L-PRO 4000
9Pages

{{requestButtons}}

Catalog excerpts

L-PRO 4000 - 1

Transmission Line Protection Relay Product Overview The L-PRO 4000 provides easy-to-use, state-of-the-art comprehensive distance and directional line protection for medium to extra-high-voltage transmission lines using communication-based schemes. It provides control, automation, metering, monitoring, fault oscillography, dynamic swing recording, fault logging, event logging with advanced communications in a flexible cost effective package. Apply the L-PRO 4000 system for high speed protection and complete control in multi-breaker applications in ring or breaker-and-a-half arrangements. The L-PRO 4000 is ideal for multi-circuit line applications to monitor mutual coupling. • Easy-to-use, intuitive setting and analysis software and individual breaker monitoring) • IEC 61850 communication via optical/copper ports • 4 shot recloser with dead line/dead bus control and • Selectable single and 3 pole trip and reclose sync check • High-speed five-zone user-defined mho or quad phase • High quality fault and swing recording and event log and ground distance protection • 8 setting groups for many operating conditions • Single and multi-breaker applications (i.e. ring bus and • Ethernet ports with 2 unique MAC addresses breaker-and-a-half capability, including breaker failure accommodate network access security needs

Open the catalog to page 1
L-PRO 4000 - 2

Application • Primary and backup protection on transmission and sub-transmission lines (using pilot protection schemes) • Overhead lines and underground cables • Backup protection for generators, transformers and reactors • Ideal for multi-circuit line applications (to monitor mutual coupling via additional VT and CT inputs) Protection & Control • Protection functions — IEEE devices 21P, 21N, 25/27/59 (25C), 27, 50BF, 50LS, 50/51/67, 50N/51N/67, 46/50/51/67, 59, 60, 68, 79, 81, Dead Line Pickup (SOTF) and Weak Infeed, 59N and 60CTS • High-speed 5 zones of phase and ground distance functions...

Open the catalog to page 2
L-PRO 4000 - 3

Flexible Communications • 2 rear ports, 100BASE-TX RJ-45 or 100BASE-FX 1300 nm multimode optical with ST style connector • Ethernet ports with 2 unique MAC addresses that easily accommodate network access security needs • Front panel USB and 100BASE-TX RJ-45 Ethernet port interfaces Substation Automation - Ethernet Ready • IEC 61850 Station Bus on a dedicated optical/copper Ethernet Port • Enhanced DNP3 SCADA communication protocol including user-selectable point lists, class support and multiple master station support • Modbus SCADA communication protocol • IRIG-B port (through BNC...

Open the catalog to page 3
L-PRO 4000 - 4

Best in Class Human-Machine Interface Large LCD display, allows for better metering display Navigation controls allow for an easy experience through settings, maintenance, service and view menus New faster processor and hardware platform Programmable target LEDs provide tripping information to expedite response to systems events Unique front panel USB and Ethernet ports provide easy and fast access to settings and set up Rear optical ports ready for IEC 61850 Goose Protection & Control Function Diagram Bus 2 5050N Rec. /67 Dead Line Pickup 6 Analog Current Inputs Optional I/O 11 External...

Open the catalog to page 4
L-PRO 4000 - 5

Detailed SpecificationsL-PRO 4000 Transmission Line Protection Relay Item General Nominal Frequency Operate Time Power Supply Settings and records are stored in non-volatile memory Including relay output operation Power Consumption: 25 - 30 VA (ac) 25 - 30 W (dc) Records are stored in a circular buffer 2 x 3-phase voltage inputs for synchronizing during reclosing 2 x3-phase current inputs for protection Extra 6 currents used for recording and ProLogic input Suitable for ring bus configurations and integrated HV breaker auto-recloser 24 statements per setting group 8 (16 group logic...

Open the catalog to page 5
L-PRO 4000 - 6

L-PRO 4000 Transmission Line Protection Relay Item Quantity/Specs Notes Burden Burden resistance: > 10 k ohms Optional 48, 110/125 or 220/250 Vdc nominal, externally wetted External Inputs Isolation 9 isolated inputs (3U chassis) 20 isolated inputs (4U chassis) 2 KV optical isolation External Input Turn-on Voltage Output Relays (contacts) 48 Vdc range = 27 to 40 Vdc 125 Vdc = 75 to 100 Vdc 250 Vdc = 150 to 200 Vdc, 0% to 80% of nominal 14 programmable outputs (3U chassis) and 1 relay inoperative contact (N.C.) 21 programmable outputs (4U chassis) and 1 relay inoperative contact...

Open the catalog to page 6
L-PRO 4000 - 7

Item Quantity/Specs Environmental: Ambient Temperature Range -40°C to 85°C for 16 hours -40°C to 70°C continuous Up to 95% without condensation Power supply, analog inputs, external inputs, output contacts - 2 kVrms, 50/60 Hz, 1 minute Tested to level 4 - 4.0kV 2.5/5 kHz on Power and I/O lines Humidity Insulation Test (Hi-Pot) Electrical Fast Transient Oscillatory Transient Test level = 2.5 kV RFI Susceptibility 10 V/m modulated, 35 V/unmodulated Conducted RF Immunity Shock and Bump Sinusoidal Vibration Voltage Interruptions 22.6 lbs (3U chassis) 26.2 lbs (4U chassis) 5.2 height x...

Open the catalog to page 7
L-PRO 4000 - 8

L-PRO 4000 Transmission Line Protection Relay Overall L-PRO Accuracies Voltage Impedance Directional Phase Angle Frequency Elements Sync Check Elements Timers Inverse Overcurrent Timers Definite Overcurrent Timers Frequency Timer ±2.5% of inputs from 0.1 to 1.0 x nominal current (In) ± 1.0% of inputs from 1.0 to 40.0 x nominal current (In) ± 1.0% of inputs from 0.01 to 2.0 x nominal voltage (Vn) ±5.0% or 5 mQ of set value from 0.05 to 66.00 ohms secondary (0.25 to 330.00 ohms secondary 1 A nominal) ±2.0° of set value of Positive Sequence Line Angle value from 25.0° to 89.0° ±0.001 Hz (fixed...

Open the catalog to page 8
L-PRO 4000 - 9

Detailed Environmental Tests Test IEC/EN 61000-4-4 IEC/EN 60255-22-4 IEEE C37.90.1 Description Type Test Burst (fast transient) Surge Induced (conducted) RFI Power frequency Magnetic field Voltage dips & interrupts Test Points Signal ports ac power port dc power Port Earth ground ports Communication ports Signal ports ac power port dc power port Signal ports ac power port dc power port Earth ground ports Binary input ports: Class A Enclosure ports ac power port IEC 60255-11 Voltage dips & interrupts IEC/EN 61000-4-12 Damped oscillatory IEC/EN 61000-4-16 Mains frequency voltage...