1. Catalogs
  2. EUROKLIMAT
  3. RAK.E/FC 17C2 - 160C4

RAK.E/FC 17C2 - 160C4

RAK.E/FC 17C2 - 160C4

RAK.E/FC 17C2 - 160C4

Product catalog summary
Main Features
  • Housing: Constructed with a base of painted galvanized steel and panels coated with PVC film for weather resistance.
  • Compressor: Hermetic scroll type with thermal protection and antivibration mountings.
  • Fan: Low-speed axial-flow fans with protective grille and aerodynamic design for efficiency and noise reduction.
  • Air Heat Exchanger: Finned coil with copper pipes and aluminum fins for high surface area.
  • Water Heat Exchanger: Plate-type made of AISI 316 steel with anti-condensate material.
  • Electrical Board: Complies with IEC 204-1/EN60204-1 standards, includes safety devices.
  • Control: Microprocessor-based control with BMS connectivity.
  • Refrigerant Circuit: Includes filter dryer, sight glass, solenoid valve, and pressure switches.
  • Water Circuit: Integrated with automatic charging, safety valve, and expansion tank.
  • Free Cooling Circuit: Maintenance-free with copper pipes and modulating 3-way valve.
Accessories
  • Vibration isolation mountings
  • Modulating fan speed control
  • Crankcase electrical heater
  • Compressor intercepting valves
  • Remote control panel
  • Voltage and phase relays
  • Pressure gauges and flow switch
  • Pumping group with additional stand-by pump
  • Automatic water filling valve
  • Separate compressor room air flow
  • Clock board
  • MODBUS and LONWORKS interface boards
Technical Data
  • Cooling Capacity: Ranges from 44.9 to 409.8 kW.
  • Free-cooling Capacity: Ranges from 37.8 to 308.3 kW.
  • Sound Pressure: Ranges from 68 to 75 dB(A).
  • Power Supply: 400/3/50+T V/ph/Hz.
  • Dimensions and Weight: Varies by model, with lengths from 2200 to 5300 mm and weights from 700 to 3800 kg.
Notes:
  • Cooling capacity and other parameters are based on specific conditions such as condenser air at 35°C and evaporator water IN/OUT at 12/7°C with 30% glycol.
  • Sound pressure is measured at 1 m in open field conditions.
See more

Catalog excerpts

RAK.E/FC 17C2 - 160C4-1

AIR COOLED WATER CHILLERS WITH FREE COOLING u Solutions B - Base I - Integrated u Version ST - Standard u Equipment AS - Standard equipment DS - Desuperheater Cooling Capacity 44,9-409,8 kW Free-cooling Capacity 37,8-308,3 kW Housing Base made of painted galvanised steel; panels made of galvanised steel externally coated with plastic (PVC) film and mounted on aluminium profiles to ensure total weathering resistance. Compressor HERMETIC SCROLL type, complete with thermal protection. Antivibration mountings and oil charge are standard. Fan Low speed, axial-flow fans fitted with accident-prevention protective grille; directly coupled motor with built-in thermal cutout and IP 54 protection degree; aerodynamic housing and wing profile blades increase efficiency and decrease noise level. Air heat exchanger Finned coil made with copper pipes and aluminium fins offering a high exchange surface area. Water heat exchanger Plate-type made of AISI 316 steel complete with water differential pressure switch. Shell covered with closed-cell neoprene anti-condensate material. Electrical board Switchboard to standards IEC 204-1/EN60204-1, complete with con- tactor and protection for compressor and fans. Main isolator and door interlock safety device. Control The microprocessor controls the unit capacity by timing the compressors and checks the operating alarms with the possibility to connect to BMS. Refrigerant circuit Filter dryer, moisture-liquid sight glass, solenoid valve, intercepting valve on the liquid line, thermostatic expansion valve with external equaliser, HP and LP pressure switches, flooding coil and hot gas by pass pressure equalising valve. Water circuit (Integrated): Automatic charging cock with gauge, safety valve, expansion tank, water pump, water tank. Free Cooling circuit NO MAINTENANCE FreeCooling coil realized by copper pipes integrated in the same aluminium fins pack of the condensing coil; modulating 3-way valve; control system integrated in the microprocessor. Vibration isolation mountings. Modulating fan speed condensing control (standard) Crankcase electrical heater (standard) Compressor intercepting valves Wall mounted remote control panel Max and min voltage relay. Sequence phases relay. Refrigerant gas HP and LP pressure gauges Electromechanical flow switch Pumping group, 1 pump. Additional stand-by water pump Automatic water filling valve Air flow separate compressor room(standard) Clock board MODBUS interface ele

 Open the catalog to page 1
RAK.E/FC 17C2 - 160C4-2

Scroll Compressor Technical data ST VERSION Cooling capacity(1) Total compressors power input(1) Water flow(1) External pressure @ Pn(1) Total air flow Sound pressure(2) Free cooling cooling capacity(3) Fans type Fans quantity Fans power input INTEGRATED SOLUTION Pump type Pump power input Water tank content DESUPERHEATER (DS Equipment) Heat capacity (4) Water flow Pressure drop DIMENSIONS AND WEIGHT - BASE Solution Lenght (L) Depth (P) Height (H) Shipping weight Dimension drawing Compressors type Compressors quantity Indipendent gas circuit Capacity steps Power supply Maximum absorbed current...

 Open the catalog to page 2