EPC9513 - 1

Read this document carefully before using this device. The guarantee will be expired by device damages if you don’t attend to the directions in the user manual. Also we don't accept any compensations for personal injury, material damage or capital disadvantages. ENDA EPC9513 Series Programmable Profile Controller Thank you for choosing EPC9513 series programmable profile controller. * 96x96mm sized. * 3,5 inches TFT , graphic and 5 digit display. * Selectable TC, RTD, NTC, R, mA, V or mV inputs. * Input offset feature. * 32 point linearization for analog inputs. * Selectable relay, SSR,motorized valve or analog outputs. * Selectable , input proportional transmitter output(mA or V). * 50ms sampling time. * PID control. * PID selftune. * PID auto-tune. Selftune automatic PID calculation or manually enter PID parameters if known. * Soft-Start feature. * 24Vdc for sensor supply. * 16 program and 8 step for profile control. * Selectable Single Setpoint Mode or Profile Control Mode. * Digital inputs for profile control. * In case of sensor failure manually , periodical or auto-periodical control can be selected. * Security levels for menu and configuration pages. * RS485 ModBus protocol communication feature.(optional) * CE marked according to Europen Norms. PRESS SET TO START PROFILE CONTROLLER Analog Inputs Input Type B (Pt30Rh-Pt6Rh) E (NiCr-Con) J (Fe-Con) K (NiCr-Ni) L (Fe-Con) N (NiCrSi-NiSi) R (Pt13Rh-Pt) S (Pt10Rh-Pt) T (Cu-Con) U (Cu-Con) Pt100 NTC 0 - 20mA 4 - 20mA 0 - 150mV 0 - 5V 1 - 5V 0 - 10V 0 - 550Ω 0 - 10kΩ Input Resist. Cable Color + undefined - white + purple - white + black - white + green - white + red - blue + lilac - white + orange - white + orange - white + brown - white + red - brown Sensor current 250µA DIGITAL INPUTS (In order to use for profile control process) Start-Stop Input Pause-Resume Input Previous Program Input Next Program Input 250V AC, 2A . Selectable as NO+NC.10.000.000 switch without load and 200.000 switch under 250V AC 2A (resistive load) 250V AC, 2A . Selectable as NO+NC.10.000.000 switch without load and 200.000 switch under 250V AC 2A (resistive load) 250V AC, 2A . Selectable as NO.10.000.000 switch without load and 200.000 switch under 250V AC 2A (resistive load) Max. 40mA , 0 - 12Volt , short-circuit protection. 0 - 20mA or 4 - 20mA DC, % ±0,5 (Max. load resistance is 750Ω.) 0 - 10V DC, % ±0,5 Max. 30mA (short-circuit protection.) ELECTRICAL CHARACTERISTICS Supply Power consumption Wiring EMC Safety requirements 90-250V AC, 50/60Hz Max. 7VA 2.5mm² screw-terminal EN 61326-1: 2013 EN 61010-1: 2010 (Pollution degree 2 , overvoltage category ||) ENVIRONMENTAL CONDITIONS Ambient/storage temp. Max. Relative humidity Rated pollution degree Height 0 ... +50°C/-25 ... 70°C Relative humidity 80% for temperatures up to 31°C , decreasing linearly to 50% relative humidity at 40°C. According to EN 60529 Front panel : IP65 , Rear panel : IP20 Max. 2000m Do not use the device in locations subject to corrosive and flammable gases. HOUSING Housing type Dimensions Weight Enclosure material Suitable for flush-panel mounting. G96xY96xD81mm Approx. 400g. Self extinguishing plastics. While cleaning the device , solvents(thinner,gasoline,acid etc.) or corrosive materials must not be used. SİSEL MÜHENDİSLİK ELEKTRONİK SAN. VE TİC. A.Ş. Şerifali Mah. Barbaros Cad. No:18 Y.Dudullu 34775 ÜMRANİYE/İSTANBU

Open the catalog to page 1
EPC9513 - 2

PRESS SET TO START PROFILE CONTROLLER Flush mounting clamp For removing the device from panel : - While pressing both flush mounting clamps of the device in direction 1 , pull it in direction 2. Not : 1) Panel thickness should be maximum 7mm. 2) If there is no 60mm free space at the back side of the device , it would be difficult to remove it from panel. CONNECTION DIAGRAM ENDA EPC9513 is intended for installation in control panels. Make sure that the device is used only for intended purpose. The electrical connections must carried out by a qualified staff and must be according to the...

Open the catalog to page 2
EPC9513 - 3

HOME SCREEN Process Value Ouput/ Alarm Relay and SSR status. (If output is active,related led turns to green.) Program Number Segment Number Remaining time in min. % Output ratio Message box PRESS SET TO START PROFILE CONTROLLER Start/Stop profile controller in “Profile Controller Mode”, Select/Unselect parameter for increase/decrease parameter value in “Programming Mode”. Change SV in “Single Setpoint Mode”. Return previous page in “Programming Mode”. Enter main menu and open sub pages and transition between sub pages in “Programming Mode”. Pause/Resume profile controller in “Profile...

Open the catalog to page 3
EPC9513 - 4

Programming Home Screen Main menu is opened and “Programming Mode” is started by pressing Enter Key for 2 seconds. PRESS SET TO START PROFILE CONTROLLER EPC9513 PROFILE CONTROLLER Desired sub menu is selected by pressing Increase/Decrease Keys. Input Configuration Page Output Configuration Page Alarm Configuration Page PID Control Configuration Page Selected sub menu is opened by pressing Enter Key. Selected sub menu can be opened if permission is given from “Security Configuration Page”. Communication Configuration Page If Back Key is pressed or by waiting 10 seconds , parameters will be...

Open the catalog to page 4
EPC9513 - 5

Programming Programming Outputs(Output Configuration Page) Control Conf Output Conf Motorized Valve Conf Output Type Maxmimum Analog Output Value(%) Minimum Analog Output Value(%) Output Type : Relay, SSR,Motorized Valve,0-20mA, 4-20mA or 0-10V. If relay is not selected for output type , relay can be configured as Alarm3 or motorized valve. Re-Transmission : If output type is selected as relay or SSR , re-transmission can be selected as a 0/4-20mA or 0-10V. If output type is selected as a 0/4-20mA , re-transmission can be selected as a 0-10V. If output type is selected as 0-10V ,...

Open the catalog to page 5
EPC9513 - 6

Independent Alarm Set Value Deviation Alarm Set Value ON Alarm Status HIGH Band Alarm ON Alarm Status HIGH Alarm Hysteresis Alarm Hysteresis Alarm Hysteresis Set _ Alarm Set Value Value Set Alarm Set + Value Value Alarm Status HIGH Set Alarm Set + Value Value Band Alarm with Inhibition Alarm Status : HIGH Set Value+ Alarm Set Value Set Value+ Alarm Set Value Set Value Set Value- Alarm Set Value Set Value- Alarm Set Value Band alarm is possible Band alarm is possible Programming Programming PID Control (PID Control Configuration Page) PID Control Conf Proportional Band (%) Auto Tune Start...

Open the catalog to page 6