Product catalog summary
Product Overview: The nVent ERIFLEX Flexibar is a flexible electrical conductor made from thin layers of bare electrolytic copper. It is available in a range of sizes from 19.5 mm² to 1200 mm² and supports current ratings from 125 A to 2800 A. The product is insulated with high-resistance, self-extinguishing PVC, which covers less than 20% of the conductor, allowing for high flexibility.
Key Features:
  • Flexibility: The Flexibar can be easily bent, folded, and twisted, which enhances assembly flexibility, shortens connections, and reduces the installation footprint.
  • Installation: Connections can be made by punching and bolting through the copper laminates, clamping, or welding using nVent ERICO Cadweld, eliminating the need for lugs and reducing installation time.
  • Cost Efficiency: Offers weight and material savings compared to wire alternatives, reducing total installation costs.
  • Compliance and Testing: The product is 100% production dielectric tested and complies with UL 758 Appliance Wiring Material requirements for cold bend testing at -40°C and -50°C. It is also EAC and RoHS compliant.
Technical Specifications:
  • Length: 2000 mm
  • Material: Copper, Polyvinylchloride
  • Dielectric Strength: 20 kV/mm
  • Flammability Rating: UL 94V-0
  • Insulation Elongation: 370%
  • Insulation Thickness: 2 mm
  • Nominal Voltage: 1000 VAC, 1500 VDC
  • Working Temperature: -50 to 105 °C
  • Forming Temperature: 0 – 55 °C
  • Certifications: UL 67, UL 758, IEC 60439.1, IEC 61439.1, IEC 60695-2-11 (Glow Wire Test 960 °C)
Performance Data: The document provides a detailed table of current ratings for various part numbers, indicating the temperature rise (∆T) at different current levels (40 K, 50 K, 60 K). The table also includes dimensions and cross-sectional areas for each part number.
Warnings: nVent products must be installed and used according to the provided instruction sheets and training materials. Improper installation or misuse may lead to product malfunction, property damage, serious injury, or death, and may void the warranty.
Legal and Trademark Information: The document includes legal disclaimers and trademark information, noting that nVent reserves the right to change specifications without prior notice.
See more

Catalog excerpts

R1866-1

• Thin Layers of bare electrolytic copper formed into a stack • Full range from 19.5 mm2 up to 1200 mm2 and 125 A to 2800 A • Insulated by high-resistance, self-extinguishing PVC with Less than 20% contact with conductor for high flexibility • Easily bent, folded, and twisted, improving assembly flexibility, shortening connections, and decreasing footprint • Dramatically smaller and more flexible than comparable cable based on ampacity • Better power density than cable with lower skin effect ratio • Connections made by punching and bolting directly through the copper laminates, clamping onto the end of the nVent ERIFLEX Flexibar, or welding using nVent ERICO Cadweld • No lugs needed, reducing installation time and improving resistance to vibration • Weight savings and material savings compared to wire alternatives • Reduces total installation cost • Traceability codes and designation part numbers printed on insulation • 100% production dielectric tested • UL 758 Appliance Wiring Material requirements for Cold Bend testing at -40°C and -50°C (-40°F and -58°F) • EAC compliant • RoHS compliant Length: 2 000 mm Material: Copper, Polyvinylchloride Dielectric Strength: 20 kV/mm Flammability Rating: UL® 94V-0 Insulation Elongation: 370 % Insulation Thickness: 2 mm Nominal Voltage, UL/CSA/IEC: 1 000 VAC, 1 500 VDC Working Temperature: -50 to 105 °C Forming Temperature: 0 - 55 °C Certification Details: UL® 67, UL® 758 Complies With: IEC® 60439.1, IEC® 61439.1, IEC® 61439.1 Class II, IEC® 60695-2-1 1 (Glow Wire Test 960 °C)

 Open the catalog to page 1
R1866-2

ADMISSIBLE CURRENTS: This table indicates the temperature rise produced by chosen current in the given section. This calculation does not take into account the heat dissipation from the switch gear. AT = Temperature of conductors - Internal temperature of panel. Refer to technical documentation for additional ampacity ratings.

 Open the catalog to page 2
R1866-3

ABS is a registered certification mark of American Bureau of Shipping. IEC is a registered trademark of the International Electrotechnical Commission. UL, UR, cUL, cUR, cULus and cURus are registered certification marks of UL LLC. WARNING nVent products shall be installed and used only as indicated in nVent's product instruction sheets and training materials. Instruction sheets are available at www.erico.com and from your nVent customer service representative. Improper installation, misuse, misapplication or other failure to completely follow nVent 's instructions and warnings may cause product...

 Open the catalog to page 3

All ERICO catalogs and technical brochures

  1. R2411

    3  Pages

  2. R2119

    2  Pages

  3. R1913

    1  Page

  4. R1914

    1  Page

  5. R1930

    2  Pages

  6. R1966

    2  Pages

  7. R3500

    3  Pages

  8. R3548

    3  Pages

  9. R852

    1  Page

  10. R1985

    1  Page

  11. R2006

    1  Page

Archived catalogs

  1. Rail Contacts

    2  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.