video corpo

iBATT100

iBATT100

Product catalog summary
Overview
The iBATT100 Battery Enclosure is designed to provide reliable battery power in hazardous areas. It houses two 12V valve regulated lead acid batteries connected in series, offering superior performance and longevity compared to conventional batteries.

Specifications
  • Certification: A II 2 G Ex e IIC T6 Gb, IECEx Ex e IIC T6 Gb
  • Housing: 316L stainless steel
  • Ingress Protection: IP43 (Ex rating) / IP45 (non-Ex rating)
  • Voltage/Capacity: 24 VDC @ 150 aH
  • Weight: 120 kg
  • Dimensions: 610 x 515 x 370 mm
  • Operating Temperature: –20°C to 55°C
  • Batteries: 2 x 12V valve regulated lead acid type, rechargeable
  • Connections: Via Ex e cable glands
  • Maximum Charge Voltage: 29.4 V
  • Maximum Charge Current: 40.5 A
  • Maximum Discharge Current: 160 A
  • Charging Environment: Hazardous or safe area

Features
  • ATEX and IECEx Zone 1 certified
  • Durable construction suitable for harsh industrial environments
  • Lockable hinged lid for secure and easy maintenance
  • Rechargeable and low maintenance

Performance
The battery run time varies with power usage, ranging from 336 minutes at 500 VA to 39 minutes at 3000 VA, at 1.67Vpc and 20°C.
See more

Catalog excerpts

iBATT100-1

ATEX and lECEx Zone 1 certified Provides battery power in hazardous areas Highly durable and rugged Provide battery power in hazardous areas The iBATT100 houses two 12V valve regulated lead acid batteries, connected in series, for superior performance and longer life than conventional electrolyte batteries. Secure and easy to maintain The iBATT100's hinged lid is lockable, ensuring easy access for battery replacement and maintenance whilst avoiding tampering. Construction from 316L stainless steel, the iBATT100 is built for harsh industrial environments. Easy to use Rechargeable in the hazardous areas and low maintenance, the iBATT100 is a hassle free solution. Certification A II 2 G Ex e IIC T6 Gb, IECEx Ex e IICT6 Gb Housing 316L stainless steel Ingress protection IP43 (Ex rating) / IP45 (non-Ex rating) Batteries 2 x 12V valve regulated lead acid type, rechargeable Connections Via Ex e cable glands Maximum charge voltage 29.4 V Maximum charge current 40.5 A Maximum discharge current 160 A Charging environment Hazardous or safe area Extronics Limited 1 Dalton Way, Midpoint 18, Middlewich, Cheshire, UK. CW10 OHU Tel: +44 (0) 845 277 5000 Fax: +44 (0)845 277 4000 E-mail: [email protected] Web: www.extronics.com 332040-4.0 Copyri ght © Extronics Ltd 2016. The information contained in this document is subject to change without notice. Extronics cannot be held responsible for any errors or inaccuracies within this document.

 Open the catalog to page 1

All Extronics Ltd catalogs and technical brochures

  1. iANT221

    2  Pages

  2. iANT216

    3  Pages

  3. iBATT5xx

    2  Pages

  4. iUPS101

    4  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.