1. Catalogs
  2. Extech
  3. PQ3470: 3-Phase Graphical Power & Harmonics Analyzer/Datalogger

PQ3470: 3-Phase Graphical Power & Harmonics Analyzer/Datalogger

PQ3470: 3-Phase Graphical Power & Harmonics Analyzer/Datalogger

Product catalog summary
Overview: The document provides detailed specifications and features of the FLIR Systems 3-Phase Graphical Power and Harmonics Analyzer, model PQ3470. It includes information on available kits, features, specifications, and accessories.
Specifications: The analyzer measures AC voltage up to 600V and AC current up to 3000A with a basic accuracy of ±0.5% for both. It can measure active, apparent, and reactive power up to 9.999MW/MVA/MVAR with an accuracy of ±1.0%. The power factor range is 0.00 to 1.00 with an accuracy of ±0.04. The frequency range is 45Hz to 65Hz with an accuracy of ±0.1Hz. Harmonics can be measured from 1st to 50th order with varying accuracy.
Features: The analyzer features a large, sun-readable, backlit LCD for displaying up to 35 parameters. It supports data logging of up to 30,000 readings on an SD card in Excel format. The device can capture transient events and analyze total harmonic distortion (THD). It includes a built-in clock and calendar, and offers a wide sampling rate range from 2 seconds to 2 hours.
Accessories and Kits: The document lists various current clamp probes available for purchase separately, including 200A, 1200A, and 3000A models. Kits are available that bundle the analyzer with different probes. The package includes voltage test leads, batteries, an SD card, a universal AC adaptor, and a carrying case.
Usage and Applications: The analyzer is suitable for full system analysis in high power distribution systems, offering adjustable current and potential transformer ratios. It is designed for easy data transfer to a PC for further analysis using Excel.
See more

Catalog excerpts

PQ3470: 3-Phase Graphical Power & Harmonics Analyzer/Datalogger-1

3-Phase Graphical Power and Harmonics Analyzer Saves data on an SD card in Excel® format For easy transfer to a PC for analysis Features: • Large dot-matrix, sun-readable, graphical, backlit LCD • Full system analysis with up to 35 parameters - V (phase-to-phase), V (phase-to-ground) A (phase-to-ground) KW / KVA / KVAR / PF (phase) KW / KVA / KVAR / PF (system) KWH / KVAH / KVARH / PFH (system) Phase angle Complete with 4 voltage leads with alligator clips, 8 AA batteries, SD memory card, Universal AC adaptor (100 to 240V), and case. Clamp probes sold separately. • Select 200A, 1200A Current Clamps or 3000A Flexible Current Probes (sold separately) • Adjustable Current Transformer CT (1 to 600) and Potential Transformer PT (1 to 1000) ratio for high power distribution systems Clamp Probes (Sold Separately) • On-screen Harmonics display (1 to 50th order) Choose the best clamp probes to fit your application needs ranging from 200A to 3000A and flexible vs traditional jaw type. • Simultaneous display of Harmonics and Waveform • Display of Waveform with peak values • Analysis of Total Harmonic Distortion (THD) • Graphic Phase diagram with 3-Phase system parameters • 3-phase Voltage or Current Unbalanced Ratio (VUR, AUR) and unbalanced factor • Capture Transient events (including dip, swell, and outage) with programmable threshold (%) • Log up to 30,000 readings on a removable SD memory card in Microsoft Excel® format Model PQ34-2 200A Current Clamp Probes with 0.8" (19mm) jaw size Model PQ34-12 1200A Current Clamp Probes with 2” (50mm) jaw size Model PQ34-30 3000A (24”/600mm) Flexible Current Clamp Probes for wrapping around busbars • Wide sampling rate range (2 seconds to 2 hours) • Captured measurements can be imported directly into Excel via the SD memory card Specifications AC Voltage (True rms) AC Current Active Power (MW) Apparent Power (MVA) Reactive Power (MVAR) Power Factor Frequency Range Phase Harmonics Crest Factor Current Clamp input • Built-in Clock and Calendar • Easy-to-use onscreen menu • Easy-to-hold rugged over molded housing Backlit LCD displays numerical values. The data can be stored in SD memory card (included) and then transferred from meter to PC using Excel® software and datalogged readings. Peak AC Voltage Accuracy Peak AC Current Accuracy Active Power Energy (MWH) Apparent Power Energy (MVAH) Reactive Power Energy (MVARH) Datalogging Dimensions/Weight Specifications subject to change without notice. 6/17/14 - R1 Copyright © 2011-2014 FLIR Systems, Inc. All rights reserved including the right of reproduction in whole or in part in any form.

 Open the catalog to page 1

Archived catalogs

  1. General catalog

    144  Pages

  2. Anemometers

    4  Pages

  3. Clamp meters

    4  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.