Lye Peeling of Fruits and Vegetables

Lye Peeling of Fruits and Vegetables

Lye Peeling of Fruits and Vegetables

Product catalog summary
Background
The document discusses the process of lye peeling for fruits and vegetables, which involves using caustic soda (NaOH) to prepare produce for peeling and canning. The concentration of the caustic solution is crucial to ensure effective peeling without damaging the produce.
The Measurement
Maintaining the correct concentration of caustic in the treatment bath is essential. The typical process involves heating an open tank of caustic to 170–220 °F (76–105 °C) with live steam, with caustic concentrations ranging from 3 to 15%. The exposure time is usually under 5 minutes, followed by washing to remove caustic residues.
Concentration Measurement
Due to caustic being carried out by the product, the bath needs constant replenishment. Conductivity measurement, particularly using toroidal sensors, is recommended to monitor and maintain the caustic concentration. The buildup of salts from peels and contaminants affects conductivity, necessitating adjustments to the measurement curve based on operating data.
Important Considerations
Selection of the appropriate toroidal conductivity sensor depends on the level of suspended solids in the bath. Data collection over the life of three baths is advised to establish a reliable conductivity-concentration relationship. Adjustments to the conductivity set point may be needed as the bath ages.
Process
The process involves using toroidal conductivity sensors (models 226 and 228) and analyzers to ensure accurate monitoring. These instruments offer features like automatic temperature compensation and customizable concentration curves.
Instrumentation
The document highlights the use of Emerson's toroidal conductivity sensors and analyzers, which are designed for chemical resistance and provide clear displays and communication protocols for effective monitoring.
See more

Catalog excerpts

Lye Peeling of Fruits and Vegetables-1

Food & Beverage Application Data Sheet Lye Peeling of Fruits and Vegetables Background Many fruits and vegetables are prepared for peeling and canning by exposure to caustic (NaOH). To ensure adequate and consistent peeling, the concentration of caustic in the treatment bath must be maintained at an effective strength. At the same time, if the caustic bath is too strong the fruit or vegetable can be damaged. Process The typical process consists of an open tank of caustic heated to 170–220 °F (76–105 °C) by live steam. The target caustic concentration can vary from 3 to 15 %. Exposure time for the product is usually 5 minutes or less, after which the product is placed on moving grates and washed by high pressure nozzles to remove entrained caustic. A significant amount of caustic is carried out by the product, so the bath must be continually replenished to maintain an adequate volume of caustic solution and a caustic concentration at the target value. This could involve addition of water, based on level control, as well as makeup caustic, based on the conductivity measurement. The best place to start is to look at how the bath behaves and how concentration is maintained manually. Since the background increase cannot be distinguished from the conductivity due to the caustic, the conductivity set point (or calibration curve for a concentration measurement) may need to change as the bath ages. This effect will be smaller for higher caustic concentrations and for shorter intervals between bath replacement. Concentration Measurement In general, when there is background conductivity, the conductivity versus concentration curve will not be the same as the standard curve for caustic (NaOH) in distilled water, due to buildup of salts in the bath. The curve must be developed from operating data, i.e. conductivity and titrated caustic concentrations. Data should be taken over the life of at least three (3) baths; the age of the bath and any additions to the bath should be noted, in addition to the conductivity and titrated caustic concentration. Once a curve has been developed, the on-line measurement can usually be corrected for salt build-up by standardization following a routine laboratory titration. Important Considerations The Measurement Due to its resistance to fouling, toroidal conductivity is the best measurement technique here. The conductivity sensor is typically mounted in the holding tank (Figure 1). Relatively clean processes may use the 228 sensor, but applications with potential for heavy coating should use the large bore 226 sensor. As the bath ages, there is a buildup of salts, which are leached out of the peels and carried in with dirt and other suspended contaminants. This buildup causes an increase in the background conductivity. Select the toroidal conductivity sensor based on how heavily the bath is loaded with suspended solids. When evaluating how to control bath concentration and volume, how the bath behaves and how it is manually controlled should be thoroughly examined. When setting up a concentration measurement, data should be taken over the life of three (3) baths to determine the relationship between conductivity and concentration.

 Open the catalog to page 1
Lye Peeling of Fruits and Vegetables-2

Food & Beverages Instrumentation 226 and 228 Toroidal Conductivity Sensors 1066 Toroidal Conductivity Analyzer Toroidal (inductive) principle of measurement and construction Chemically-resistant materials of construction 4–20 mA output with superimposed HART® or FOUNDATION™ Fieldbus communications protocol Clear, Large, easy-to-read display Customizable percent concentration curve Automatic/manual temperature compensation ensures accurate monitoring and control Figure 1 - Lye Peeling of Fruits and Vegetables Fruit or Vegetables Washers Holding Tank www.RosemountAnalytical.com www.analyticexpert.com...

 Open the catalog to page 2

All Emerson Automation Solutions - ROSEMOUNT catalogs and technical brochures

  1. FRL Accessories

    14  Pages

  2. TankRadar Pro

    32  Pages

  3. Roxar PTPT15K

    2  Pages

  4. SW-300

    4  Pages

  5. DL8000

    12  Pages

  6. AMS Suite

    16  Pages

  7. Line Card

    2  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.