EMG - EMCO Exciters and PMG Brushless exciters systems - For electrics alternators - Exciters for power stations alternators.
Open the catalog to page 1specializes in Brushless exciters systems for power stations alternators and produces machines from 20 KW (600 mm diameter) to more than 300 KW (2400 mm diameter) covering the entire market needs . The Exciters which we offer are designed to be assembled directly on the shaft of the main alternator without modification. They are provided with a rotating rectifier bridge and they are adapted to each alternator : Electric characteristics, shaft diameter, mechanical fixations. Furthermore, they can replace existing commutator exciters on hydraulic alternators in order to obtain a brushless...
Open the catalog to page 2exciters are made as follows : • The rotor is assembled directly on a main alternator shaft, and is constructed with a varnished electrical lamination , windings are made of enameled wire or copper bars and which are fixed to the rotating rectifier bridge. The stator is manufactured with magnetic lamination . The number of poles define the frequency of exit (between 4 and 80 poles, according to the nominal RPM of the main alternator). Low speeds, from 100 to 1800 RPM, for hydraulic applications or diesels. Hight speeds, from 3000 to 3600 RPM, for turbo alternators.
Open the catalog to page 3Exciters associated with the rotating rectifier bridge The current generated by the exciter must be rectified to be injected into the polar wheel of the main alternator, it's the job of the rotating rectifier. It consists generally of 6 diodes and can be equipped with over voltage protection or other safety devices. Optimum reliability is obtained by use of a rectifier equipped only with diodes. Exciter stator is fed by a voltage regulator. Electric diagram. The exciters can be supplied with P M G : Exciter system with P M G (permanent magnet generators).
Open the catalog to page 5Exciters for Hydro-electric Power Stations : The majority of hydro-electric power stations were built before 1970. Today with new technologies, these power stations can increase their production of energy by 20% by renovating the unit harnesses alternator. The infrastructure is preserved, this relatively inexpensive solution is used worldwide. With these modifications, the exciter system easily be modified to brushless system. is one of the few companies worldwide who can offer the transformation of these original exciters to brushless exciters by re-using the original magnetic circuit thus...
Open the catalog to page 6specializes in exiters and PMG. We can provide new alternators for hydraulic production or for renewing machines. We can also offer a total solution for you including voltage regulators.
Open the catalog to page 7The advantages of Brushless exciters : • • • • • • • No maintenance No replacement of brushes. No pollution in main the alternator and exciter. Better insulation of the main alternator. Increased alternator life. Possibility of autonomous functioning of the block with a PMG alternator The restoration, replacement of rings or exciter comutators with brusless exciters. Exciter rotor with rectifier bridge for hydraulic machine
Open the catalog to page 8Exciter rotor in place with main alternator 1500 RPM on balancing tool Exciter rotor for tubo alternator 3000 RPM
Open the catalog to page 9Exciter with rectifier bridge and PMG 3000 RPM EMG exciter on horizontal hydraulic alternator 80 MW 600 RPM
Open the catalog to page 10All EMG-EMCO catalogs and technical brochures
-
Series DH/GH DC Motors
2 Pages
-
DIRECT CURRENT MOTORS GH225-450
122 Pages
-
DC MOTORS MARINE& OFFSHORE
2 Pages
-
ISO 9001-2015 certificate
1 Pages
-
General catalogue
4 Pages
-
PMG
23 Pages
-
Hydro Brushless Exciter
23 Pages
-
MILL DC motor
2 Pages
-
PMG general catalogue
4 Pages
-
ACor DC motor comparison
7 Pages
-
400 Hz Frequency converter
1 Pages