TORRIX M12

TORRIX M12
1 / 40 PagesView full catalog

TORRIX M12

Product catalog summary
Overview
The TORRIX M12 is a high-precision magnetostrictive level sensor designed for continuous liquid level measurement in tanks, particularly in the chemical industry. It features an M12 plug connector and is configurable via PC. Available versions include TORRIX C/CVT, RS485, SC, and FLEX, with probe lengths from 100 mm to 10 m. The TORRIX Ex version is suitable for explosive environments.
Safety Instructions
The sensor is intended for gauging liquid levels in tanks and must be handled by trained personnel following safety regulations. Improper use or modifications can pose hazards.
Design and Function
The sensor uses a screw-in unit or flange for installation and a float to gauge liquid levels. It operates on the magnetostriction principle, using a tensioned wire and magnetic field interaction to determine the float's position.
Installation
Installation must comply with national safety regulations, especially in explosive areas. Care is needed to avoid bending the probe tube or exposing it to strong magnetic fields.
Electrical Connection
Wiring configurations vary by version (standard or Ex). The Ex version requires certified equipment connections, adhering to specific electrical outputs and permissible external capacitance and inductance.
Probe Configuration
Configuration is done via PC, with specific procedures for each TORRIX version. Failure modes are addressed to ensure proper operation.
Maintenance
The sensor is generally maintenance-free, but return shipments require FAFNIR authorization. Regular maintenance includes overhauls and proper return procedures.
Technical Data
Specifications include material and operational parameters for the sensor and float.
Annex
Includes the EC Declaration of Conformity, EC-Type Examination Certificate, and additional instructions.
Electrical Connection and Wiring
Detailed wiring instructions emphasize disconnecting power before proceeding. The connection involves plugging the FAFNIR cable into the M12 connector, with specific torque and color coding for signals. Earthing must comply with regulations.
Cable Length and Resistance
Maximum cable length is determined by total resistance, including line resistances and device loads. A table provides maximum resistances for different voltages and cross-sections.
TORRIX (Ex) SC and RS485 Wiring
The TORRIX (Ex) SC requires a 4-wire cable and connection to specific FAFNIR units. The RS485 version requires certified equipment connections in explosive atmospheres.
Probe Configuration
Configuration of the TORRIX (Ex) C/CVT is via a computer tool, not to be used in explosive zones. The tool displays probe data, configuration data, and user information.
Maintenance and Technical Data
The sensor is maintenance-free, with return shipments requiring FAFNIR authorization. Technical data includes electrical connections, supply voltage, dimensions, protection class, material, temperature ranges, and communication protocols.
Specifications
Materials and pressure ratings for float types are outlined, suitable for vacuum pressure of -1 bar, contingent on undamaged floats.
Standards and Compliance
Sensors comply with EN 60079-0, EN 60079-11, and EN 60079-26 for intrinsic safety and explosive atmosphere suitability.
Installation and Use
Installation requires power disconnection, adhering to EN 60079-14 and local regulations, with detailed assembly and adjustment instructions.
Maintenance
Sensors are maintenance-free, but defects require FAFNIR repair. Cleaning instructions prevent electrostatic charging.
Technical Data
Electrical input values and operating temperature ranges are specified, with tables for maximum operating temperatures and protection levels.
Safety and Warnings
Warnings about electrostatic charging hazards and guidelines for safe use in explosive atmospheres are included.
Contact Information
FAFNIR GmbH's contact details are provided for inquiries.
See more

Catalog excerpts

TORRIX M12-1

Technical Documentation

 Open the catalog to page 1
TORRIX M12-4

The high-precision TORRIX level sensor is designed to provide continuous gauging of liquid media levels in tanks. The measuring principle used by the sensor exploits the physical effect of magnetostriction and is largely unaffected by temperature. This method is particularly ideal where level measurements are required to be extremely accurate, such as in the chemical industry. In this documentation, the TORRIX is described as a variant with M12 plug connector. As another option, the TORRIX with cable gland is available, see: Technical documentation TORRIX, art. no. 207074 The TORRIX with M12...

 Open the catalog to page 4
TORRIX M12-5

Safety instructions The purpose of the TORRIX level sensor is to gauge liquid levels in tanks. The level sensor must be used exclusively for this purpose. The manufacturer accepts no liability for any form of damage resulting from improper use. The level sensor has been developed, manufactured and tested in accordance with the latest good engineering practices and generally accepted safety standards. Nevertheless, hazards may arise from its use. For this reason, the following safety instructions must be observed: Do not change or modify the level sensor or add any equipment without the prior...

 Open the catalog to page 5
TORRIX M12-6

The design of the TORRIX level sensor is illustrated in the version with screw-in unit (see following figure). At the sensor head (1) of the level sensor located are the M12 plug connector (2) and the connection for potential equalization (3). The electrical connection is done via M12 plug on the sensor head. On the probe tube (4) is a screw-in unit (5) (cutting ring fitting or ferrule fitting) for height adjustment capability or a flange (not shown) for fixed installation. The float (6) is the key component for continuous gauging of the product filling level or boundary layer and is held on...

 Open the catalog to page 6
TORRIX M12-7

The measuring principle illustrated in the following figure exploits the physical effect of magnetostriction and is largely unaffected by temperature. The probe tube contains a tensioned wire (1) made of magnetostrictive material. The sensor electronics transmit current pulses (2) through the wire, which generate a circular magnetic field (3). A magnet (4) inside the float acts as the filling level sensor. Its magnetic field applies an axial magnetic field to the wire. The superposition of the two magnetic fields produces a torsional wave (5) at the float position, which then propagates along...

 Open the catalog to page 7
TORRIX M12-8

Installation When installing and maintaining the level sensor in potentially explosive areas, the national rules must be observed (Explosion Protection Regulations, Industrial Health and Safety Regulations, Equipment Safety Regulations and the specific conditions of the EC-Type Examination Certificates). The generally accepted rules of engineering and these operating instructions must be observed. All applicable local safety and accident prevention regulations not included in this manual must also be observed. This section describes how to install the level sensor depending on the type (see the...

 Open the catalog to page 8
TORRIX M12-9

During installation, take great care not to bend the probe tube, and protect the float from shock and impact loads. Installing a level sensor in areas exposed to a powerful external magnetic field is not permitted because this could impair gauging. The level sensor can also be fitted into the tank from underneath. If the container additionally is pressurized, then the maximum length of the level sensor is 2 m. If the float is removed during installation, it must be slid back onto the probe tube afterwards with the “TOP” marking oriented towards the sensor head to enable correct measurements....

 Open the catalog to page 9
TORRIX M12-10

For correct gauging, the float must be slid onto the probe tube with the “TOP” marking oriented towards the sensor head. Refit circlip (1) on the tube, align the set screws with the groove and tighten. Adjust the height of the process connection and fix the union nut (5) by hand finger-tight. Fix the union nut (5) with a 1 ¼ clockwise turn (see following figure). 5 Figure 5: Compression fitting fixing Installation with flange The probe tube is permanently welded to the flange, which means that the installation length cannot be altered. The screws or nuts and the seals are the responsibility of...

 Open the catalog to page 10
TORRIX M12-11

Electrical connection Connection diagram of the standard version The level sensor without Ex approval is installed in accordance with the following wiring diagram: TORRI X Power supply Spannungsquelle Umax = 50 V Leitungswiderstände Cable resistance Load Bürde U Figure 6: Connection diagram TORRIX Power supply: Umax = 50 V DC Minimum supply voltage: Umin = 8 V Permissible total resistance (including cable resistance and load): ΣR = (U - Umin) / 0.0215 A Connection diagram of the Ex version The level sensor with Ex approval is installed in accordance with the following connection diagram: TORRI...

 Open the catalog to page 11
TORRIX M12-12

FAFNIR The intrinsically safe version of the TORRIX Ex C level sensor, when installed in a potentially explosive atmosphere, is permitted to be connected only to associated equipment that have been certified by a recognised inspection authority and offer electrical outputs that meet the following conditions: Uo < 30 V data can be found in the EC-Type Examination Certificate (refer to the Appendix). If the level sensor is to be used in a potentially explosive atmosphere, always make sure that the permissible external capacitance (C0) and inductance (L0) of the associated equipment are not exceeded...

 Open the catalog to page 12
TORRIX M12-13

The connection cable between the TORRIX ... and the associated equipment must have the following properties: • 2-wire unshielded cable For Ex applications colour blue or marked blue (cable for intrinsically safe power circuits) The earthing or equipotential bonding must be carried out by the installer in accordance with the national installation regulations applicable in each case. The earth connector of the sensor head can be used for earthing or equipoten-tial bonding requirements. Note also the general installation regulations. 5.1.4 Cable length The maximum cable length depends on the total...

 Open the catalog to page 13

All FAFNIR GmbH catalogs and technical brochures

  1. TORRIX XTS

    2  Pages

  2. TORRIX 6

    1  Page

  3. LPG Sensors

    8  Pages

  4. SEPARIX

    8  Pages

  5. O²-PID

    4  Pages

  6. QE 200

    4  Pages

  7. UM 2.1/2.2/2.3

    20  Pages

  8. TORRIX HART

    28  Pages

  9. LS 300 / 500

    7  Pages

  10. 76 A / NB 220

    5  Pages

  11. SECON-X

    4  Pages

  12. PRESSURIX

    12  Pages

  13. Insite360

    4  Pages

  14. Plugs

    12  Pages

  15. TORRIX-HART

    28  Pages

  16. DIVELIX

    8  Pages

  17. CONDURIX-HART

    28  Pages

  18. CONDURIX

    24  Pages

  19. VAPORIX

    12  Pages

  20. VISY-X

    24  Pages

  21. Accessories

    3  Pages

  22. VISY-Reed

    4  Pages

  23. VISY-RF

    2  Pages

  24. VISY-Stick

    15  Pages

  25. TORRIX

    10  Pages

  26. TORRIX CI

    1  Page

  27. TORRIX RS485

    3  Pages

  28. TEMPERIX

    8  Pages

  29. VISY-Command

    5  Pages

  30. LPG-Sensoren

    8  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.