Overview: The iUPS200 Zone 2 UPS system is designed to provide an uninterruptible power supply to critical plant equipment in hazardous environments, including those that are explosive, harsh, wet, and corrosive. It is certified for Zone 2 hazardous areas and offers backup power for up to 120 minutes at a full load of 70W.
Specifications: The system is constructed from 316L stainless steel and has an IP66 protection rating, making it suitable for extreme conditions. It operates within a temperature range of -20°C to +55°C and supports a power supply of 90-264VAC. The maximum power output is 67.2W at 12V or 62.4W at 24V, depending on the configuration.
Features: The iUPS200 includes advanced battery charge controls with temperature compensation to ensure optimal battery life. It offers status indication via enclosure-mounted lamps and logic outputs for integration with DCS or other equipment. The enclosure can be wall or pole-mounted, and various mounting solutions are available.
Battery and Logic Control: The system provides battery charging and high voltage indicators, as well as input OK indicators. It also includes an output off pushbutton for manual control. Logic outputs are available as an alternative to status indicators.
Ordering Information: Customers can specify options for battery/power output voltage, battery charging indicators, input OK indicators, output off pushbutton, enclosure cable entry, and logic outputs. Accessories such as pipe mount bracket kits are also available.
Certification: The iUPS200 is ATEX certified (ITS09ATEX46416) for use in explosive atmospheres, ensuring compliance with safety standards.
See more

Catalog excerpts

Zone 2 Uninterruptible Power Supply iUPS200-1

iUPS200 Zone 2 Uninterruptible Power Supply Zone 2 UPS system provides an uninterruptible power supply to plant equipment installed in potentially explosive, harsh, wet, and corrosive environments ATEX II 3 G Ex nA II T4 (-20oC≤Ta≤+55oC) IP66 protection 316L stainless steel construction Overview The iUPS200 Zone 2 UPS Enclosure is certified for use in Zone 2 hazardous areas and provides back up power for up to 120 minutes, at 70W full load. Critical equipment such as wireless network nodes or equipment used in people tracking and automatic mustering systems are protected in the event of a blackout or brownout. The iUPS200 is designed to be either wall or pole mounted, is IP66 rated and made of 316L stainless steel making the rugged enclosure suitable for installation in potentially explosive, harsh, wet and corrosive environments. With its advanced battery charge controls, including built in temperature compensation feedback, the uninterruptible power supply system ensures the internal lead acid battery is receiving the correct charge. Other features available include UPS status indication via enclosure mounted lamps, power output disable via an enclosure mounted button, active logic outputs for connection to a DCS or other equipment. Mounting solutions and brackets are available on request. Features and Benefits Equipment Protection No loss of power to critical equipment during black & brown outs Logic Outputs Unit can have either in-built lamp & pushbutton indication/control or supply inputs/outputs for connection to a DCS or other equipment Battery Control The unit includes advanced battery charge control for increased battery life Rugged Enclosure Custom enclosure with IP66 ingress protection made from 316L stainless steel for installation in extremely arduous environments. Backup Time For full load, approx 120 minutes @ 25oC Extronics Ltd., 1 Dalton Way, Midpoint 18, Middlewich, Cheshire, UK. CW10 0HU Tel: +44 (0) 845 277 5000 Fax: +44 (0)845 277 4000 E-mail: [email protected] Web: www.extronics.com

 Open the catalog to page 1
Zone 2 Uninterruptible Power Supply iUPS200-2

Specification Power Supply Maximum Power Output 67.2W, 5.6A @ 12V or 62.4W, 2.6A @ 24V depending on battery/power output voltage ordered Backup Time For full load, approx 120 minutes @ 25oC Enclosure Material Ingress Protection Operating temperature: –20oC to 550C Storage temperature; –20oC to 850C Relative humidity; 0 to 95%, non condensing Input Connections 115/230VAC fused screw terminals via M20 cable gland See cable gland option #6 Output Connections 12/24VDC fused screw terminals via M20 cable gland See cable gland option #6 Enclosure Status Indicators (Optional, when logic outputs not...

 Open the catalog to page 2