Total Dissolved Gas Content

Total Dissolved Gas Content

Total Dissolved Gas Content

Product catalog summary
Overview: The document outlines the process and equipment specifications for analyzing Total Dissolved Gas Content (TDGC) in insulation liquids, specifically for oil-filled transformers, according to IEC 567 and IEEE C57.104-1991 standards. The analysis ensures high selectivity and sensitivity through a two-step process involving vacuum degassing and optional gas chromatographic analysis.
Analysis Procedure:
  • Step 1: Gas separation is achieved through a patented vacuum degassing method, which involves multi-periodical degassing using a four-step vacuum pump. This method ensures high sensitivity in gas separation.
  • Step 2 (Optional): A gas chromatographic analysis can be conducted following the determination of total gas content.
The entire process is controlled by a micro-processor, ensuring fast and reliable measurements.
Vacuum Degassing Method:
  • The method uses a vacuum chamber to separate gases, with a linear pressure sensor measuring the total gas content online.
  • The system allows for feedback of oil into the transformer and includes a heated transfer pipe for gas sample injection into the gas chromatograph.
Control and Evaluation:
  • The system is micro-processor controlled with a serial interface (RS 232) for data transfer to a remote computer.
  • Analysis intervals can be defined by the operator, and the system includes eight additional analog inputs for measuring other transformer parameters.
Display of Results:
  • Results are displayed in Vol% and stored in a databank, with options for viewing on a monitor, spreadsheet, or printed report.
  • Data can be transferred to a remote computer and stored in a log file, maintaining a history from the day of commissioning.
Equipment Specifications:
  • Type: Vacuum degassing procedure, oil- and mercury-free.
  • Vacuum Connections: DN 16 KF.
  • Vacuum Pump: Diaphragm pump, chemically resistant, three-stage, with a pumping speed of 2.0 m3/h.
  • Vacuum Sensor: Measuring range of 0.1 – 200 mbar, with a read-out of 5 per second.
  • Sample Volume: 50-100 ml.
  • Power Supply: 230 V, 50/60 Hz; 115 V, 50/60 Hz.
See more

Catalog excerpts

Total Dissolved Gas Content-1

Total Dissolved Gas Content ( TDGC ) for Insulation Liquids accord. To IEC 567 and IEEE C57.104-1991 Automatic analysis of the dissolved gases in oil-filled transformers The analysis is done in 2 steps which guarantee a very high selectivity and sensitivity of the determination of dissolved gases: 1. Gas separation by means of fully vacuum degassing ( accord. to DIN EN 60567, DIN IEC 599 and IEEE C57.104-1991) and display of results 2. Option: Subsequently to the determination of the total gas content a gas chromatographic analysis can be made. ENERGY SUPPORT Experts in providing mobile Solutions

 Open the catalog to page 1
Total Dissolved Gas Content-2

ENERGY SUPPORT Sperberweg 47 D - 41468 Neuss/Germany Both steps are synchronized via a micro-processor control thus a fast and reliable measurement procedure is guaranteed Vacuum Degassing A new invented vacuum degassing method (Patent pend. DE 102 52 652 4) degasses the oil sample multi-periodical. After extraction through a 4 step vacuum pump the gases are dosed into vacuum chamber and separated. The gases are evacuated from the vacuum chamber with a vacuum pump; therefore a very high sensitivity can be reached. The measuring principle is shown in fig, 1. In and outlet of the oil sample as...

 Open the catalog to page 2
Total Dissolved Gas Content-3

The injection of the gas sample into the gas chromatograph is via a fixed mounted and heated transfer pipe. An additional port for withdrawal of gas samples is installed. Control and Evaluation The system is controlled by a micro-processor; a serial interface (RS 232) allows transferring the data to a remote computer. The intervals of the analysis cycle can be freely defined by the operator (number of analysis/day or hour). The system has 8 additional analog inputs (0 -1 V) for the measurement of other transformer parameters (Oil temperature, winding temperature, ambient conditions etc.) The...

 Open the catalog to page 3
Total Dissolved Gas Content-4

ENERGY SUPPORT Sperberweg 47 D - 41468 Neuss/Germany Specification of vacuum degassing equipment: ENERG^^ SUPPORT Experts in providing mobile Solutions

 Open the catalog to page 4

All Energy Support catalogs and technical brochures

  1. MOBILE GC

    4  Pages

  2. SIGMA 2000

    2  Pages

  3. TOP TOGA GC

    3  Pages

  4. TDM 4000

    4  Pages

  5. ICMcompact

    3  Pages

  6. VLF-34E

    1  Page

  7. VLF28

    2  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.