VAREC 5000/5010 SERIES FLAME ARRESTERS Group ‘D’ end-of-line flame arresters with a unique extensible bank frame designed to stop the propagation of flame from external sources FEATURES • Models available for vertical or horizontal configurations. • Heavy wall cast housing in 356 T6 aluminum, carbon steel or 316 stainless steel. • Net free area through banks three to four times the unit pipe size, resulting in increased flow capacity with minimal pressure drop. • Bank’s large surface area improves heat dissipation. • Removable cover plate and extensible bank assembly for easy inspection, cleaning or replacement. • Unitized housing does not require support for proper bank alignment during maintenance. • ‘Off-set’ housing design ensures flow capacity unaffected by condensate accumulation, even when installed in horizontal piping. • 5010 Series ½” NPT drain plug at the low point is located conveniently for routine draining*. • UL approved**. 5000 SERIES VERTICAL GENERAL APPLICATION TECHNICAL DATA The 5000 and 5010 Series, Group ‘D’, end-ofline flame arresters are used in gas piping systems, petroleum storage tank roofs and digester covers to prevent the propagation of a flame into the system. © 2017 Emerson. All Rights Reserved. Sizes: Connections: Pressure rating: Aluminum, carbon steel, stainless steel 2” to 12” (50 to 300 mm) Drilled flanges To 10 psi (0.7 bar) * A Varec drip trap should be specified for field installation at this connection to provide for safe removal of condensate. ** For approved sizes pl
Open the catalog to page 1MODELS OVERVIEW EXTENSIBLE ALUMINUM BANK FRAME 5000 and 5010 Series flame arresters stop the propagation of a flame by absorbing and dissipating heat through the surface area of the bank sheets. Ignited vapor attempting to pass through the arrester is forced through small passages within the bank assembly. Heat is absorbed, lowering the temperature of the gas below its ignition point and quenching the flame. 5000 Series is for vertical installation; 5010 Series is for horizontal or vertical installation. They can be mounted up to 15 feet (4.6 m) upstream of the ignition source in accordance with...
Open the catalog to page 2VAREC 5000/5010 SERIES FLAME ARRESTERS DIMENSIONS AND WEIGHTS 5000 SERIES Gas flow either direction Bank removal clearance Gas flow either direction Bank removal clearance DIMENSIONS, INCHES AND POUNDS (millimeters and kilograms) Size code Nominal pipe size Flange drilling per ANSI Class 150 flat face flange (aluminum); per ANSI Class 150 raised face flan
Open the catalog to page 3VAREC 5000/5010 SERIES FLAME ARRESTERS FLOW CURVES 5000 AND 5010 FLAME ARRESTERS Pressure Ounces per square inch Vacuum Ounces per square inch Thousand cubic feet/hour at 60°F and 14.7 psia air flow (SCFH)
Open the catalog to page 4VAREC 5000/5010 SERIES FLAME ARRESTERS FLOW CURVES Combination 2010B valve and 5000 flame arrester, set at 0.865 inch of water Curve data by actual tests in accordance with API Std. 2000. Certified test data by independent laboratory available on request Pressure Inches of water Thousands of cubic feet/hour at 60°F and 14.7 psia, air flow (SCFH) Vacuum Inches of water Thousands of cubic feet/hour at 60°F and 14
Open the catalog to page 5VAREC 5000/5010 SERIES FLAME ARRESTERS FLOW CURVES Combination 2010B valve and 5000 flame arrester, set at 1 inch of water Curve data by actual tests in accordance with API Std. 2000. Certified test data by independent laboratory available on request Pressure Inches of water Thousands of cubic feet/hour at 60°F and 14.7 psia, air flow (SCFH) Vacuum Inches of water Thousands of cubic feet/hour at 60°F and 14
Open the catalog to page 6VAREC 5000/5010 SERIES FLAME ARRESTERS FLOW CURVES Combination 2010B valve and 5000 flame arrester, set at 2 inches of water Curve data by actual tests in accordance with API Std. 2000. Certified test data by independent laboratory available on request Pressure Inches of water Thousands of cubic feet/hour at 60°F and 14.7 psia, air flow (SCFH) Vacuum Inches of water Thousands of cubic feet/hour at 60°F and 14
Open the catalog to page 7VAREC 5000/5010 SERIES FLAME ARRESTERS FLOW CURVES Combination 2010B valve and 5000 flame arrester, set at 4 inches of water Curve data by actual tests in accordance with API Std. 2000. Certified test data by independent laboratory available on request Pressure Inches of water Thousands of cubic feet/hour at 60°F and 14.7 psia, air flow (SCFH) Vacuum Inches of water Thousands of cubic feet/hour at 60°F and 14.7 psia, air flow (SCFH)
Open the catalog to page 8VAREC 5000/5010 SERIES FLAME ARRESTERS FLOW CURVES Combination 2010B valve and 5000 flame arrester, set at 6 inches of water Curve data by actual tests in accordance with API Std. 2000. Certified test data by independent laboratory available on request Pressure Inches of water Thousands of cubic feet/hour at 60°F and 14.7 psia, air flow (SCFH) Vacuum Inches of water Thousands of cubic feet/hour at 60°F and 14
Open the catalog to page 9Model 50 Flame arrester Housing/bank assembly frame/sheet material 1 Aluminum/aluminum (extensible frame)/aluminum 2 Aluminum/aluminum (extensible frame)/316 stainless steel 3 Carbon steel/316 stainless steel (fixed frame)/316 stainless steel 6 316 stainless steel/316 stainless steel (fixed frame)/316 stainless steel Hardware material S Stainless steel * Zn plated carbon steel (standard) - leave blank