Overview: The TERRACAP TCB040 grounding system is designed to ensure safe discharge of electrostatic charges in tanker trucks. It uses a clamp to identify a low-resistance connection and discharges charges via a resistor to prevent spark discharge. The system continuously monitors the connection during the pumping process.
Specifications:
  • Supply Voltage: 100 – 240 VAC, 47–63 Hz, with automatic mains identification.
  • Housing Material: Cast aluminium with explosion-proof enclosure.
  • Weight: 10 kg.
  • Entries: 4 tapped entries for M20 cable glands.
  • Protection Class: IP66.
  • Dimensions: 230 x 230 x 150 mm.
  • Interlock Output: 1 voltage-free normally open contact.
  • SIL Level: Meets SIL 2 requirements.
  • Approval/Marking: II 2(1) G Ex d [ia Ga] IIC T6 Gb, II 2(1) D Ex tb [ia Da] IIIC T85°C Db IP66.
Functional Components:
  • TCT Function Test Unit: Used for testing the correct function of the TERRACAP TCB040 grounding system.
  • TCS Keyswitch: Allows switching the measuring circuit from capacitive to resistive measurement.
Operational Process: The system checks the capacity detected at the clamp. If correct, a green display lights up, and the interlocking relay enables the pumping process. The system ensures a continuous low-resistance connection to the ground to prevent electrostatic charge build-up.
See more

Catalog excerpts

Brochure Terracap General-1

electrostatic innovations Grounding System TERRACAP

 Open the catalog to page 1
Brochure Terracap General-2

TERRACAP TERRACAP The TERRACAP TCB040 grounding system identifies a low-resistance connection using the jaws of the clamp. If a connection is identified, the device discharges electrostatic charges safely via a resistor, which prevents spark discharge. The control unit then checks the capacity detected at the clamp. If the capacity for the tank truck is correct, a green display lights up and the interlocking relay enables the pumping process. The device then forms a low-resistance connection to the ground, which prevents further build-up of electrostatic charges. The connection using the clamps...

 Open the catalog to page 2

All Eltex-Elektrostatik-GmbH catalogs and technical brochures

  1. Brochure ESA

    15  Pages

  2. Brochure SDS

    4  Pages

  3. Brochure RX3

    3  Pages

  4. Brochure WM3000

    15  Pages

  5. Brochure SCC

    3  Pages

  6. Brochure RX11

    3  Pages

  7. Brochure MTS

    3  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.