1. Catalogs
  2. EMC PARTNER AG
  3. Protection Device Test Equipment
video corpo

Protection Device Test Equipment
1 /20Pages

Protection Device Test Equipment

Protection Device Test Equipment
1 /20Pages

Catalog excerpts

Protection Device Test Equipment-1

Component Tests Protection Device Test System Brief Overview of Phenomena. . . . . . . . . . . . . . . . 2 Applicable Standards . . . . . . . . . . . . . . . . . . . 3 Test System Overview. . . . . . . . . . . . . . . . . . . 4 Generator Specications. . . . . . . . . . . . . . . . . 11 Accessories and Options. . . . . . . . . . . . . . . . . 15 Software . . . . . . . . . . . . . . . . . . . . . . . 16 EMC PARTNER’s Product Range . . . . . . . . . . . . . . 17 Component Tests: Protection Device Test System

 Open the catalog to page 1
Protection Device Test Equipment-2

Brief Overview of Phenomena Surge currents can generate over voltages in power distribution and data transmission networks. Computer related products, process control equipment and data communications environments can be damaged by high-voltage surges and spikes. Such power surges and spikes are most often caused by lightning strikes. However, there are occasions when the surges and spikes result from any one of a variety of other causes. These causes may include direct contact with power/lightning circuits, high energy transients coupled into equipment from cables in close proximity and potential...

 Open the catalog to page 2
Protection Device Test Equipment-3

Applicable Standards International Electrotechnical Committee (IEC) IEC 60060-1 (1989). High-voltage test techniques. Part 1: General denitions and test requirements. IEC 61643-1 Ed 2 (2005) Low-voltage surge protective devices - Part 1: Surge protective devices connected to low-voltage power distribution systems - Requirements and tests IEC61000-4-5 Ed 2 (2005) Electromagnetic compatibility (EMC) - Part 4-5: Testing and measurement techniques - Surge immunity test IEC61180-1 Ed1 (1992) High-voltage test techniques for low voltage equipment - Part 1: Denitions, test and procedure requirements...

 Open the catalog to page 3
Protection Device Test Equipment-4

Test System Overview Test System Features The Protection Device Test System has many unique and outstanding features: - Clamping Voltage tests - Surge Withstand tests - Energy Absorption tests - Combination Wave Tests - Currents up to 100kA - Voltages up to 24kV - Power Line CDNs up to 50kA - Short charging time - Electronic polarity change - Semiconductor switches - All parameters on one screen - Parameter ramp feature - Internal program memory - Backlight LCD display - Compact design - Fulls ALL standard requirements - Remote control and software upgrade through standard interface - Wide range...

 Open the catalog to page 4
Protection Device Test Equipment-5

Generators Impulse testing is performed on components and assemblies either on the production line or in quality control laboratories. Tests on power main protection devices are performed on single and three phase power ports. Because of the high energy levels involved, a special Coupling and Decoupling Network (CDN) is required to superimpose the impulses and provide protection for auxiliary equipment that is not part of the test setup. Accurate monitoring of the impulse wave shapes on the EUT is an essential part of any protection device test system. Clamping Voltage Testers MIG0603CLV1 and...

 Open the catalog to page 5
Protection Device Test Equipment-6

Surge Withstand Testers The 6kV and 12kV testers consist of 4 or 5 identical circuits which can be connected in parallel. The advantages of this conguration are that two or four electrode SPDs can be tested and the overall current range is greater compared to a single circuit device. Surge Withstand Testers 6kV - MIG0603CLP Varistor tester with waveforms 8/20μs, 10/1000μs, CWG 1.2/50μs / 8/20μs - MIG0606 Current tester 8/20μs 2x 3kA, Zsource 1 or 2 Ohm - MIG0612 Current tester 8/20μs, 2x 6kA , Zsource per circuit 1 Ohm MIG0624 - MIG0612UL Varistor tester with waveforms 8/20μs, 10/1000μs, CWG...

 Open the catalog to page 6
Protection Device Test Equipment-7

Energy Absorption Testers - MIG0612EA 2ms rectangular waveform generator for energy testing on varistors: current range 5A up to 150A, Emax 700 Joule on a 20mm varistor disk - MIG0636EA 2ms rectangular waveform generator for energy testing on varistors: current range 20A up to 500A, Emax 2100 Joule on a 40mm varistor disk - MIG0624LP1 Current tester 8/20μs, 4x 6kA , Zsource per circuit 1 Ohm; 10/1000, 4x 60A. Disk Energy surge rating 2ms or 10/1000μs Combination Wave Testers - MIG1206SPD SPD tester. CWG up to 12kV/6kA IEC 61643-1 Varistor test CWG Class III, 1.2/50μs up to 12kV Class I and II,...

 Open the catalog to page 7
Protection Device Test Equipment-8

SYSTEM FLOWCHARTS Clamping Voltage Testers ITEMA TEST MANAGER 6kV Surge Withstand Testers ITEMA TEST MANAGER customized solution Component Tests: Protection Device Test System

 Open the catalog to page 8
Protection Device Test Equipment-9

12kV Surge Withstand Testers TEMA TEST MANAGER customized solution Energy Absorption Testers TEMA TEST MANAGER customized solution Component Tests: Protection Device Test System

 Open the catalog to page 9
Protection Device Test Equipment-10

Combination Wave Testers jTEMA TEST MANAGER Component Tests: Protection Device Test System

 Open the catalog to page 10
Protection Device Test Equipment-11

Generator Specications Clamping Voltage MIG0603CLV1 Voltage range Voltage increment Impulse capacitor Maximum energy Source Impedance Pulse front time Pulse duration Polarity MIG0603CLV2 Voltage range Voltage increment Impulse capacitor Maximum energy Source impedance Pulse front time Pulse duration Polarity Surge Withstand 6kV MIG0603CLP Current range Output 1 Current range Output 2 Current range Output 3 Open circuit voltage Impulse capacitor Maximum energy Clamping voltage Source Impedance Pulse front time Pulse duration Polarity MIG0606 Current range Current increment Impulse capacitor Maximum...

 Open the catalog to page 11
Protection Device Test Equipment-12

MIG0612 (UL) Output range Output increment Impulse capacitor Maximum energy Source Impedance Pulse front time Pulse duration Polarity MIG0624 Current range Current increment Impulse capacitor Maximum energy Source impedance Pulse front time Pulse duration Polarity Surge Withstand 12kV MIG1248 Current range Current increment Impulse capacitor Maximum energy Source impedance Pulse front time Pulse duration Polarity MIG1260 Current range Current increment Impulse capacitor Maximum energy Source impedance Pulse front time Pulse duration Polarity MIG12100 Current range Current increment Impulse capacitor...

 Open the catalog to page 12
Protection Device Test Equipment-13

Energy Testers MIG0612EA Current range Vcl varistor ranges Impulse capacitor Maximum energy Pulse duration (90% - 90%) Pulse duration (10% - 10%) Maximum amplitude deviation Polarity MIG0636EA Current range Vcl varistors Impulse capacitor Maximum energy Pulse duration (90% - 90%) Pulse duration (10% - 10%) Maximum amplitude deviation Polarity MIG0624LP1 Current range Current increment Impulse capacitor Maximum energy Source impedance Pulse front time Pulse duration Current range Current increment Impulse capacitor Maximum energy Pulse front time Pulse duration Component Tests: Protection Device...

 Open the catalog to page 13
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.