Air blower heater

Air blower heater

Air blower heater

Product catalog summary
Application
The air blower heaters are designed for heating air in hazardous areas such as production or storage halls and containers.
Specifications
  • Heating capacity ranges from 3.0 kW to 30.0 kW.
  • Dimensions vary with capacity, with larger units having dimensions of 530 x 1800 x 515 mm.
  • Flow rate ranges from 500 m³/h to 2800 m³/h.
  • Sound level is consistent at 60-70 dB(A).
  • Weight ranges from 90 kg to 105 kg.
  • Voltage requirement is 400 V 3/PE 50 Hz.
  • Available for temperature class T4 or alternative designs upon request.
  • Optional exchangeable filter inset available on request.
Design
The heaters feature a duct-type housing made of sheet steel with explosion-proof heating coil and ventilator. Adjustable louvers are included for directing airflow. The housing is painted silver/grey, with stainless steel options available on demand.
Installation and Electrical Connection
Heaters must be installed vertically with sufficient space for air intake from below. Electrical connections should comply with EN 60079-14 section 9, using appropriate cable cross sections. The ventilator motor requires a series-connected circuit breaker with a proven tE-trip characteristic. Complete control boards in explosion-proof execution or for safe areas are available upon request.
Wiring Proposal and Accessories
Ex-control boards for air heaters or safe areas are available upon request. An Ex Temperature Regulator (Type QTREK -20...+50°C) is also available.
Alternative Designs
Compact type or circulating air heaters are available on request.
See more

Catalog excerpts

Air blower heater-1

Wandheizl iifter x/ Air blower heater <S> II 2G Anwendung Application Die Heizlufter dienen zur Erwarmung der Raumluft in explo- The air heaters serve for heating of air in hazardous areas, sionsgefahrdeten Betriebsstatten, z.B. in Betriebs- oder e.g. in production or storage halls or containers. Lagerraumen oder Containern. Auswahltabelle Selection Table Heizleistung/ Heating capacity [kW] Ausfuhrung fur Temperaturklasse T4 oder alternative Bauformen auf Anfrage. Option auswechselbarer Filtereinsatz auf Anfrage Heaters for temperature class T4 or alternative design on request. Option: exchangeable filter inset, on request ELMESS-Thermosystemtechnik GmbH & Co. KG ■ Nordallee 1, D-29525 Uelzen ■ Telefon: +49 (0) 581-9083-0 ■ Fax: +49 (0) 581-9083-44 ■ E-Mail: [email protected] www.elmess.de

 Open the catalog to page 1
Air blower heater-2

In einem aus Stahlblech gefertigten kanalförmigen Gehäuse ist jeweils ein Heizregister und ein Ventilator in explosionsgeschützter Bauart eingebaut. Die jeweilige Temperaturklasse wird auch bei Ausfall des Ventilators gewährleistet. Die Heizlüfter sind mit verstellbaren Ausblasjalousien ausgerüstet. Das Gehäuse ist komplett lackiert (Hammerschlag silbergrau). Ausführung aus Edelstahl auf Anfrage. Heating coil and ventilator each of explosion-proof construction are installed in a duct-type housing made of sheet steel. The individual temperature class will also be guaranteed in case of ventilator...

 Open the catalog to page 2
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.