The PECON+ system is designed to monitor the protective earth (PE) conductor in mobile machinery and equipment using frequency inverters and servo drives. It addresses the issue of increased operational leakage current, which can exceed the 3.5 mA limit set by DIN EN 50178/VDE 0160, necessitating a permanent PE connection.
Specifications
The PECON+ is a compact, DIN rail-mounted system that monitors single-phase (100 VAC) to three-phase (480 VAC) networks. It ensures the quality of the PE conductor and activates the machine's main contactor when safe. The device measures 75 x 45 x 125 mm, has a power loss of approximately 10 W, and an IP 20 protection rating.
Operation Principle
The system continuously checks the availability of the PE conductor. A green LED indicates normal operation, while a red LED signals a fault. It remains functional despite reverse polarity, although specific models (PECON+ S1/S3) require correct polarity.
Installation and Usage
The PECON+ is installed at the mains power feed-in point, with terminals L, N, and PE permanently connected. For networks without a neutral, the PECON+ IT variant is available. The system supports manual functionality testing via a front cover test button.
Safety and Compliance
Exceeding the 3.5 mA leakage current limit poses a safety risk, necessitating additional measures like a second PE conductor, isolation transformer, or PE monitoring (e.g., PECON+). The system complies with DIN EN 50178/VDE 0160 standards, ensuring safe operation in environments with high leakage currents.
Introduction
The document discusses the safety implications of electrical contact and the role of Residual Current Devices (RCDs) in ensuring personal safety. It highlights natural reflexes that may prevent injury upon contact with electricity but emphasizes the risks associated with prolonged contact with voltage-carrying components.
Risk Areas
Common risk areas include door handles, gear shifts, and climbing equipment, where contact with electricity can lead to muscle cramping and inability to let go, defined as the 'let-go limit' at 15 mA.
Role of RCDs
RCDs are praised for their effectiveness, but modern electrical systems, including inverters and charging concepts, often require additional measures due to leakage currents caused by Y-capacitors in RFI-filters.
Standards and Solutions
Standards by VDE, TÜV, and BG allow for leakage currents but require protective earthing to prevent dangerous potential rises. For leakage currents above 3.5 mA, solutions include installing a second protective earth, using an isolation transformer, or employing protective earth monitoring systems like PECON+.
Contact Information
The document is presented by EPA GmbH, with contact details provided for further inquiries.
See more

Catalog excerpts

EPA_PECON+-1

PECON+ Schutzleiterüberwachung für ein- und dreiphasige Netze Protective earth monitoring for single and three phase networks Produktinformation Product information Für den mobilen Einsatz von Frequenzumrichtern und Servoantrieben Die 3,5 mA-Grenze gemäß DIN EN 50 178 /VDE 0160 darf damit überschritten werden Für Netze mit Nennspannungen von 100 VAC bis 480 VAC mit oder ohne Neutralleiter* For mobile use of frequency inverters and servo drives The 3.5 mA-limit as per DIN EN 50 178 / VDE 0160 may be exceeded For networks with rated voltages of 100 VAC up to 480 VAC with or wit

 Open the catalog to page 1
EPA_PECON+-2

g Permanente Überwachung der Schutzleiterqualität g Kompakte Bauform g DIN-Hutschienenmontage g Permanent supervision of the protective conductor quality g Compact type g DIN rail mounting Schutzleiterüberwachung | Protective earth monitoring Hersteller von Maschinen und Geräten mit Steckeranschluss kennen das Problem: Durch den Einsatz moderner Antriebsregler wie z. B. Frequenzumrichter und Servoregler, kann der betriebsbedingte Ableitstrom des Gerätes bzw. der Maschine erhöht werden. Manufacturers of machinery and equipment with plug connectors are familiar with the problem: By use of modern...

 Open the catalog to page 2
EPA_PECON+-3

Das PECON+ ist eine Überwachungseinrichtung, die unmittelbar am Einspeisepunkt der mobilen Maschine installiert wird. Die Qualität des Schutzleiters wird durch das PECON+ permanent überwacht; ist diese in Ordnung, so gibt der integrierte Sicherheitskontakt des PECON+ das Hauptschütz der Maschine frei. PECON+ is a monitoring system that is installed directly into the equipment‘s mains power feed-in point. The quality of the protective earth will be monitored permanently through the PECON+; In a safe condition the safety contact will activate the mains contactor of the machine. Das nur 45 mm breite...

 Open the catalog to page 3
EPA_PECON+-4

Das PECON+ ermittelt messtechnisch die Verfügbarkeit des Schutzleiters und betätigt bei vorhandenem Schutzleiter ein internes Freigabe-Relais. The PECON+ unit takes readings to confirm availability of the PE conductor and, if a PE conductor is present, activates an internal status relay. Bei Betriebsbereitschaft des PECON+ leuchtet die grüne LED „OK“ im Frontdeckel. Arbeitsposition = Schutzleiter OK Once the PECON+ is operationally ready, the green „OK“ LED lights on the front cover. Operation position = PE conductor OK Bei Unterbrechung des Schutzleiters fällt das Freigabe-Relais im PECON+ ab....

 Open the catalog to page 4
EPA_PECON+-5

Neutralleiter zwingend | Neutral compulsory Klemme für ext. Prüftaste | Terminal for ext. test button gelbe LED leuchtet bei Verpolung | yellow LED lights up at reverse polarity vorhanden | available schaltet bei Verpolung | switches at reverse polarity zusätzlicher Meldekontakt | additional signal contact rote Alarm-LED leuchtet bei Verpolung | red alarm LED lights up at reverse polarity Verpolung L / N | Reverse polarity L / N Sichere Schutzleiterüberwachung in AC-Netzen | Safe protective earth monitoring in AC networks Betriebsspannung | Supply voltage EPA-Art.-Version | EPA-Art.-Nr. | EPA...

 Open the catalog to page 5
EPA_PECON+-6

Für alle PECON+ Modelle gilt | For all PECON+ Prüfbare Netze | Testable networks L/N/PE – L1/L2/L3/N/PE (PECON+ IT ohne N) L/N/PE – L1/L2/L3/N/PE (PECON+ IT without N) Normengrundlage | Underlining standards Betriebsspannung | Supply voltage PECON+ PECON+ PECON+ PECON+ PECON+ PECON+ PECON+ PECON+ PECON+ PECON+ PECON+ PECON+ Verlustleistung | Power loss Meldekontakt | Signal contact Montageart | Mounting type Befestigung auf Hutschiene nach DIN EN 50022 Mounting on DIN rail according to DIN EN 50022 Schutzart | Degree of protection Umgebungstemperatur | Ambient temperature Betrieb Lagerung Operation...

 Open the catalog to page 6
EPA_PECON+-7

Leakage current = Life threatening!? Ableitstrom größer als AC 3,5 mA: Lebensgefahr? Hersteller und Betreiber von Maschinen sowie ortsveränderlichen bzw. mobilen elektrischen Geräten betrifft das Thema gleichermaßen. Hat ein elektrisches Betriebsmittel bei bestimmungsgemäßer Verwendung dauerhaft einen höheren Ableitstrom als AC 3,5 mA (in manchen Regelwerken ist die Grenze auf AC 10 mA festgesetzt), so sind für seinen Betrieb besondere Vorschriften zu beachten. Leakage current exceeds 3.5 mA AC: Danger of life? Manufacturer and operators of machines as well as portable respectively mobile electrical...

 Open the catalog to page 7
EPA_PECON+-8

Alle Angaben ohne Gewähr auf Richtigkeit und Genauigkeit. | All information without liability for correctness and accuracy. Überreicht durch | Presented by: Fliederstraße 8, D-63486 Bruchköbel Deutschland / Germany Telefon / Phone: +49 (0) 6181 9704 - 0 Telefax / Fax: +49 (0) 6181 9704 - 99 E-Mail: [email protected] Internet: www.epa.de Marken – Geschäftliche Bezeichnungen Die erwähnten Firmen- und Produktnamen dienen ausschließlich der Kennzeichnung und werden als solche ohne Berücksichtigung eines eventuell bestehenden gewerblichen Schutzrechtes genannt. Das Fehlen der Kennzeichnung eines eventuell...

 Open the catalog to page 8