1. Catalogs
  2. EXHEAT Ltd
  3. Computational Flow Analysis.

Computational Flow Analysis.

Computational Flow Analysis.

Computational Flow Analysis.

Product catalog summary
Overview: The document provides detailed information about the BFP range of hazardous area Ex d certified immersion heaters, designed for use in hazardous environments and customizable to client specifications.
Features:
  • Certified to ATEX or IECEx standards, ensuring safety and compliance in hazardous areas.
  • Weatherproof terminal box certified to IP65 and Type 4 standards.
  • Temperature classifications range from T1 to T6, with power up to 1400kW.
  • Specially sealed elements to prevent moisture ingress, with the capability for on-site replacement without special tools.
  • Withdrawable elements available for replacement without draining the vessel.
  • Suitable for high ambient temperatures, with optional anti-condensation heaters.
Typical Applications: The heaters are suitable for a variety of applications including crude oil, hydrocarbon liquids, molecular sieve regeneration, glycol reboilers, heat transfer oils, industrial gases, tank heating, natural gas, heating medium, fuel gas, water, and fuel oils.
Technical Specifications:
  • Nominal flange sizes range from 6 inches (150 mm) to 40 inches (1000 mm), with varying kW loads depending on the immersed length.
  • Certification includes ATEX / IECEx II 2 G/D, Ex d IIB T1 to T6 Gb, and Ex tD A21 T85 to T450°C Db IP65, compliant with EN 60079 standards.
  • Terminal boxes are made from low temperature carbon steel or stainless steel with a flanged lid.
  • Elements are made from 80/20 NiCr resistance wire, sheathed in corrosion/erosion resistant materials such as Incoloy, stainless steel, Inconel, titanium, and Monel.
  • Internals include a baffle type support assembly to prevent vibration and deformation.
  • Suitable for voltages up to 690V.
See more

Catalog excerpts

Computational Flow Analysis.-1

Hazardous Area Electrical Process Heaters & Control Solutions FEATURES Certified to ATEX or IECEx standards Terminal box is certified weatherproof to IP65 as well as Type 4 standards Temperature classifications T1 to T6 Up to 1400kW Elements are specially sealed to prevent moisture ingress Elements are individually replaceable on site without the need for special tools Withdrawable type elements are available to facilitate replacement without draining the vessel Suitable and certified for use in high ambient temperatures (e.g. Middle East) Anti-condensation heaters fitted, if required BFP Range of Hazardous Area Ex d Certified Immersion Heaters The BFP electric heater comprises a large range of process immersion heaters, certified for use in hazardous areas and are custom built to meet client specifications. TYPICAL APPLICATIONS Crude oil / hydrocarbon liquids Molecular sieve regeneration Glycol (TEG & MEG) reboilers Heat transfer oils Industrial gases Tank heating Natural gas Heating medium Fuel gas Water Fuel oils +44 (0)1953 886200 | [email protected] | www.exheat.com

 Open the catalog to page 1
Computational Flow Analysis.-2

Hazardous Area Electrical Process Heaters & Control Solutions Nominal Flange Size Inch mm kW LOAD with Maximum Immersed Length of 3665 mm 1 w/sq cm 2.5 w/sq 7.44 w/sq cm Certification Terminal Box Elements Internals Voltage ATEX / lECEx <fi II2G/D Ex d MB T1 to T6 Gb Ex tD A21 T85 to T450°C Db IP65 EN 60079-0, EN 60079-1, EN 60079-7, EN 60079-31 Manufactured from low temperature carbon steel or stainless steel throughout, with flanged lid Manufactured from 80/20 NiCr resistance wire with high purity compacted magnesium oxide powder sheathed within corrosion / erosion resistant tube,...

 Open the catalog to page 2
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.