GI 1000 DSPG

GI 1000 DSPG

Product catalog summary
Technical and Functional Characteristics
  • The burner operates in two-stage progressive output and can be modulated continuously with a P.I.D. controller, which is ordered separately with a modulating kit.
  • Optimal combustion values are achieved by regulating combustion air and the blast-pipe.
  • Maintenance is simplified as the atomisation unit can be removed without detaching the burner from the boiler.
  • Air flow regulation for both stages is managed by an electric servomotor, which includes a pause closure of the gate to prevent heat dispersion.
  • The burner comes with an insulating seal for boiler fastening, two flexible hoses, and a line filter. The nozzle must be ordered separately based on the required flow.
Construction Characteristics
  • The burner includes a combustion air intake with an air flow adjustment device.
  • It features a boiler coupling flange with a hinge for easy dismantling of the atomising unit and deflector disk.
  • An air pressure switch ensures the presence of combustion air.
  • An electric servomotor with a mechanical cam regulates combustion air and fuel simultaneously.
  • The gear pump includes a pressure regulator, and the atomisation unit has a magnet to control outlet/nozzle return pins.
  • Automatic control and command equipment comply with European standard EN230, and flame detection is managed by photoresistance.
  • The on-board control panel includes a stop/go switch, automatic/manual and minimum/maximum selector, fuel change switch, and operation block.
  • There is a terminal block for electrical and thermostatic connections to the burner and for controlling the second stage of operation or connecting the electronic output regulator.
  • The electrical protection rating is IP40.
Specifications
  • The burner model GI 1000 DSPG operates within a thermal output range of 2500 to 10500 kW.
  • It conforms to E.M.C. Directive 89/336/CEE and L.V. Directive 73/23/CEE.
  • Available in both 50 Hz and 60 Hz frequencies, with specific part numbers for each.
  • Dimensions and weight are specified for packaging and installation requirements.
Accessories and Options
  • Accessories include a line filter, flexible hoses, and a boiler coupling kit.
  • Optional items include a modulation kit, modulating probe kit, and a nozzle with a 1-3 ratio.
  • The burner can operate with biodiesel according to European norm EN14213-FAME.
See more

Catalog excerpts

GI 1000 DSPG-1

Conform to: E.M.C. Directive 89/336/CEE L.V. Directive 73/23/CEE CONSTRUCTION CHARACTERISTICS The burner consists of: • Combustion air intake with air flow adjustment device. • Boiler coupling flange with hinge to facilitate dismantling of the atomising unit and deflector disk. • Air pressure switch to ensure the presence of combustion air. • Electric servomotor with mechanical cam for simultaneous regulation of combustion air and fuel. • Gear pump with pressure regulator. • Atomisation unit with magnet to control the outlet/nozzle return pins. • Automatic control and command equipment for the burner compliant with European standard EN230. Max visc. °E at 20°C Electrical supply • Flame detection by photoresistance. • On-board control panel comprising stop/go switch, automatic/manual and minimum/ maximum selector, fuel change switch and operation, block. • Terminal block for the electrical and thermostatic connections to the burner and to control the second stage of working or for the connection of the electronic output regolator. • Electrical protection rating IP40. To complete the burner GI 1000 DSPG Nozzle with 1-3 ratio (see page 229). Two-stage progressive/modulating light oil burner TECHNICAL AND FUNCTIONAL CHARACTERISTICS • Two-stage progressive output operation. for first and second stage by means of • Continuous modulation operation by electric servomotor with pause closure installing P.I.D. controller on control panel of gate to prevent any heat dispersion to (to be ordered separately with modulating flue. kit). • Equipped with one insulating seal for • Ability to obtain optimal combustion boiler fastening, 2 flexible hoses and values by regulating combustion air and one line filter; nozzle not included, to blast-pipe. be ordered separately depending on the • Maintenance facilitated by the fact that required flow. the atomisation unit can be removed without having to remove the burner from the boiler. • Minimum and maximum air flow regulation Modulating mode Part.no 98000055 Modulation kit (see page 228). Modulating probe kit (see page 228) Optionals Description Light oil burner accessories Line filter - Flex hoses - Boiler coupling kit Notes 4) Equipped with air closure device. Net calorific value of light oil: Hi = 42,70 MJ/kg = 10200 kcal/kg. 5) Biodiesel according to european norm EN14213-FAME. Net calorific value of light oil: Hi = 42,70 MJ/kg = 10200 kcal/kg.

 Open the catalog to page 1

All EOGB energy products ltd catalogs and technical brochures

  1. TBG 140 LX PN

    2  Pages

  2. TBG 80 LX PN

    2  Pages

  3. GI 510 DSPGN

    2  Pages

  4. GI 350 DSPGN

    2  Pages

  5. BTG 28 ME

    2  Pages

  6. TBG 45 P

    2  Pages

  7. TBG 35 P

    2  Pages

  8. SparkGas 35 P

    2  Pages

  9. SparkGas 30 P

    2  Pages

  10. TBG 45

    2  Pages

  11. TBG 60

    2  Pages

  12. TBG 35

    2  Pages

  13. BTG

    8  Pages

  14. GI

    1  Page

  15. BT

    2  Pages

  16. Spark 35 DSG

    1  Page

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.