RMI-M Series Inverter

RMI-M Series Inverter

Product catalog summary
Overview: The RMI-M Series Inverter is a modular, parallelable inverter designed for high reliability and flexibility, suitable for 110VDC and 220VDC systems with a power range of 1-80KVA.
Key Features:
  • Digital Control: Utilizes 32-bit DSP and high-frequency SPWM technology for accurate control and pure output waveform.
  • N+1 Parallel Redundancy: Allows for a power system with module backup, enhancing reliability.
  • No Master-Slave Technology: Each module operates independently, eliminating single points of failure.
  • Hot Swap Support: Modules can be replaced or added without configuration, simplifying maintenance.
  • Built-in Module Bypass: Users can select between inverter or bypass operation.
  • Monitoring Management: Includes an indicator panel, fault alarms, RS485 communication interface, and fault dry contact.
  • Protection Functions: Features input anti-reverse connection, undervoltage, overvoltage, output overload, short circuit, and overtemperature protection.
Specifications:
  • Rated Power: Available in 1KVA, 2KVA, 3KVA, 5KVA, 6KVA, 8KVA, 10KVA.
  • DC Input Voltage: 110V/220VDC with a range of 92-142VDC/185-285VDC.
  • Bypass Input Range: 176-264VAC.
  • Bypass Switching Time: Electronic type <5ms, Mechanical type <20ms.
  • Rated Output Voltage: 220VAC.
  • Rated Output Frequency: 50Hz.
  • Load Regulation: <1%.
  • Frequency Accuracy: <0.1%.
  • Crest Ratio: 3:1.
  • Waveform Distortion: Resistance full load <3%, nonlinear full load <5%.
  • Dynamic Response: Voltage transient range <3%, recovery time ≤60ms.
  • Parallel Uneven Flow: <3% rated current RMS.
  • Communication Interface: RS485.
  • Insulation Strength: 2kVAC, 1min.
  • Noise Level: <45dB at 1m.
  • Operating Ambient Temperature: -10 to 50°C.
  • Transport and Storage Temperature: -40 to 70°C.
  • Relative Humidity: 0-90%, no condensation.
  • Relative Altitude: ≤3000m, with a 1% decrease in output for every 100m increase above 1500m.
  • Overload Capacity: Load current 125-150%, continuous work after 1min shutdown; Load current >150%, after 20ms shutdown.
Dimensions: Varies by model, with examples including 490×88×385mm for 1KVA and 540×132×405mm for 3KVA.
See more

Catalog excerpts

RMI-M Series Inverter-1

RMI-M Series Inverter Technical Data (220V AC OUTPUT): Rated Power Product Form 19 Inch Modular 110VDC & 220VDC Parallelable Inverter RMI-M Series 1-80KVA Dimensions (W×H×D)(mm) DC Input Range Input Parameter Bypass Input Range Bypass Switching Time 176~264VAC Electronic type<5ms (external) Mechanical type<20ms Electronic type<5ms (external) Mechanical type<30ms Rated Output Frequency Load Regulation Crest Ratio Waveform Distortion Resistance full load<3%, nonlinear full load<5% Dynamic Response Frequency Accuracy Rated Output Voltage Voltage transient range<3%, transient response recovery time ≤60ms (load from 0 to 100%) Parallel Uneven Flow AC Output Load current <105%, continuous work Digital control: using 32-bit D S P and high- frequency S P W M technology, with strong antiinterference ability, fast operation speed, high intelligence degree, accurate control, pure output waveform and other characteristics. Load current 105~125%, continuous work 10min shutdown Overload Capacity Load current 125~150%, continuous work after 1min shutdown Load current>150%, after 20ms shutdown N+1 parallel redundancy design: can be composed of N+1 parallel redundancy power system, module backup each other, high reliability, flexible and convenient configuration. No master-slave parallel technology: the operation of each module is independently controlled by the built-in D S P, no single point of failure, independent flow sharing between modules. Protection Function Built-in module bypass: users can choose inverter or bypass first. Monitoring management: indicator panel, fault acousto-optic alarm, RS485 communication interface and fault dry contact. Protection function: with input anti-reverse connection, undervoltage, overvoltage protection, output overload, short circuit, overtemperature protection. Work Environment Support hot swap: no need to do any setting and operation, plug and play, the module automatically normal working state, simple maintenance and replacement. Communication Interface Insulation Strength Input connection protection, input under voltage and over-voltage protection, output overload protection, output short circuit protection, over temperature protection Operating Ambient Temperature Transport And Storage Temperature Relative Humidity

 Open the catalog to page 1

All EverExceed Industrial Co. Ltd catalogs and technical brochures

  1. EHCS 7K-11K

    3  Pages

  2. Battery rack

    2  Pages

  3. UXcel series

    5  Pages

  4. CHF series

    2  Pages

  5. Smart V1.0

    4  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.