current and voltage outputs. UM 2.3 U/I includes a numeric display and configuration buttons.
Installation: Units must be installed in a weatherproof location with specific temperature conditions. Wiring should be done with the unit de-energized, following all relevant safety and technical regulations. Detailed connection instructions are provided for each unit type.
Technical Data: Each unit has specific technical specifications, including output types and connection requirements. UM 2.1 and UM 2.3 allow setting of limit values, while UM 2.3 requires configuration for tank data.
Decimal Point Configuration: Users can set the position of the decimal point for display purposes. Options include no decimal point, or placement after the 1st, 2nd, or 3rd digit. The desired position is set using the plus button and confirmed with the OK button.
Tank Design Configuration: The tank design must be configured using a numeric code to convert the filling level to liters. Options include linear tanks, cylindrical tanks, spherical tanks, plastic battery tanks, oval tanks, plastic tanks with recess, and semi-circular cisterns. The appropriate design is selected and confirmed using the plus and OK buttons.
Tank Volume Entry: The maximum total volume of the tank is entered as a 4-digit value in liters. For volumes larger than 9999 liters, the value is entered in cubic meters, and the decimal point position may need adjustment. Each digit is selected and confirmed sequentially.
Tank Height Entry: The tank height is entered as a 4-digit value in millimeters. Each digit is selected and confirmed sequentially.
Current Filling Level Entry: The current filling level is entered as a 4-digit value in millimeters. This requires prior installation of the level sensor. The setting is made when the tank is relatively full, and each digit is selected and confirmed sequentially.
Configuration Verification: After configuration, the displayed liquid volume may need verification and adjustment. This involves using a sounding stick and chart, and adjusting the display value using the plus and OK buttons.
Error Messages: If an error message appears during configuration, it must be acknowledged by pressing the OK button after resolving the issue. The setting mode will revert to the first configuration stage for re-entry.
Limit Values Setting: Limit values are set on the measurement evaluation unit by simulating input voltage and adjusting the limit signal potentiometers. The appropriate LED indicates the limit signal relay response, with a hysteresis of approximately 3% to prevent chattering.
Technical Data:
  • UM 2.1: IP 40 protection, 230 V auxiliary power, 0 to 10 V DC input, 0 V to 10 V output, red LED light-strip indicator with 5% resolution.
  • UM 2.2: IP 40 protection, 24 V or 230 V auxiliary power, 0 to 10 V DC input, 0 (4) to 20 mA and 0 V to 10 V output.
  • UM 2.3 U/I: IP 40 protection, 230 V auxiliary power, 0–10 V DC or 4–20 mA input, 2x floating changeover contact output, red LED-numeric display for liquid volume.
See more

Catalog excerpts

UM 2.1/2.2/2.3-1

Technical Documentation UM 2.1/UM 2.2/UM 2.3 Measurement evaluation units

 Open the catalog to page 1
UM 2.1/2.2/2.3-2

© Copyright: Reproduction and translation only with the written consent of the company FAFNIR. FAFNIR reserves the right to carry out product alterations without prior notice. Measurement evaluation units UM 2.1/UM 2.2/UM 2.3

 Open the catalog to page 2
UM 2.1/2.2/2.3-3

Measurement evaluation units UM 2.1/UM 2.2/UM 2.3

 Open the catalog to page 3
UM 2.1/2.2/2.3-4

Characteristic features of the measurement evaluation units UM 2.1, UM 2.2 and UM 2.3 The measurement evaluation units UM 2.1, UM 2.2 and UM 2.3 U / UM 2.3 I are used for evaluating and displaying levels of liquids in tanks. The levels measured and transferred to the measurement evaluation units are processed in such a way that they can either be read off a display on the measurement evaluation units or have an electrical output: • UM 2.1 indicates the level in the form of a bar display and outputs two freely definable limit values via changeover contacts. • UM 2.2 provides an output of 0/4–20...

 Open the catalog to page 4
UM 2.1/2.2/2.3-5

The measurement evaluation units UM 2.1, UM 2.2, UM 2.3 U, or UM2.3 l serve the purpose of measuring and evaluating the filling levels in tanks. Use the system for this purpose only. The manufacturer shall not be liable for any form of damage resulting from improper use! The measurement evaluation units were developed, manufactured and inspected in accordance with state-of-the-art technology and with recognised technical safety rules and regulations. Nevertheless, hazards may arise from the use of these devices. Therefore, observe the following safety instructions. Do not change or modify the...

 Open the catalog to page 5
UM 2.1/2.2/2.3-6

Structure and mode of operation Measurement evaluation units UM 2.1, UM 2.2 and UM 2.3 U/ UM 2.3 I contain the power supply and signal evaluation for the connected level sensor. Measurement evaluation unit UM 2.1 Measurement evaluation unit UM 2.1 has a light-strip indicator with 5% increments for displaying the levels in the tank (1). With the Test button (4) and three potentiometers (5) at the bottom of the measurement evaluation unit two limit values can be set. The operating state of the measurement evaluation unit is indicated by three LEDs (LEDs). The green LED „Operation“ (3) is lit when...

 Open the catalog to page 6
UM 2.1/2.2/2.3-7

Measurement evaluation unit UM 2.2 Measurement evaluation unit UM 2.2 provides an output of 0/4–20 mA and an output of 0–10 V proportional to filling level. The green LED „Operation“ (1) is lit when the UM 2.2 is connected to the power supply and is ready for operation. 1 Hersteller: FAFNIR GmbH Hamburg Hilfsenergie: 230 V Ausgang: 0(4)–20mA max. 500 Ω Fig. 1b: Measurement evaluation unit UM 2.2 Measurement evaluation units UM 2.1/UM 2.2

 Open the catalog to page 7
UM 2.1/2.2/2.3-8

Measurement evaluation units UM 2.3 U and UM 2.3 I Measurement evaluation units UM 2.3 and UM 2.3 I have a 4-digit numeric display for indication the levels in the tank (1). With the aid of the plus (2) and ok buttons (7) at the top of the measurement evaluation unit the unit can be configured and matched to respective tank data. With the Test button (5) and three potentiometers (6) at the bottom of the measurement evaluation unit two limit values can be set. The operating state of the measurement evaluation unit is indicated by three LEDs (LEDs). The green LED „Power“ (4) is lit when the measurement...

 Open the catalog to page 8
UM 2.1/2.2/2.3-9

Installation The measurement evaluation units are integrated into a plastic housing with IP 40 protection and must be installed in a weatherproof location. The permissible ambient temperature is between -20 °C and +40 °C. Carry out the wiring work only when the unit is in its deenergised state. Switch off the 230 V power supply system before opening the measurement evaluation unit. The power supply system is only allowed to be switched on only when the measurement evaluation unit has been firmly screwed together. For any work being carried out on the measurement evaluation unit, the relevant...

 Open the catalog to page 9
UM 2.1/2.2/2.3-10

2. Connect up measurement evaluation unit in accordance with Figs. 2a, 2b, 2c and 2d. N - Output 0–10V RLoad ≥ 10 kOhm Connecting cable Filling level sensor – UM 2.1 4 x 0,5 mm2, shielded Filling level sensor Fig. 2a: Connection of the measurement evaluation unit UM 2.1 L1 (-) not galvanically separated from 3 and 4 + Output 0 V bis 10 V - RLoad ≥ 10 kOhm not galvanically separated from 3 and 4 Connecting cable Filling level sensor – UM 2.2 4 x 0.5 mm2, shielded Filling level sensor Fig. 2b: Connection of the measurement evaluation unit UM 2.2 Measurement evaluation units UM 2.1/

 Open the catalog to page 10
UM 2.1/2.2/2.3-11

- Output 0–10V + R Load ≥ 10 kOhm Connecting cable Filling level sensor – UM 2.3 U 4 x 0.5 mm2, shielded Filling level sensor Fig. 2c: Connection of the measurement evaluation unit UM 2.3 U N Connecting cable Filling level sensor – UM 2.3 I 2 x 0.5 mm2 Filling level sensor Fig. 2d: Connection of the measurement evaluation unit UM 2.3 I Measurement evaluation units UM 2.1/UM 2

 Open the catalog to page 11
UM 2.1/2.2/2.3-12

3. Replace the housing and screw it on. 4. Finally turn on the power supply. The green LED „Operation“ and „Power“ are lit. Hersteller: FAFNIR GmbH Hamburg Hersteller: FAFNIR GmbH Hamburg Hilfsenergie: 230 V Ausgang: 0(4)–20mA max. 500 W Betrieb Test Power Test FAFNIR GmbH Hamburg Measurement evaluation unit UM 2.2 is now ready for operation. Measurement evaluation unit UM 2.3 still has to be configured and matched to the respective tank data. Finally, the two limit values are set on measurement evaluation units UM 2.1 and UM 2.3. Measurement evaluation unit UM 2.1 Setting limit values To set...

 Open the catalog to page 12
UM 2.1/2.2/2.3-13

and switches off again when the filling height is exceeded with a value of 23 %. Messauswertung Typ UM 2.1 Hersteller: FAFNIR GmbH Hamburg Fig. 3: Measurement evaluation unit UM 2.1 Measurement evaluation units UM 2.3 U and UM 2.3 I Configuring measurement evaluation units When the measurement evaluation unit has been connected up to the level sensor and the power supply, it has to be configured for correct indication of the level of liquid and hence for the respective tank data. The following parameters are configured in this order: 1. Decimal point (on the display) 2. Decimal point (on the...

 Open the catalog to page 13

All FAFNIR GmbH catalogs and technical brochures

  1. TORRIX XTS

    2  Pages

  2. TORRIX 6

    1  Page

  3. LPG Sensors

    8  Pages

  4. SEPARIX

    8  Pages

  5. O²-PID

    4  Pages

  6. QE 200

    4  Pages

  7. TORRIX HART

    28  Pages

  8. TORRIX M12

    40  Pages

  9. LS 300 / 500

    7  Pages

  10. 76 A / NB 220

    5  Pages

  11. SECON-X

    4  Pages

  12. PRESSURIX

    12  Pages

  13. Insite360

    4  Pages

  14. Plugs

    12  Pages

  15. TORRIX-HART

    28  Pages

  16. DIVELIX

    8  Pages

  17. CONDURIX-HART

    28  Pages

  18. CONDURIX

    24  Pages

  19. VAPORIX

    12  Pages

  20. VISY-X

    24  Pages

  21. Accessories

    3  Pages

  22. VISY-Reed

    4  Pages

  23. VISY-RF

    2  Pages

  24. VISY-Stick

    15  Pages

  25. TORRIX

    10  Pages

  26. TORRIX CI

    1  Page

  27. TORRIX RS485

    3  Pages

  28. TEMPERIX

    8  Pages

  29. VISY-Command

    5  Pages

  30. LPG-Sensoren

    8  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.