Catalog excerpts
Feeder Protection Relay Digitally signed by Norbert Wegner DN: cn=Norbert Wegner, o=ERLPhase Power Technologies Ltd., ou, email=nwegner@erlphase.com, c=CA Date: 2018.05.18 15:09:20 -05'00' Product Overview F-PRO is the family of numerical multifunction relays suitable for transmission, distribution and industrial solutions. It provides complete feeder protection with current, voltage and frequency elements which can suit the requirements for variety of power automation applications. This product family is included with metering, communications, fault logs, disturbance recordings, sequence of events with 1ms time stamp resolution for analysis. Flexible I/O options, draw out construction of the relay cases, easy mounting and user friendly settings make easy maintenance and less time consumption to the end users. F-PRO can be integrated in to Serial (IEC 60870-5-103 (or) Modbus RTU) and Ethernet based communication (IEC 61850) with selectable electrical or fiber ports. This product is also enabled with Parallel Redundancy Protocol (PRP, IEC 62439-3) – optional while ordering. Application F-PRO provides current, voltage and frequency protections for Line, Generator, Motor, Bus bar, Reactor, Capacitor, etc., Rear side communication capability allows integration in to Smart Grid such as Substation Automation, Monitoring system and SCADA.
Open the catalog to page 1Measurements& Monitoring • Phase Voltages and Currents • Phase to Phase Voltages • Residual Voltage and Current • Sequence Voltages and Currents • Frequency and Phase Angles • Active Power, Reactive Power and Power factor • Total Harmonic Distortion (THD) • I2 t accumulated for CB Maintenance • |2 t for last operation • Percentage Thermal State • Monitoring - status of Digital Inputs and Relay Outputs • Monitoring - status of Prologic and Virtual Inputs Front: USB 2.0 port Rear: RS485, Ethernet - Cu/FO (Refer ordering sheet) Communication Protocol • Modbus RTU / ASCII • IEC60870 - 5 -...
Open the catalog to page 2Detailed Specifications Item General Operate Time Memory ProLogicTM Recording Transient (Fault) Events Quantity/Specs 1.0 to 1.5 cycles Settings and records are stored in non-volatile memory Records are stored in a circular buffer 20 statements per setting group 32 s/c oscillography of all analog and external input channels 1000 events with 1ms resolution including relay output operation 5 inputs per ProLogicTM statement Record Length : 1 to 20 sec Pre-fault Length : 0.1 to 0.5sec A compressed event record can be created for 1000 events with manual trigger. Record Capacity 20 records of a...
Open the catalog to page 4Auxiliary Power Supply Nominal Operating range Analog Inputs Rated current (In) : 1A or 5A AC - Site Selectable Rated Voltage (Un) : 63.5/69V AC PN or 110/120V AC PP Frequency : 50Hz / 60Hz (Site Selectable) Digital Outputs Carry Continuous : 8A AC or DC Make & Carry : 30A AC or DC for 0.2secods 5000VA AC Resistive Load Break : 1250 VA AC Resistive Load 50W DC Inductive Load @L/R <40msec with 110V DC Continuous Rating Short time Thermal Rating CT Circuit : 4X In AC (4 A for 1A CT) (20A for 5A CT) VT Circuit : 139 VAC Burden Physical Dimensions AC SEF Current AC Voltage Input Binary...
Open the catalog to page 5Current Voltage Directional Phase Angle Frequency Elements Sync Check Elements Timers Inverse Over current Timers Definite Over current Timers Frequency Timer ±2.5% of inputs from 0.1 to 1.0 x nominal current (In) ±1.0% of inputs from 1.0 to 4.0 x nominal current (In) ±1.0% of input from 0.01 to 2.0 x nominal voltage (Vn) ±5.0% of set Value ±0.01Hz (fixed level) ±0.01Hz/sec (df/dt) ±0.2 degrees ±3ms of set value ±2.5% or ±1 cycle of selected curve ±2.5% or ±1 cycle non-directional ±2.5% or ±1 cycle directional ±2.5% of set value plus 2.5 cycles of inherent delay (fixed level)...
Open the catalog to page 6INTENTIONALLY LEFT BLANK
Open the catalog to page 7INTENTIONALLY LEFT BLANK ERLPhase Power Technologies Ltd., 74 Scurfield Blvd, Winnipeg, MB, R3Y 1G4 Canada Tel: +1 204-477-0591 Fax: +1 204-478-1697 E-Mail: info@erlphase.com The policy of ERL is continuous improvement and development. The Company therefore reserves the right to supply equipment which may differ slightly from that described and illustrated in this publication (E00005R03). Technical Support: techsupport@easunreyrolle.com / support@erlphase.com www.easunreyrolle.com / www.erlphase.com
Open the catalog to page 8All ERLPhase catalogs and technical brochures
-
TESLA Portable
2 Pages
-
ERMLG
4 Pages
-
T-PRO 4000
8 Pages
-
L-PRO
8 Pages
-
Multi Busbar Protection Relay
14 Pages
-
RecordBase Central Station
2 Pages
-
S-PRO 4000
9 Pages
-
L-PRO 4000
9 Pages
-
B-PRO 4000
8 Pages
-
TESLA LITE
5 Pages
-
TESLA 4000
8 Pages