EPC9513

EPC9513
1 / 10 PagesView full catalog

EPC9513

Product catalog summary
Overview: The ENDA EPC9513 Series is a programmable profile controller designed for industrial automation. It features a 96x96mm size with a 3.5-inch TFT graphic display and supports various input types such as TC, RTD, NTC, R, mA, V, or mV. Key functionalities include PID control, self-tuning, auto-tuning, and a soft-start feature.
Specifications:
  • Input Types: Supports a wide range of temperature inputs and analog signals with high accuracy.
  • Outputs: Configurable for relay, SSR, motorized valve, or analog outputs.
  • Sampling Time: 50ms for precise control.
  • Profile Control: Capable of handling 16 programs with 8 steps each.
  • Communication: Optional RS485 ModBus protocol for system integration.
  • Environmental Conditions: Operates within 0 to +50°C and can be stored between -25 to 70°C.
Procedures:
  • Installation: Designed for flush-panel mounting with specific dimensions and space requirements.
  • Operation Modes: Includes Single Setpoint Mode and Profile Control Mode, with digital inputs for control.
  • Safety: Requires adherence to local regulations and protection against humidity, vibrations, and extreme temperatures.
Standards and Compliance:
  • CE marked and compliant with European norms such as EN 60751, EN 60584, and EN 61326-1: 2013.
  • Safety requirements according to EN 61010-1: 2010.
Recommendations:
  • Ensure proper electrical connections by qualified personnel.
  • Avoid using the device in environments with corrosive or flammable gases.
  • Regular maintenance and adherence to the user manual are crucial for optimal performance.
Key Features:
  • Security levels for menu and configuration pages.
  • Soft-start and PID tuning features for enhanced control.
  • Multiple input and output configurations for versatile applications.
Profile Controller Overview: The EPC9513 Profile Controller manages temperature profiles by sampling and saving process values every minute. It can be started with the Set Key, and the last saved program graph can be viewed using the Back Key.
Configuration Pages: The controller includes several configuration pages:
  • Input Configuration: Selection of input types and units, settings for input offset, digital filter coefficient, and decimal points.
  • Output Configuration: Configures output types and settings like maximum/minimum analog output values and hysteresis.
  • Alarm Configuration: Sets alarm values, types, and statuses, including behavior during probe failure.
  • PID Control Configuration: Adjusts PID parameters with auto-tuning and self-tuning features.
  • Communication Configuration: Enables Modbus communication with adjustable device address and baud rate.
  • Security Configuration: Controls page visibility and requires a security code for changes.
Programming and Control: Supports programming of profiles with multiple segments, each with configurable soft start times. Operates in profile control mode or single setpoint mode, with options for consistent control and behavior during power failures.
Alarms and Outputs: Alarms can be configured as independent, deviation, or band alarms, with options for inhibition. Outputs can be re-transmitted in various formats depending on the selected output type.
Graphical Representation: The Graph Page displays program numbers, set values, segment counts, and lengths, providing a visual overview of the programmed profile.
Communication and Operating Errors: Communication errors occur due to data corruption during transmission. Parity and CRC checks are recommended to prevent these. Operating errors occur when the data format is correct, but the function fails to execute, indicated by an error message with the most significant bit of the function code set to '1'.
MODBUS Error Messages: Error codes for MODBUS communication include:
  • 01 - Illegal Function: The function code is not allowed for the slave.
  • 02 - Illegal Data Address: The data address is not allowed for the slave.
  • 03 - Illegal Data Value: The value in the query data field is not allowed for the slave.
Programming Profile Controller: Configuration includes adjustable parameters such as program number, start delay, step count, repeat count, and segment times. Alarms can be configured for each segment, and a single setpoint can be activated if needed.
Parameter Information: Provides a detailed list of parameters, including input types, scale minimum and maximum, unit settings, digital filter coefficients, and alarm configurations. Each parameter is associated with a register address, minimum and maximum values, and default settings.
Modbus Address Map: Profile program parameters can be read or written via Modbus, starting from base address 1000. The document explains how to calculate the address for specific parameters based on the program number and segment.
Control Configuration: Outlines control configurations such as ON-OFF control, power failure behavior, and auto-tuning for PID parameters. Describes how to enable or disable features like linearization tables and profile control functions via Modbus.
Output and Alarm Status: Monitors the status of various outputs and alarms, including relay, SSR, and profile controller states, specifying how these statuses are represented in the system.
See more

Catalog excerpts

EPC9513-1

Read this document carefully before using this device. The guarantee will be expired by device damages if you don’t attend to the directions in the user manual. Also we don't accept any compensations for personal injury, material damage or capital disadvantages. ENDA EPC9513 Series Programmable Profile Controller Thank you for choosing EPC9513 series programmable profile controller. * 96x96mm sized. * 3,5 inches TFT , graphic and 5 digit display. * Selectable TC, RTD, NTC, R, mA, V or mV inputs. * Input offset feature. * 32 point linearization for analog inputs. * Selectable relay, SSR,motorized valve or analog outputs. * Selectable , input proportional transmitter output(mA or V). * 50ms sampling time. * PID control. * PID selftune. * PID auto-tune. Selftune automatic PID calculation or manually enter PID parameters if known. * Soft-Start feature. * 24Vdc for sensor supply. * 16 program and 8 step for profile control. * Selectable Single Setpoint Mode or Profile Control Mode. * Digital inputs for profile control. * In case of sensor failure manually , periodical or auto-periodical control can be selected. * Security levels for menu and configuration pages. * RS485 ModBus protocol communication feature.(optional) * CE marked according to Europen Norms. PRESS SET TO START PROFILE CONTROLLER Analog Inputs Input Type B (Pt30Rh-Pt6Rh) E (NiCr-Con) J (Fe-Con) K (NiCr-Ni) L (Fe-Con) N (NiCrSi-NiSi) R (Pt13Rh-Pt) S (Pt10Rh-Pt) T (Cu-Con) U (Cu-Con) Pt100 NTC 0 - 20mA 4 - 20mA 0 - 150mV 0 - 5V 1 - 5V 0 - 10V 0 - 550Ω 0 - 10kΩ Input Resist. Cable Color + undefined - white + purple - white + black - white + green - white + red - blue + lilac - white + orange - white + orange - white + brown - white + red - brown Sensor current 250µA DIGITAL INPUTS (In order to use for profile control process) Start-Stop Input Pause-Resume Input Previous Program Input Next Program Input 250V AC, 2A . Selectable as NO+NC.10.000.000 switch without load and 200.000 switch under 250V AC 2A (resistive load) 250V AC, 2A . Selectable as NO+NC.10.000.000 switch without load and 200.000 switch under 250V AC 2A (resistive load) 250V AC, 2A . Selectable as NO.10.000.000 switch without load and 200.000 switch under 250V AC 2A (resistive load) Max. 40mA , 0 - 12Volt , short-circuit protection. 0 - 20mA or 4 - 20mA DC, % ±0,5 (Max. load resistance is 750Ω.) 0 - 10V DC, % ±0,5 Max. 30mA (short-circuit protection.) ELECTRICAL CHARACTERISTICS Supply Power consumption Wiring EMC Safety requirements 90-250V AC, 50/60Hz Max. 7VA 2.5mm² screw-terminal EN 61326-1: 2013 EN 61010-1: 2010 (Pollution degree 2 , overvoltage category ||) ENVIRONMENTAL CONDITIONS Ambient/storage temp. Max. Relative humidity Rated pollution degree Height 0 ... +50°C/-25 ... 70°C Relative humidity 80% for temperatures up to 31°C , decreasing linearly to 50% relative humidity at 40°C. According to EN 60529 Front panel : IP65 , Rear panel : IP20 Max. 2000m Do not use the device in locations subject to corrosive and flammable gases. HOUSING Housing type Dimensions Weight Enclosure material Suitable for flush-panel mounting. G96xY96xD81mm Approx. 400g. Self extinguishing plastics. While cleaning the device , solvents(thinner,gasoline,acid etc.) or corrosive materials must not be used. SİSEL MÜHENDİSLİK ELEKTRONİK SAN. VE TİC. A.Ş. Şerifali Mah. Barbaros Cad. No:18 Y.Dudullu 34775 ÜMRANİYE/İSTANBU

 Open the catalog to page 1
EPC9513-2

PRESS SET TO START PROFILE CONTROLLER Flush mounting clamp For removing the device from panel : - While pressing both flush mounting clamps of the device in direction 1 , pull it in direction 2. Not : 1) Panel thickness should be maximum 7mm. 2) If there is no 60mm free space at the back side of the device , it would be difficult to remove it from panel. CONNECTION DIAGRAM ENDA EPC9513 is intended for installation in control panels. Make sure that the device is used only for intended purpose. The electrical connections must carried out by a qualified staff and must be according to the relevant...

 Open the catalog to page 2
EPC9513-3

HOME SCREEN Process Value Ouput/ Alarm Relay and SSR status. (If output is active,related led turns to green.) Program Number Segment Number Remaining time in min. % Output ratio Message box PRESS SET TO START PROFILE CONTROLLER Start/Stop profile controller in “Profile Controller Mode”, Select/Unselect parameter for increase/decrease parameter value in “Programming Mode”. Change SV in “Single Setpoint Mode”. Return previous page in “Programming Mode”. Enter main menu and open sub pages and transition between sub pages in “Programming Mode”. Pause/Resume profile controller in “Profile Controller...

 Open the catalog to page 3
EPC9513-4

Programming Home Screen Main menu is opened and “Programming Mode” is started by pressing Enter Key for 2 seconds. PRESS SET TO START PROFILE CONTROLLER EPC9513 PROFILE CONTROLLER Desired sub menu is selected by pressing Increase/Decrease Keys. Input Configuration Page Output Configuration Page Alarm Configuration Page PID Control Configuration Page Selected sub menu is opened by pressing Enter Key. Selected sub menu can be opened if permission is given from “Security Configuration Page”. Communication Configuration Page If Back Key is pressed or by waiting 10 seconds , parameters will be saved...

 Open the catalog to page 4
EPC9513-5

Programming Programming Outputs(Output Configuration Page) Control Conf Output Conf Motorized Valve Conf Output Type Maxmimum Analog Output Value(%) Minimum Analog Output Value(%) Output Type : Relay, SSR,Motorized Valve,0-20mA, 4-20mA or 0-10V. If relay is not selected for output type , relay can be configured as Alarm3 or motorized valve. Re-Transmission : If output type is selected as relay or SSR , re-transmission can be selected as a 0/4-20mA or 0-10V. If output type is selected as a 0/4-20mA , re-transmission can be selected as a 0-10V. If output type is selected as 0-10V , re-transmission...

 Open the catalog to page 5
EPC9513-6

Independent Alarm Set Value Deviation Alarm Set Value ON Alarm Status HIGH Band Alarm ON Alarm Status HIGH Alarm Hysteresis Alarm Hysteresis Alarm Hysteresis Set _ Alarm Set Value Value Set Alarm Set + Value Value Alarm Status HIGH Set Alarm Set + Value Value Band Alarm with Inhibition Alarm Status : HIGH Set Value+ Alarm Set Value Set Value+ Alarm Set Value Set Value Set Value- Alarm Set Value Set Value- Alarm Set Value Band alarm is possible Band alarm is possible Programming Programming PID Control (PID Control Configuration Page) PID Control Conf Proportional Band (%) Auto Tune Start Selftune...

 Open the catalog to page 6