EVRM-NC EVRM-6NC Safety solenoid valves for gas Manual reset - Normally closed DN10 … DN200
Open the catalog to page 1ELEKTROGAS – TECHNICAL MANUAL EVRM-NC EVRM-6NC Safety solenoid valves for gas Manual reset - Normally closed Contents Description ………………………………………….. 2 Features …………………………………………….. 2 Functioning and application ………………………. 3 Special versions and optionals …………………… 4 Technical specifications …………………………… 4 Gas flow chart (pressure drop) …………………… 6 Ordering information ………………………………. 8 Standards and approvals …………………………. 9 Installation and servicing ………………………….. 10 The EVRM-NC /6NC type valve is a manual reset safety valve that is normally closed (open when energized). This type of device,...
Open the catalog to page 2ELEKTROGAS – TECHNICAL MANUAL The EVRM-NC type valve is a manual reset safety valve that is normally closed. When not in working position the spring works on the shutter keeping the gas orifice closed. Simply by energizing the coil the valve does not open. It is necessary to manually move the reset rod located at the top of the coil. Once opened, the valve can maintain this position until electric current circulates on the coil. In absence of electric current the valve closes rapidly and remains shut upon return of same. Once the causes for the lock have been eliminated, valve must be...
Open the catalog to page 3ELEKTROGAS – TECHNICAL MANUAL Special versions and optionals The sizes 1”¼, 1”½ and 2” can be provided with G1/4 gauges also in the outlet chamber. A closed position indicator micro-switch (CPI) can be installed. Models from DN65 to DN200 are provided with G1/8 connection on the bottom for these facilities -on request from 3/4" to 2" - (not available for 6 bar versions and brass models). To install the micro-switch the adapting kit must be required. The threaded models Rp11/2 and Rp2 can be provided with flanged connections using an optional kit. Whole range can be provided with Ex-proof...
Open the catalog to page 4ELEKTROGAS – TECHNICAL MANUAL Tab. 2 Material and connections CuZn Rp 3/8 Rp 1/2 G 3/4 G1 Overall dimensions ( ) Valve open
Open the catalog to page 5ELEKTROGAS – TECHNICAL MANUAL Gas flow chart (Pressure drop) Formula of conversion from air to other gases Specific gravity ρ [Kg/m³] Air Natural gas Town gas LPG
Open the catalog to page 6ELEKTROGAS – TECHNICAL MANUAL When the flow read on the diagram is referred to operating pressure instead of standard conditions, the pressure drop ∆p read on the diagram must be multiplied for the factor: (1+ relative pressure in bar) Example: 3 In the 2” solenoid valve with an air flow of 80 Nm /h there is a pressure drop ∆p = 5 mbar. 3 If we consider that 80 m /h is the flow at 200 mbar of inlet pressure, then the pressure drop to be consider is: ∆p = 5x(1+0,2) = 6 mbar Normally, pressure drop and flow rate for the valves are read from the gas flow diagram. However, the valves can also...
Open the catalog to page 7ELEKTROGAS – TECHNICAL MANUAL Connections Rp 3/8 brass Rp 1/2 brass G 3/4 brass G 1 brass Rp 3/8 Rp 1/2 Rp 3/4 Rp 1 Rp 1¼ Rp 1½ Rp 2 DN 40 (1) DN 50 (1) DN 65 DN 80 DN 100 DN 125 DN 150 DN 200 NOTE: models up to DN80 are provided with DIN plug, models from DN100 up to DN200 are provided with terminal box. (1) Optional kit The versions with inlet pressure p1 ≤ 6 bar (600 kPa) may be order inserting the digit “6” in to the designation. Different voltage than 230V may be order adding to the standard designation the additional code shown above. Other optionals must be order with their ordering...
Open the catalog to page 8ELEKTROGAS – TECHNICAL MANUAL The valve design meets current European approval requirements regarding safety shut-off functions on gaseous fuels. These products conform with the Pressure Equipment Directive (97/23/EC) and the certification has been issued by the notified body: C.S.I. Spa Viale Lombardia 20 I-20021 Bollate (MI) The following standards/technical specifications have been fulfilled: - Quality Management System is certified according to UNI EN ISO 9001 and the monitoring is carried out by the notified body: Kiwa Gastec Italia Spa. Via Treviso, 32/34 I- 31020 San Vendemiano (TV)
Open the catalog to page 9ELEKTROGAS – TECHNICAL MANUAL To assure a proper and safe operation, as well as a long life of the valve, the installation procedure and a periodical servicing are very important topics and the following instructions should be always fulfilled. IMPORTANT: before proceeding with the installation, ensure that all the features of your system comply with the specifications of the valve (gas type, operating pressure, flow rate, ambient temperature, electrical voltage, etc.). CAUTION Shut off the gas supply at the main manual shut-off valve and disconnect electrical power to the valve before...
Open the catalog to page 10ELEKTROGAS – TECHNICAL MANUAL Valve is provided with an ISO 4400 plug for the electrical connections. To connect the valve do the following: - Using a screwdriver remove the plug from the coil. Unscrew the gland-nut (7) and remove the washer (6) and grommet (5). To remove the rectifier unit (1) from the plug housing (3), remove the gasket (2) and extract the screw (4) completely, then insert a flat screwdriver into the slot located on edge and pull it. Insert the cable in to the gland-nut, washer, grommet and then into the plug housing. Connect power cables to the rectifier terminals...
Open the catalog to page 11All Elettromeccanica Delta S.p.A. catalogs and technical brochures
-
General Catalogue
44 Pages
-
VMERNA
7 Pages
-
vmm
11 Pages
-
VMH
16 Pages
-
VML
11 Pages
-
VMR
11 Pages
-
FG Gas filter
9 Pages
-
PSG Pressure Switch for Gas
6 Pages
-
VF-VFH Butterfly valves
12 Pages
-
EV oil valve
3 Pages
-
A-AD aluminium pump
6 Pages