Catalog excerpts
ENhanced TECnology
Open the catalog to page 1General Features Pad mount switchgear is designed for distribution automation system with combination of circuit breaker, load break switch and direct circuit. Multiple selection of load break switches and circuit breakers make the end user distribution line `s system more flexible. SF6 gas insulated switchgear and Solid insulated switchgear will provide full support with various choice of controls in order to complete distribution line system.
Open the catalog to page 2Ratings Item Rated Maximum voltage Rated continuous current Closed loop and load breaking current Cable charging breaking current Transformer magnetizing breaking current Short circuit breaking capacity Symmetrical short time current, 1 sec Peak withstand current Short circuit making current Basic impulse withstand voltage(1.2 x 50 ) Power frequency withstand voltage, dry DC withstand voltage, 15min. Corona extinction voltage kV A A A A kArms kArms kApeak kApeak kV kV kV kV Switchgear configureation Total Number of Circuit Total Number of Circuit Load Break Switch Circuit Break Switch...
Open the catalog to page 3Technical Features 1. Control Circuit Breaker/Load Break Switch controller, Protection Relay, FRTU, Modem can be placed Remote operation available (Built-In RTU : Option) 2. Load Break Switch(LBS) All circuit has independent operation function Each circuit has one operation hole to Close/Open/Earth Status Indicators of circuit breaker and load break switch are available Prevention of switching from Close to Earth by using 3 Position operations for LBS Operation Counter * 3-position operation Dual contacts : Enhanced Making and Disconnecting capacity Increased contact distance of Open status...
Open the catalog to page 45. Live-Line Indicator(Manual type switchgear) All circuit has independent operation function Close/Open operation by button in controller Earth operation is available on CB open status Indicators of circuit breaker status available Operation counter Live line indicator is provided on each circuit for safety 6. Voltage/Current sensing bushing 4. Gas Pressure gauge and valve (SF6 Gas type switchgear) Gas Pressure is indicated on Gauge Gas refilling valve available Current Transformer : 1000: 1 ratio (User`s choice) Accuracy : CVD type : 3 %(Standard), Resistor type P/T : 1%(option) Epoxy...
Open the catalog to page 5Controller Control Part Feeder Remote Terminal Unit Control Protection and Metering Dual Protection Relay : ETR-102 Protection Time Current Curve editable IEEE, IEC and 37 non-standard inverse time curves Protective settings in nonvolatile memory during power failure Delay time overcurrent protection(51P,51G) Instantaneous overcurrent protection(50P,50G) Negative sequence overcurrent protection(46) Cold load pickup and sequence coordination Underfrequency and load shedding(81) Undervoltage, overvoltage detection and alarm(27,59) Metering Voltage, Current Measures KW and KWH, Power factor...
Open the catalog to page 6Polymer(Solid) Type LOAD BREAK SWITCH
Open the catalog to page 778-2 BUNCHEON-RI BONGDAM-EUP HWASEONG-CITY GYUNGGI-DO KOREA TEL: +82-31-227-1161 FAX : +82-31-227-1164 http://www.entecene.co.kr E-mail : entec@entecene.co.kr
Open the catalog to page 8All ENTEC ELECTRIC & ELECTRONIC CO. catalogs and technical brochures
-
Solid Insulated Switchgear
20 Pages
-
SF 6 Gas Insulated Automatic
4 Pages
-
DC Switchgear
10 Pages
-
Solid Dielectric Ring Main Unit
12 Pages