POWER TRANSFORMERS

POWER TRANSFORMERS

POWER TRANSFORMERS

Product catalog summary
General Overview
Elettromeccanica Colombo manufactures power transformers for both general and specific purposes, including autotransformers and insulating transformers. The company has a long-standing reputation for reliable technology and has adapted to advancements in power electronics, particularly in converter transformers used with rectifier groups. Compliance with IEC 61378-1 standards is emphasized, ensuring transformers are suitable for various types of converters and harmonics. The company's ISO 9001 certified quality assurance system guarantees a product lifespan of over 30 years under normal conditions.
Production Range
The production range includes oil-filled transformers with power ratings from 3.15 MVA to 40 MVA and voltages from 3 kV to 72.5 kV, adhering to IEC 60076-13 and IEEE 57.12.00 standards. Dry type cast resin transformers range from 3.15 MVA to 10 MVA with voltages up to 36 kV, following IEC 60076-11 and IEEE 57.12.01 standards. Both types operate at frequencies of 50-60 Hz.
Testing Procedures
All transformers undergo individual testing, including routine-acceptance tests such as voltage ratio measurement and impedance voltage measurement. Type tests, like temperature rise and lightning impulse tests, are conducted upon request. Special tests, such as short circuit withstand tests, are performed at CESI laboratories in Milan.
Oil Power Transformers
These transformers comply with IEC 60076-13 standards and feature a core made of high permeability steel with cooling channels. Windings are made of 99.9% electrolytic copper, and the transformers are filled with oil under vacuum conditions. Cooling is achieved through tank-mounted radiators, and units can be equipped with fans or pumps. Transformers can operate beyond nominal ratings as per IEC 354 standards.
Cast Resin Power Transformers
Built according to IEC 60076-11 standards, these transformers use a core made of cold-rolled oriented grain steel. The LV windings are made of aluminum foil with class H insulation, while MV windings use aluminum foil strips. The casting process involves vacuum and temperature control to ensure high-quality standards.
Additional Features
Transformers can be equipped with accessories like overpressure valves, conservators with diaphragms, and electronic voltage regulators. On-site erection services are available by skilled personnel.
See more

Catalog excerpts

POWER TRANSFORMERS-2

POWER TRANSFORMERS GENERALITÀ Oltre ai trasformatori di distribuzione, la ELETTROMECCANICA COLOMBO produce trasformatori di potenza, sia per usi comuni (per abbassamento-elevamento tensione su linee principali, per alimentazione di trasformatori ausiliari, per trasferire in rete la corrente autoprodotta) che per usi specifici (autotrasformatori, trasformatori di avviamento, di isolamento, etc). La loro tecnologia è collaudata da diversi decenni. In tempi recenti, grazie ai progressi compiuti dall’elettronica di potenza, è invalso l’uso di trasformatori per convertitori, collegati gruppi di conversione...

 Open the catalog to page 2
POWER TRANSFORMERS-3

TRASFORMATORI DI POTENZA IN OLIO I trasformatori sono costruiti secondo gli standards: OIL POWER TRANSFORMERS The transformers are built in compliance with IEC 60076-13 IEC 60076-13 o IEEE C57.12.01 (o altri standards a richiesta). standards and, IEEE C57.12.01 (or other on request). Il nucleo è realizzato con lamierino magnetico ad alta permeabilità The core is made of high permeability cristal oriented steel sheet e bassa cifra di perdite, a gradini, taglio a 45° montaggio step-lap, low loss, in a step section with 45° joints step-lap assembly, and is fitted with cooling channels. I conduttori...

 Open the catalog to page 3
POWER TRANSFORMERS-4

TRASFORMATORI IMMERSI IN OLIO CON COMMUTATORE A VUOTO OIL IMMERSED TRANSFORMERS WITH NO LOAD TAP CHANGER 20 MVA - NUCLEO MAGNETICO - MAGNETIC CORE COMMUTATORE A VUOTO Il commutatore a vuoto serve a variare il rapporto di trasformazione sul lato M.T. a trasformatore disattivato e per gradini fissi (ad esempio 2,5%). Se necessario il comando della commutazione può essere rimandato a lato cassa invece che sul coperchio, con attivazione manuale o motorizzata. PARTE ESTRAIBILE - ACTIVE PART TRASFORMATORE MONTATO - ASSEMBLED TRANSFORMER CASSA A RADIATORI STACCABILI - TANK WITH DETACHABLE RADIATORS...

 Open the catalog to page 4
POWER TRANSFORMERS-5

TRASFORMATORI IMMERSI IN OLIO CON COMMUTATORE SOTTO CARICO OIL IMMERSED TRANSFORMERS WITH ON LOAD TAP CHANGER COMMUTATORE SOTTO CARICO Il commutatore sotto carico serve a variare il rapporto di trasformazione con trasformatori in servizio e fornisce una regolazione continua. I commutatori sotto carico installati nei nostri trasformatori di potenza sono prodotti dalla Maschinenfabrik Reinhausen, fornitore di commutatori sotto carico di concezione tecnicamente molto evoluti. Il commutatore sotto carico è attivato da una unità motore. L’albero di comando e un rimando a squadra collegano meccanicamente...

 Open the catalog to page 5
POWER TRANSFORMERS-6

TRASFORMATORI DI POTENZA IN RESINA CAST RESIN POWER TRANSFORMERS I trasformatori sono costruiti secondo gli standards: The transformers are built in compliance with IEC 60076-11 IEC 60076-11 o IEEE C57.12.01 (o altri standards a richiesta). standards and, IEEE C57.12.01 (or other on request). Il nucleo è costruito impiegando lamierini magnetici a cristalli The core is made of cold rolled oriented grain steel sheet with orientati a bassa cifra di perdita ed elevata permeabilità. low specific loss, cut at 45°C, step-lap, assembled at E’ realizzato con sezione a gradini, taglio a 45° step-lap calcolato...

 Open the catalog to page 6
POWER TRANSFORMERS-7

TRASFORMATORI IN RESINA CON DUE AVVOLGIMENTI IN PARALLELO CAST RESIN TRANSFORMERS WHIT TWO PARALLEL WINDINGS 10 MVA - NUCLEO MAGNETICO STEP-LAP - 10 MVA - STEP-LAP MAGNETIC CORE NUCLEO CON AVVOLGIMENTI BT/MT - MAGNETIC CORE WITH LV/MV WINDINGS TRASFORMATORE LATO BASSA TENSIONE - TRANSFORMER LOW VOLTAGE SIDE TRASFORMATORE LATO MEDIA TENSIONE - TRANSFORMER MEDIUM VOLTAGE SIDE

 Open the catalog to page 7
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.