| Model | Voltage | Output | Mounting | T-Class | Ambient | 'A' | 'B' |
|---|---|---|---|---|---|---|---|
| FXE30 | 110-120V, 220-254VAC | 30W | Wall/Rail | T3, T4 | 80°C, 40°C | 175 | 250 |
| FXE50 | 110-120V, 220-254VAC | 50W | Wall/Rail | T3, T4 | 80°C, 40°C | 250 | 325 |
| FXE75 | 110-120V, 220-254VAC | 75W | Wall/Rail | T3 | 60°C | 250 | 50 |
| FXE100 | 110-120V, 220-254VAC | 100W | Wall/Rail | T3 | 60°C | 325 | 50 |
The ‘FXE’ range of heaters is designed specifically for frost protection, anti‐condensation and temperature control within Zone 1 and Zone 2 Hazardous Areas. The ‘FXE’ delivers a constant power output and comes complete with mounting bracket and a 1.5 metre flying lead. FEATURES Certified to meet the requirements of the ATEX Directive 94/9/EC & IECEx Compact design, requires minimal space Optional over‐temperature protection Black anodized convective surface Standard product available with short delivery times Suitable for ambient temperatures ‐50 °C up to +80 °C TYPICAL APPLICATIONS Control / Monitoring Panels Instrumentation Cabinets Condensation Prevention Temperature Fluctuations Frost Protection Motor Enclosures
Open the catalog to page 1Finned Aluminium, Anodised Matt Black If required, heaters can be supplied with a range of remote mounted thermostats Weather Protection Control Options Option of a thermostat located in the connection cable to control the enclosure ambient operating temperature. Enclosure Thermostat FXT In‐Line Enclosure Thermostat FXT‐I