POWER TRANSFORMERS

POWER TRANSFORMERS

POWER TRANSFORMERS

Product catalog summary
General Characteristics
ELETTROMECCANICA COLOMBO manufactures power transformers for both general and specific purposes. General-purpose transformers are typically high voltage to medium voltage (HV/MV) or medium voltage to medium voltage (MV/MV) with on-load tap changers (OLTC). Specific transformers often use converters for various machines. Transformers are designed according to Ecodesign regulations to maximize efficiency and meet the Minimum Peak Efficiency Index (PEI). The company has extensive experience, ensuring reliable products with a lifespan of over 30 years under normal conditions. Quality management is certified under ISO 9001-2015, ISO 14001-2015, and ISO 45001-2018.
Production Range
The production range includes transformers with power from 5 MVA to 45 MVA ONAN (63 MVA ONAF), medium voltage (MV) tensions of 11/15/20/30/52/70 KV, and high voltage (HV) tensions of 90, 110, 123, 132, 150 KV, operating at frequencies of 50-60 Hz. Standards followed include IEC 60076-13 and IEEE 57.12.01.
Testing Procedures
All transformers undergo individual testing. Routine tests include voltage ratio measurement, induced over-voltage withstand, winding resistance measurement, and partial discharge measurement. Type tests include temperature rise and lightning impulse tests. Special tests, such as short circuit withstand, are conducted at CESI laboratories in Milan.
Oil Power Transformers
These transformers comply with IEC 60076 standards. They feature high permeability steel cores and E-CU 99.9% electrolytic copper windings. Cooling is achieved through tank-mounted radiators, with options for fans or pumps to increase power. Transformers can operate above nominal ratings as per IEC 354. Accessories include overpressure valves and temperature indicators.
Transformers with Tap Changers
No load tap changers adjust the transformation ratio on the MV side when the transformer is inactive. On load tap changers (OLTC) provide continuous regulation while the transformer is in service, activated by a motor drive and controlled by an electronic voltage regulator.
See more

Catalog excerpts

POWER TRANSFORMERS-1

TRASFORMATORI DAL 1901 TRANSFORMERS SINCE 1901 TRASFORMATORI DI POTENZA POWER TRANSFORMERS

 Open the catalog to page 1
POWER TRANSFORMERS-2

Caratteristiche generali Oltre ai trasformatori di distribuzione, ELETTROMECCANICA COLOMBO produce trasformatori di potenza sia per usi comuni (abbassamento-elevamento tensione su linee principali, per alimentazione di trasformatori ausiliari, per trasferire in rete la corrente autoprodotta) che per usi specifici (trasformatori industriali, autotrasformatori, trasformatori di isolamento, di avviamento, per prove). I primi sono normalmente trasformatori alta tensione/media tensione (AT/MT) o media tensione/media tensione (MT/MT), frequentemente con commutatore sotto carico. I trasformatori di...

 Open the catalog to page 2
POWER TRANSFORMERS-3

General features In addition to distribution transformers ELETTROMECCANICA COLOMBO manufactures power transformers either for general purposes (reducing-increasing voltage on main grid, feeding auxiliary transformers, transferring to the grid the own produced current) and for specific purposes (industrial transformers, autotransformers, insulation transformers, starting transformers, transformers for testing). These general purpose transformers normally are converting high voltage to medium voltage (HV/MV) or medium voltage to medium voltage (MV/MV),frequently with OLTC (On load tap changer)....

 Open the catalog to page 3
POWER TRANSFORMERS-4

Trasformatori di potenza in olio I trasformatori sono costruiti secondo gli standard IEC 60076 (o altri standard a richiesta). Il nucleo è realizzato con lamierino magnetico ad alta permeabilità e bassa cifra di perdite, a gradini, taglio a 45° montaggio step-lap, con canali di raffreddamento. I conduttori degli avvolgimenti sono in rame elettrolitico E-CU 99,9%. In base al disegno del trasformatore, gli avvolgimenti possono essere continui a disco trasposto, a elica semplice o multipla. I canali di raffreddamento sono fatti con stecche adeguatamente formate e anelli di guida del flusso. La commutazione...

 Open the catalog to page 4
POWER TRANSFORMERS-5

Trasformatori con commutatore a vuoto Il commutatore a vuoto serve a variare il rapporto di trasformazione sul lato M.T. a trasformatore disattivato e per gradini fissi (ad esempio 2,5%). Se necessario il comando della commutazione può essere rimandato a lato cassa invece che sul coperchio, con attivazione manuale o motorizzata. Transformers with no load tap changer The no load tap changer is used to vary the transforming ratio on M.V. side with the transformer out of duty and with fixed steps (for instance 2,5%). If necessary, the handle of the tap-normally on the cover-can be placed on tank...

 Open the catalog to page 5
POWER TRANSFORMERS-6

Elettromeccanica Colombo s.a.s. Via Kennedy, 34 - 20010 Mesero (MI) Italy Phone: Fax: E-mail:

 Open the catalog to page 6
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.