VRLA battery ST series

VRLA battery ST series
1 / 12 PagesView full catalog

VRLA battery ST series

Product catalog summary
Overview
The document outlines the technical specifications and features of EverExceed's Standard Range VRLA AGM batteries, designed for high performance in telecommunications and electric utility applications, with capacities ranging from 18Ah to 250Ah.
Specifications
  • Operating Temperature: -40°C to +70°C, ideal range +20°C to +28°C.
  • Storage Time: 12 months at 20°C ~25°C, halving for every 9°C increase.
  • Design Life: 12 years at 20°C.
  • Self-Discharge Rate: Less than 3% per month.
Applications
The batteries are suitable for telecommunications, electric utilities, distributed power, switchgear control power, UPS, power plants, data centers, railroads, microwave, substations, and broadband.
Innovative Features
  • Thick positive plate design for maximum service float life.
  • High-compression AGM technology for over 99% recombination efficiency.
  • Proprietary Fixed Orifice Plate Pasting technology for consistent performance.
  • Nano-carbon enhanced active material for improved cycle performance.
  • Heavy-duty copper terminals for ease of assembly and safety.
  • Advanced lead alloy for reduced grid corrosion.
  • Optional flame-retardant ABS container.
  • Safety one-way fireproof release venting system.
Standards and Compliances
The batteries comply with NEBS, EUROBAT "Long Life", BS 6290 PART 4, IEC 60896-21/22, Bellcore TR-NWT-000766, and ANSI TI: 330 standards.
Manufacturing and Safety
Advanced manufacturing technologies include automated sealing detection, computer-controlled acid filling, and temperature-controlled formation processes. Classified as non-hazardous for transport by surface, marine, and air.
Construction
Features calcium/tin lead alloy grids, a highly porous glass micro-fibre separator, and reinforced ABS housing for minimal resistance and optimal electrolyte absorption.
Electrical Specifications
Details on nominal voltage, capacity, short circuit current, internal resistance, terminal type, weight, and dimensions for various battery models.
Discharge Data
Comprehensive discharge data for different models, detailing discharge times at various voltages and temperatures.
Procedures
Recommended charging voltage is 2.27 V/cell, adjusted based on ambient temperature. Constant voltage charging is advised, with a float voltage range of 2.25VPC to 2.30VPC at 25°C, and an equalize voltage of 2.35VPC for 12 hours.
Temperature Compensation
Necessary for 0°C to 40°C, with adjustments of 3 mV/°C/cell above or below 25°C.
Recharging Time
Depends on charging current, provided for up to 50%, 70%, and 90% of capacity at 25°C with a charging voltage of 2.27 V/cell.
Self-Discharge
Includes a graph showing self-discharge in relation to storage temperature, indicating capacity retention over time.
Recommendations
Emphasizes constant voltage charging and temperature compensation to ensure optimal performance.
Additional Information
Document is copyrighted by EverExceed Corporation and includes a graph illustrating capacity over storage months at different temperatures.
See more

Catalog excerpts

VRLA battery ST series-1

Standard Range VRLA www.everexceed.com

 Open the catalog to page 1
VRLA battery ST series-2

power your applications Telecommunications □ Distributed Power □ UPS □ Data Center l Microwave l Broadband SEALED VRLA MONOBLOC AGM BATTERIES 18AH to 250AH The extremely powerful, compact AGM VRLA batteries of EverExceed telecom Standard Range are an ideal energy source for durability in Telecommunications and Electric Utility applications, the EverExceed top terminal Standard Range provides high performance and reliability in long duration discharge applications. Our development team combines the market's demand with design optimization, precision component selection and state-of-the-art manufacturing...

 Open the catalog to page 2
VRLA battery ST series-3

Standard Range VRLA CONSTRUCTION - AGM battery construction is as shown in the diagram below. The positive and negative grids are cast from a advantage low calcium / high tin lead alloy to reduce grid growth and corrosion. The active material is manufactured from best purity lead (99.994%) to minimize the negative effects of impurities. Separator is mat of random woven acid resistant glass fibers, which acts as sponge - soaking up and immobilizing the electrolyte whilst maintaining good acid to plate contact and availability during discharge. “U wrapping” is employed to eliminate the risk of...

 Open the catalog to page 3
VRLA battery ST series-4

power your applications Standard Range VRLA Electrical Specifications & Dimensions Battery *CA: Cable assembly with TEW-105 (#12 AWG) tinned copper wire, AMP connector housing Plug Kit and sockets. 03 □ mm www.everexceed.com Copyright © EverExceed Corporation. All rights reserved

 Open the catalog to page 4
VRLA battery ST series-5

power your applications Standard Range VRLA Standard Range VRLA Discharge Ampere Hours Data @ 20°C (68°F) Actual Battery Discharge Data may be +/-5% of figures shown above. Copyright © EverExceed Corporation. All rights reserved. 04

 Open the catalog to page 5
VRLA battery ST series-6

power your applications Standard Range VRLA Discharge Ampere Hours Data @ 20°C (68°F) Actual Battery Discharge Data may be +/-5% of figures shown above. Copyright © EverExceed Corporation. All rights reserved.

 Open the catalog to page 6
VRLA battery ST series-7

power your applications Standard Range VRLA Standard Range VRLA Discharge Amps Data @ 20°C (68°F) Actual Battery Discharge Data may be +/-5% of figures shown above. Copyright © EverExceed Corporation. All rights reserved 06

 Open the catalog to page 7
VRLA battery ST series-8

power your applications Standard Range VRLA Discharge Amps Data @ 20°C (68°F) Actual Battery Discharge Data may be +/-5% of figures shown above. □ mmCopyright © EverExceed Corporation. All rights reserved 07

 Open the catalog to page 8
VRLA battery ST series-9

power your applications Standard Range VRLA Standard Range VRLA Discharge Watts Data @ 20°C (68°F) Actual Battery Discharge Data may be +/-5% of figures shown above. Copyright © EverExceed Corporation. All rights reserved 08

 Open the catalog to page 9
VRLA battery ST series-10

power your applications Standard Range VRLA Discharge Watts Data @ 20°C (68°F) Actual Battery Discharge Data may be +/-5% of figures shown above. Copyright © EverExceed Corporation. All rights reserved.

 Open the catalog to page 10
VRLA battery ST series-11

power your applications Standard Range VRLA Float Voltage & charging Constant Voltage charging is recommended Recommended float voltage: 2.27VPC @ 25°C(77°F) Float Voltage Range: 2.25VPC to 2.30 VPC @ 25°C(77°F) Equalize voltage: 2.35VPC for 12 Hours Temperature compensation: Apply for temperature range of 0°C / 32°F to 40°C / 104°F. Sub tract 3 mV / °C / cell or 1.7 mV / °F / cell, above 25°C / 77°F. Add 3mV / °C / cell or 1.7 mV / °F / cell, below 25°C / 77°F. For charging 2.27 V/cell is recommended. The charging voltage must be compensated according to the curve for continuously different...

 Open the catalog to page 11
VRLA battery ST series-12

Supplied Worldwide by EverExceed Corporation

 Open the catalog to page 12

All EverExceed Industrial Co. Ltd catalogs and technical brochures

  1. EHCS 7K-11K

    3  Pages

  2. Battery rack

    2  Pages

  3. UXcel series

    5  Pages

  4. CHF series

    2  Pages

  5. Smart V1.0

    4  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.