HART standard or OCX 8800 Oxygen/Combustibles Transmitter
16Pages

{{requestButtons}}

Catalog excerpts

HART standard or OCX 8800 Oxygen/Combustibles Transmitter - 1

OCX 8800 Product Data Sheet Oxygen/Combustibles Transmitter ■ Oxygen and combustibles measurements in a single, easy-to-install transmitter design ■ Integral or remote-mounted electronics options - The first and only oxygen and combustibles analyzer to support FOUNDATION® fieldbus - HART® and AMS/PlantWeb® compatible - Air purge cycle and improves cell calibration - Optional factory built auto-calibration panel - Internal filter for use in higher than normal particulate levels* - Additional in situ filters - Large surface area filter for higher particulate levels - Stainless steel and hastelloy filters - Optional HART wireless communications - ATEX, FM, CSAType4X/IP66, lECEx, CE, NEPSI + Application form must be completed for coal-fired or other applications with high particulate levels ROSEMOUNT* EMERSON.

Open the catalog to page 1
HART standard or OCX 8800 Oxygen/Combustibles Transmitter - 2

Continued Improvements of the Oxygen/Combustibles Transmitter Emerson continues to enhance the design of the Rosemount Analytical OCX product line through continuous innovation. Improvements to the combustibles sensor and software to enhance the reliability of these measurements are primary reasons that the OCX leads the industry. The new sensor design and software upgrades make the OCX 8800 even more dependable. The power of this rugged and reliable design coupled with the inherent advantages of FOUNDATION Fieldbus makes the OCX 8800 unmatched in overall performance. The ability to get...

Open the catalog to page 2
HART standard or OCX 8800 Oxygen/Combustibles Transmitter - 3

OCX 8800 The OCX 8800 Transmitter is completely field-repairable The OCX 8800 is fully field-repairable. The probe’s design provides convenient access to internal probe components and electronics so technicians can service the unit in-house. The sensing cell and heater/thermocouple are fully field-replaceable. We offer sample probes in different materials and lengths up to 9 feet for flue gas temperatures up to 2600°F (1427°C). The electronics can be attached to the sensor housing or separate to provide a convenient location for the electronics and operator interface for integral mounted...

Open the catalog to page 3
HART standard or OCX 8800 Oxygen/Combustibles Transmitter - 4

Specifications1 OCX 8800 Oxygen/comb transmitter Net O2 range 0-1% to 0-40% Fully field-selectable via HART or LOI Combustibles 0-1000 ppm to 0-5% Fully field-selectable via HART or LOI Accuracy Oxygen ± .75% of reading or .05% O2, whichever is greater Combustibles ± 1% F.S. when calibrated at 0-5000 ppm range System Response to Test Gas O2 10 sec T90 Combustibles 25 sec T90 Temperature limits Process 32° to 2600°F (0° to 1427°C) Sensors Housing -40° to 212°F (-40° to 100°C) Electronics Housing -40° to 149°F (-40° to 65°C) Maximum Process Pressure 8” water column Probe lengths, Nominal and...

Open the catalog to page 4
HART standard or OCX 8800 Oxygen/Combustibles Transmitter - 5

Specifications1 (continued) Logic Signals SPA HART ALARM module (optional) Low O2 alarm High Comb alarm Calibration status Unit failure Power Consumption limits Power Consumption of Heaters 750 W nominal maximum Power Consumption of Electronics 50 W nominal maximum Emerson Process Management has satisfied all obligations coming from the European legislation to harmonize the product requirements in Europe. All static performance characteristics are with operating variables constant. Specifications subject to change without notice. Communicate with the OCX 8800 almost anywhere via the HART...

Open the catalog to page 5
HART standard or OCX 8800 Oxygen/Combustibles Transmitter - 6

Dimensional drawings Outline dimensions for OCX 8800 Oxygen/combustible transmitter with intergal electronics INTERNAL LOCAL OPERATION INTERFACE (LOI) HAS STANDARD ORIENTATION AS SHOWN AND CAN BE ROTATED FOR DESIRED ORIENTATION (90° INCREMENTS) FOR VIEWING THROUGH THE WINDOW. REFER TO MANUAL FOR DETAILS. TABLE INSTALLATION/REMOVAL PROBE LENGTH

Open the catalog to page 6
HART standard or OCX 8800 Oxygen/Combustibles Transmitter - 7

Outline dimensions for OCX 8800 Oxygen/combustible transmitter with intergal electronics ■ IN - SITU FILTER OPTION EXHAUST TUBE- -EXTRACTIVE TUBE EDUCTOR DRIVE &

Open the catalog to page 7
HART standard or OCX 8800 Oxygen/Combustibles Transmitter - 8

Outline dimensions for OCX 8800 Oxygen/combustible transmitter with split electronics Electronics Housing Sensor Housing

Open the catalog to page 8
HART standard or OCX 8800 Oxygen/Combustibles Transmitter - 9

Outline dimensions for OCX 8800 Oxygen/combustible transmitter with split Mounting Options Table I. Mounting Plate_ Probe Insertion Removal Length Depth Envelope

Open the catalog to page 9
HART standard or OCX 8800 Oxygen/Combustibles Transmitter - 10

Outline dimensions for OCX 8800 Oxygen/combustible transmitter In Situ PROCESS ANALYTIC DIVISION Process Management Auto-calibration panel Standard stainless steel and hastelloy filters Stainless steel high surface area filter

Open the catalog to page 10
HART standard or OCX 8800 Oxygen/Combustibles Transmitter - 11

Ordering information OCX88A Oxygen /Combustibles Transmitter - General Purpose Model Product Description Oxygen /Combustibles Transmitter (OCX 88A) Probe Length and Material 00 No probe or exhaust tube Probe Mounting Assembly 10 2” 150# ANSI flange-requires a 2.5” (63.5mm) process hole, see drawing Standard O2 cell 2” 150# ANSI flange-requires a 2.5” (63.5mm) process hole, see drawing Acid-resistant O2 cell (DIN) 185mm diameter flange, 145mm BC with 4 x 18mm dia. holes (European Std) -Standard O2 Cell (DIN) 185mm diameter flange, 145mm BC with 4 x 18mm dia. holes (European Std) -High Sulfur...

Open the catalog to page 11
HART standard or OCX 8800 Oxygen/Combustibles Transmitter - 12

Ordering information (continued) OCX88A Oxygen /Combustibles Transmitter - General Purpose Integral to sensor housing electronics Split electronics with no cable Split electronics with 6m (20’) cable Split electronics with 12m (40’) cable Split electronics with 18m (60’) cable Split electronics with 24m (80’) cable Split electronics with 30m (100’) cable Split electronics with 45m (150’) cable Stainless Steel High Surface Area Stainless Steel Blowback only Cal Gas Flow Rotometers & Ref Gas Set w/Blowback Cal Gas Flow Rotometers & Ref Gas Set w/Blowback, Panel Mounted Cable lengths to 300’...

Open the catalog to page 12
HART standard or OCX 8800 Oxygen/Combustibles Transmitter - 13

Ordering information OCX88C Oxygen /Combustibles Transmitter - Explo-Proof for hazardous area Model Product Description Oxygen /Combustibles Transmitter - Explo-Proof (OCX 88C) Probe Length and Material 00 No probe or exhaust tube Probe Mounting Assembly 10 2” 150# ANSI flange-requires a 2.5” (63.5mm) process hole, see drawing 2” 150# ANSI flange-requires a 2.5” (63.5mm) process hole, see drawing (DIN) 185mm diameter flange, 145mm BC with 4 x 18mm dia. holes (European Std) - Standard O2 Cell (DIN) 185mm diameter flange, 145mm BC with 4 x 18mm dia. holes (European Std) - High Sulfur O2 Cell...

Open the catalog to page 13