TRANS-SYNCRO AUTO START LOAD SHARE UNIT 1. Introduction 1.1 General Specifications TRANS-SYNCRO is an synchronising & load sharing unit for diesel, gas or gasoline generators. The unit is an easy to use multi-generator loadshare system, designed to synchronise up to 32 generators including electronic and non-electronic engines. The unit has got the “Event Log” that will record last 500 events. General Specifications: - Multi genset load sharing (up to 32 gensets) - kW and kV Ar load sharing - Busbar voltages and frequency measurements - Dead bus sensing - Bus failure detection - Sequential set start - Load dependent automatic start/stop - Equal aging of gensets - Manual voltage/frequency adjustment - Direct/Reverse Governor and AVR control - Auto adjust feature for Governor and AVR - Volts, frequency and phase matching - Synchroscope display - Logic Controller functionality for PLC - Black or gray theme selection for 4.3" TFT LCD screen 1.2 Warranty EMKO Elektronik warrants that the equipment delivered is free from defects in material and workmanship. This warranty is provided for a period of two years. The warranty period starts from the delivery date. This warranty is in force if duty and responsibilities which are determined in warranty document and instruction manual performs by the customer completely. 1.3 Maintenance Repairs should only be performed by trained and specialized personnel. Cut power to the device before accessing internal parts. Do not clean the case with hydrocarbon-based solvents (Petrol, Trichlorethylene etc.). Use of these solvents can reduce the mechanical reliability of the device. Use a cloth dampened in ethyl alcohol or water to clean the external plastic case. Introduction Brochure. ENG TRANS-SYNCRO 01 V37 01/2

 Open the catalog to page 1
TRANS-SYNCRO AUTO START LOAD SHARE UNIT-2

Before beginning installation of this product, please read the instruction manual and warnings below carefully. A visual inspection of this product for possible damage occured during shipment is recommended before installation. It is your responsibility to ensure that qualified mechanical and electrical technicians install this product. If there is danger of serious accident resulting from a failure or defect in this unit , power off the system and seperate the electrical connection of the device from the system. Keep the power off until all of the wiring is completed so that electric shock and...

 Open the catalog to page 2
TRANS-SYNCRO AUTO START LOAD SHARE UNIT-3

2.3 Electrical Connection TRANS-SYNCRO three phase connections schematic MULTI LINK RS485 COMMUNICATION COMMUNICATION (CAN OPEN) Sender Common Level Sender or Configurable Analog Input-1 To Engine Earth Temperature Sender BATTERY Configurable Analog Input-2 Generator Contactor Output Connect screen at generator only Connect screen at generator only 1- Connect the unit as shown in the appropriate diagram. Be sure to connect the battery supply the right way round. External fuse is recommended. Stranded cable cross section: 1,5mm2, Solid cable cross section: 2,5mm2, The stripping length is 7 to...

 Open the catalog to page 3
TRANS-SYNCRO AUTO START LOAD SHARE UNIT-4

Operation Screen Operator setting Technician setting Factory adjustment When the Prog button is pressed, the parameters section is asked for accessing to parameters. Press the Up or Down buttons to select the section you wish to view/change. Operator setting Technician setting Factory adjustment Press the Enter (t button. Enter password with cursor (Right, Left, Up and Down) buttons. TECHNICIAN SETTING Notel: If Enter button is pressed and the technician password is zero, Password screen is ignored. Press the Enter button to confirm password. If the password is incorrect, the unit will drop out...

 Open the catalog to page 4
TRANS-SYNCRO AUTO START LOAD SHARE UNIT-5

014.Under volt set 015.Under volt actions 016.Under volt actions delay 003.Under volt prealarm 004.Under volt prealarm reset 017.Under volt prealarm delay 018.Over volt set 019.Over volt actions © © © Press the Enter button to view parameter value. 03.01.GENERATOR VOLT LEVEL 001.Nominal voltage 400 Vac Parameter can be changed with Up and Down buttons. 03.01.GENERATOR VOLT LEVEL 001.Nominal voltage 405 Vac © © © Press Enter button to confirm the changed value. 014.Under volt set 015.Under volt actions 016.Under volt actions delay 003.Under volt prealarm 004.Under volt prealarm reset 017.Under...

 Open the catalog to page 5
TRANS-SYNCRO AUTO START LOAD SHARE UNIT-36

Relay Outputs : Generator contactor output 8A at DC supply voltage Configurable output-10 8A at DC supply voltage : Fuel or Configurable output-1 15A at DC supply voltage Crank or Configurable output-2 15A at DC supply voltage Configurable output-3,4,5,6,7,8,9 1A at DC supply voltage : , , Transistor Outputs 6. Other Informations Manufacturer Information: Emko Elektronik Sanayi ve Ticaret A.Þ. Bursa Organize Sanayi Bölgesi, Fethiye OSB Mah. Turkuaz Cad. No:15 16215 Nilüfer - BURSA / TÜRKÝYE Phone : +90 224 261 19 00 Fax : +90 224 261 19 12 Repair and maintenance service information: Emko Elektronik...