1. Catalogs
  2. ENTEC ELECTRIC & ELECTRONIC CO.,LTD
  3. Solid insulated vacuum recloser

Solid insulated vacuum recloser

Solid insulated vacuum recloser

Solid insulated vacuum recloser

Product catalog summary
General Features
ENHANCED TECHNOLOGY introduces a Solid Insulated Vacuum Recloser using hydrophobic cycloaliphatic epoxy materials. This recloser is designed for reliability, intelligent automation, and environmental friendliness, being oil and gas-free. It features a stainless steel enclosure with epoxy resin bushings, offering advantages like flexibility, arc resistance, and UV resistance. The control cubicle is insulated to minimize temperature variations and is protected against vermin and moisture.

Mechanism and Operation
The recloser operates with a magnetic actuator, reducing mechanical parts for high reliability and maintenance-free operation. It uses a low-voltage power source and a backup battery for independent operation, supporting SCADA and distribution automation. Integrated sensors provide overcurrent protection and measure various electrical parameters.

Control and Communication
The recloser supports programmable functions and data records, accessible via PC or remote communication. It supports DNP3.0, MODBUS, and IEC communication protocols. The EVRC2A control unit reduces automation costs and supports various communication protocols and SCADA capabilities.

Protection and Features
The recloser offers multiple protection features, including overcurrent, SEF, and synchronism checks. It supports user-programmable logic and enhanced fault detection algorithms. The ETR300-R control unit provides advanced protection, monitoring, and communication features, enhancing power quality management.

Technical Specifications
The recloser is rated for 50/60 Hz frequency, with control voltage options of 110-240VAC/125VDC. It operates in temperatures from -25 to 70°C and offers IP65 protection. It supports up to 10,000 mechanical and electrical operations.

Electrical Ratings
The recloser is available in different units (EPR-1, EPR-2, EPR-3) with varying electrical ratings, including maximum voltage, current, and withstand capabilities.

Contact Information
Distributor: 78-2 BUNCHEON-RI BONGDAM-EUP, HWASEONG-CITY, GYUNGGI-DO, KOREA. Tel: +82-31-299-8400, Fax: +82-31-227-1164, Email: [email protected]
See more

Catalog excerpts

Solid insulated vacuum recloser-1

ENhanced TEChnology Solid insulated vacuum recloser for power distrbution system thru 15kV, 27kV, 38kV

 Open the catalog to page 1
Solid insulated vacuum recloser-2

General features We, ENTEC introduce a Solid Insulated Vacuum Recloser encapsulated with Hydrophobic cycloaliphatic epoxy materials. The Solid Insulated Vacuum Recloser is designed for the inherently reliable, intelligent automation and environmentally friendly, completely oil free and gas free. the mechanism is enclosed in a powder coated stainless steel and Hydrophobic cycloaliphatic epoxy resin bushing is bolted on to the stainless steel enclosure. The Hydrophobic cycloaliphatic epoxy advantages are permanent flexibility, superior surface arc tracking resistance, hydrophobic preventing continuous...

 Open the catalog to page 2
Solid insulated vacuum recloser-3

The advantages of Hydrophobic cycloaliphatic epoxy encapsulation - Environmentally friendly, oil free and gas free - Proven performance in outdoor use - Compact, light weight, easy for transportation - Superior surface arc tracking resistance - Excellent hydrophobicity - Highly resistant against moisture absorption - Ultraviolet resistance - Outstanding tensile characteristics Pole Installation The advantages of magnetic actuator - Elimination of mechanical latches and associated linkage provide reliable, trouble free operation - Dramatic reduction in moving parts provides maintenance free and...

 Open the catalog to page 3
Solid insulated vacuum recloser-4

Microprocessor Based Recloser Control EVRC2A Features Reduced distribution automation costs RTU and control mounted in one control cubicle with space for modem DNP 3.0, MODBUS, IEC60870-5-101/104 communication protocols and SCADA capability 12Vdc ~ 24Vdc auxiliary power available for modem Voltage, current and power metering Record of operation, fault waveform data for line and load profile data Un-interruptable power supply with trip and close Inner heat insulation for polyurethane foaming Microsoft Windows-based EVRC2A interface software DynSync Software that can monitor and control a remote...

 Open the catalog to page 4
Solid insulated vacuum recloser-5

Remote Communication - Current - Voltage - Measures KW and KWH, power factor, demand Watts and VARs and frequency - Load profile data & oscillogram - RS-232 & 485 ports, RJ45(TCP/IP) - DNP3.0, MODBUS, IEC60870-5-101/104 Communication protocols - Built in RTU - Complete remotely access for recloser functions, settings metering and data records Microprocessor Based Recloser Control ETR300-R ETR300-R includes common features associated with EVRC2A and provides more enhanced functions in protection, monitoring, metering, communication and recorder. ETR300-R can also support your power distribution...

 Open the catalog to page 5
Solid insulated vacuum recloser-6

Technical Control Specifications RATINGS Rated frequency Control voltage ENVIRONMENTAL Ambient temperature range Outdoor(Humidity) Degree of protection Insulation test voltage Impulse voltage withstand Interference test withstand Radio frequency interference GENERAL PROTECTION (CT ratio 1000:1A) Phase time overcurrent Phase instantaneous overcurrent Ground time overcurrent Ground instantaneous overcurrent Sensitive earth fault Phase and ground time curves 50 or 60 Hz 110-240VAC / 125VDC Storage -40 to +85 Operation -25 to +70 100% IP65 2kV 50/60Hz, One minute 6kV Peak, 1.2/50 ANSI C62.45, IEC...

 Open the catalog to page 6
Solid insulated vacuum recloser-7

Construction H V terminal Vacuum interrupter Integrated sensors Hydrophobic Cycloaliphatic Epoxy Bushing water proof cabinet Open/Close indicator Manual trip and locking lever Manual closing shaft Magnetic actuator Electrical ratings Description Rated maximum voltage Continuous current Frequency Short circuit interrupting current Short time withstand current. 3sec Making current Cable charging interrupting current Transformer magn etizing interrupting current Basic impulse withstand voltage(1.2×50㎲) Power frequency withstand volt age, dry Power frequency withstand voltage, wet - Operating control...

 Open the catalog to page 7
Solid insulated vacuum recloser-8

Distributor : 78-2 BUNCHEON-RI BONGDAM-EUP HWASEONG-CITY GYUNGGI-DO KOREA TEL : + 82-31-299-8400 FAX : + 82-31-227-1164 http: //www.entecene.co.kr E-mail : [email protected]