video corpo

VRLA battery FGL series
13Pages

{{requestButtons}}

Catalog excerpts

VRLA battery FGL series - 1

Front Access FT Gellyte Range VRLA

Open the catalog to page 1
VRLA battery FGL series - 2

□ Solar / Photovoltaic □ Wind Generation □ Cathodic Protection 1 CATV □ Data Center Specifications Voltage Plate alloy Element, post Container/cover Specific gravity Electrolyte Vent VRLA MONOBLOC Gellyte BATTERIES 55Ah to 200Ah @ C10 The extremely powerful, compact Gel batteries of EverExceed front access FT Gellyte Range are an absolutely reliable energy source for durability in Solar / Photovoltaic, Telecommunications and Electric Utility applications. The EverExceed front access FT Gellyte Range VRLA provides excellent performance and reliability in long duration discharge & cycling...

Open the catalog to page 2
VRLA battery FGL series - 3

FT Gellyte Range VRLA Gellyte BATTERY CONSTRUCTION - The positive and negative grids are cast from a calcium / tin lead alloy to reduce grid growth and corrosion. The active material is manufactured from high purity lead (>99.994%) to minimize the negative effects of impurities. Gellyte Separator is mat of random woven acid resistant glass fibres. “U wrapping” is employed to eliminate the risk of short circuits due to mossing and debris at the bottom of the cell. The purpose of the separator is to maintain a constant distance between the positive and negative plates, thus removing the...

Open the catalog to page 3
VRLA battery FGL series - 4

power your applications EverExceed FT Gellyte Range Electrical Specifications & DimensionsTerminal and Torque 9NM 11NM 12 Years Design Life Grid Plate Monobloc Battery Nominal Capacity 55~200Ah Deep Discharge Recovery Maintenance Free Recyclable Valve Regulated Lead - Acid GEL Plastic screwed cap to hold down flat and o-ring Epoxy seal (Red for + Black for-) Plastic Flat Ring Rubber o-ring Lead terminal post with brass insert Float Voltage & Charging Constant voltage charging is recommended Recommended float voltage: 2.25VPC @ 20°C(68°F) Float voltage range: 2.25VPC to 2.27 VPC @ 20°C(68°F)...

Open the catalog to page 4
VRLA battery FGL series - 5

power your applications Battery Model Actual Battery Discharge Data may be +/-5% of figures shown above. Copyright © EverExceed Corporation. All rights reserved 04

Open the catalog to page 5
VRLA battery FGL series - 6

power your applications Battery Model Actual Battery Discharge Data may be +/-5% of figures shown above. Copyright © EverExceed Corporation. All rights reserved 05

Open the catalog to page 6
VRLA battery FGL series - 7

power your applications FT Gellyte Range Discharge Amps Data @ 20°C ( 68°F) Battery Model Actual Battery Discharge Data may be +/-5% of figures shown above.

Open the catalog to page 7
VRLA battery FGL series - 8

power your applications FT Gellyte Range Discharge Amps Data @ 20°C ( 68°F) Battery Model Actual Battery Discharge Data may be +/-5% of figures shown above. Copyright © EverExceed Corporation. All rights reserved 07

Open the catalog to page 8
VRLA battery FGL series - 9

power your applications Battery Model Actual Battery Discharge Data may be +/-5% of figures shown above. Copyright © EverExceed Corporation. All rights reserved 08

Open the catalog to page 9
VRLA battery FGL series - 10

power your applications Battery Model Actual Battery Discharge Data may be +/-5% of figures shown above. Copyright © EverExceed Corporation. All rights reserved 09

Open the catalog to page 10
VRLA battery FGL series - 11

power your applications FT Gellyte Range Constant Voltage Charge Characteristic Curve Self-Discharge of Gel Batteries at Different Temperatures VRLA Copyright © EverExceed Corporation. All rights reserved.

Open the catalog to page 11
VRLA battery FGL series - 12

FT Gellyte Range VRLA BATTERY CYCLING ABILITY The EverExceed’s FT Gellyte Range Battery excels in cycling applications. FT Gellyte Range batteries are capable of 5000+ charge / discharge cycles depending on the depth of discharge. Cycle Life Depth of Discharge at +20℃ (68℉) Based on IEC 896-2 TYPICAL CYCLIC PERFORMANCE Cycle Times CAPACITY WITHDRAWN CONSTANT CHARGING VOLTAGE: Shown is the constant charging voltage in relation to the ambient temperature. The bandwidth shows a tolerance of ± 30mV/cell. This constant voltage is suitable for continuous charging and cyclic operation. In a...

Open the catalog to page 12
VRLA battery FGL series - 13

power your applications Supplied Worldwide by EverExceed Corporation

Open the catalog to page 13

All EverExceed Industrial Co. Ltd catalogs and technical brochures

  1. EHCS 7K-11K

    3 Pages

  2. Battery rack

    2 Pages

  3. UXcel series

    5 Pages

  4. CHF series

    2 Pages

  5. Smart V1.0

    4 Pages