LEAK_ALERT_75_80_Filter_Dust_Leak_Monitors_PCME_ENVEA
4Pages

{{requestButtons}}

Catalog excerpts

LEAK_ALERT_75_80_Filter_Dust_Leak_Monitors_PCME_ENVEA - 1

PCME LEAK ALERT 75/80 Filter Dust & Leak Monitors PROCESS & EMISSIONS MONITORING SYSTEMS (shown: LEAK ALERT 80) SPECIFIC FEATURES: Range of leak and dust monitors for control and monitoring of arrestment plant, especially bagfilters Versions with European (TUV & MCERTS) approvals as ‘filter dust monitors’ and ‘filter leak monitors’ and meeting US Standards for Bagfilters (MACT) Selection of advanced features and options for improved performance, incl. automatic internal zero and reference self-checks for regulatory compliance TUV APPROVED EN15859 MCERTS CLASS 2 &3 EQUIVALENT US ASTM D7392-07

Open the catalog to page 1
LEAK_ALERT_75_80_Filter_Dust_Leak_Monitors_PCME_ENVEA - 2

TECHNOLOGY SYSTEM DESCRIPTION LEAK ALERT 75/80 instruments are particularly suited for use on fabric-filter type dust collectors (baghouses), and provide reliable and robust monitoring of particulate dust levels and leaks from faulty bag media. With compact, cost-effective transmitter design, reliable monitoring can now be provided for all types of industrial filters. The instruments benefit from ENVEA’s unique ElectroDynamic™ Probe Electrification technology and advanced features enabling configuration for all types of bag filters irrespective of cleaning sequence, including an external...

Open the catalog to page 2
LEAK_ALERT_75_80_Filter_Dust_Leak_Monitors_PCME_ENVEA - 3

The Leak Alert 75/80 provides a full choice of user-selectable added-value features. These include the following options: Automatic insulator Short-Circuit Check for contamination detection ElectroDynamic™ sensors are tolerant to dust contamination of the sensor rod (unlike Triboelectric systems) due to the non-contact measurement principle; however, build-up of conductive material across the insulator at the base of the rod can lead to error (as with all Probe Electrification systems). For standard, dry dust collector applications contamination is unlikely, but a possibility. The...

Open the catalog to page 3
LEAK_ALERT_75_80_Filter_Dust_Leak_Monitors_PCME_ENVEA - 4

DIMENSIONS Leak Alert Sensor (shown with optional external display and keypad) Duct Connection 296 mm ORDER CODES LEAK ALERT 75/80 INSTRUMENT TYPE: 80 FILTER DUST MONITOR75 FILTER LEAK MONITOR Mechanical Options (1-5) PC Software Options (PC-ME DUST TOOLS) Sensor Features and Accessories (A-J, P) J Display Externally viewable standard ED Leak-Locate Capabilities Filter Display Module (req. F)*** option BPD *not available with insulated rod option * * standard on LEAK ALERT 80 sensors ***choose F or G (these options are exclusive; note that option P requires option F) Note: For details on...

Open the catalog to page 4