SLR 4 Series

SLR 4 Series

Product catalog summary
Insulation Data:
  • Basic insulation at 250 VAC with air and creepage distance >4 mm, test voltage 2500 V / 50 Hz / 1 min.
  • Double or reinforced insulation at 250 VAC with air and creepage distance >8 mm, test voltage 4000 V / 50 Hz / 1 min.
  • Double or reinforced insulation at 250 VAC with air and creepage distance >10 mm, test voltage 5000 V / 50 Hz / 1 min.
  • Test voltage contact open 1500 V / 50 Hz / 1 min.
  • Creepage resistance CTI 250, Pollution degree 2, Overvoltage category III.
  • Insulation resistance at Up 500 VDC >100 MΩ.
Additional Data:
  • Mechanical endurance >10 x 106 operations, Switching frequency, mechanical 15 Hz.
  • Response time (all NO closed) typically 15 ms, Drop-out time (NC closed) typically 4 ms.
  • Bounce time of NO contact typically 6 ms, NC contact typically 12 ms.
  • Shock resistance 16 ms NO > 10g, NC > 6g.
  • Vibration resistance NO > 5g (10-200 Hz), NC > 1.5g.
  • Resistance to short circuiting contacts 1000 A SCPD 10 A gG / gL (pre-fuse).
  • Ambient temperature -40°C to +70°C, Thermal Resistance 55 K / W, Temperature limit for coil 120°C.
  • Weight approx. 30 g, Mounting position any, Mounting distance recommended >5 mm.
  • Test method A / group assembly, Type of protection RT II, Solder bath temperature 270°C / 5 s.
Tests, Regulations, Standards:
  • Approvals: UL File E188953 Sec. 3.
  • Insulation class IEC 60664-1 250 VAC, Fire protection requirements UL 94 / V0.
  • Standards: IEC 61810-1, IEC 61810-3.
Options, Accessories:
  • None available.
Product Key:
  • SLR 3 1 2 24VDC, Coil voltage, Solder terminals, Number of NC contacts, Number of NO contacts, Type designation.
Contact Lifetime NO Contacts:
  • AC 1:230V DC 1: 24V, AC 15: 230V, DC 13: 24V.
  • Maximal switching capacity (DIN EN 60947-5-1, Tab. C2): AC 15: 230 V / 5 A, DC 13: 24 V / 7.5 A / 0.1 Hz, UL 508: C600 / R300.
  • Maximal contact load at AC 1 with 230 V: 2 contacts with 10 A each, 3 contacts with 8.4 A each.
Relay Key Data:
  • PCB relay with forcibly guided contacts, Protective separation between coil/control contact and output contacts (>8 mm), as well as output contacts against each other (>10 mm).
  • IEC 61810-3 Type A, Contact mounting: SLR312 3 NO / 1 NC, SLR222 2 NO / 2 NC.
  • Small external dimensions, Nominal coil power 0.6 W, Holding coil power 0.18 W.
  • Coil for railway application according EN 50155 on request.
Contact Data:
  • Contact material AgSnO2 + 0.2 μm Au, Type of contact crown contact.
  • Rated switching capacity 250 VAC 10 A AC1 2500 VA, Electr. Life AC1(360 S / h) approx. 100000.
  • Inrush current max. 25 A for 20 ms, Switching voltage range 5 to 250 VDC / VAC.
  • Switching current range* 10 mA to 10 A, Switching capacity range* 60 mW to 2500 W(VA).
  • Contact resistance (as delivered) ≤100 mΩ / 6 V / 100 mA.
Standard Coils for Direct Current:
  • Nominal voltage VDC, Min. pick-up voltage at 20 °C, Drop-out voltage at 20 °C, Nominal current in mA at 20 °C, Resistance in Ohm at 20 °C.
See more

Catalog excerpts

SLR 4 Series-1

SLR 4 Series Relay Key Data Circuit Diagram (relay top view) Contact Lifetime NO Contacts - PCB relay with forcibly guided contacts - Protective separation between coil/control contact and output contacts (>8 mm), as well as output contacts against each other (>10 mm) - IEC 61810-3 Type A - Contact mounting: SLR312 3 NO / 1 NC SLR222 2 NO / 2 NC - Small external dimensions - Nominal coil power 0,6 W - Holding coil power 0,18 W - Coil for railway application according EN 50155 on request - Test voltage2500 V / 50 Hz / 1 min - Double or reinforced insulation at 250 VAC - ■ — ■ - - Air and creepage distance >8 mm - Test voltage4000 V / 50 Hz / 1 min - Double or reinforced insulation at 250 VAC ^■ - Air and creepage distance >10 mm - Test voltage5000 V / 50 Hz / 1 min Test voltage contact open1 500 V / 50 Hz / 1 min Creepage resistance CTI 250 Pollution degree2_ Overvoltage category III Maximal switching capacity (DIN EN 60947-5-1, Tab. C2) AC 15: 230 V / 5 A Maximal contact load at AC 1 with 230 V: 2 contacts with 10 A each 3 contacts with 8,4 A each Load Limit Curve with Direct Current Additional Data Contact Data Contact materialAgSnO2 + 0,2 pm Au Type of contact crown contact Rated switching capacity 250 VAC 10 A AC1 2500 VA Electr. Life AC1(360 S / h) approx. 100000 Inrush current max.25 A for 20 ms Switching voltage range 5 to 250 VDC / VAC Switching current range*10 mA to 10 A Switching capacity range* 60 mW to 2500 W(VA) Contact resistance (as delivered) <100 mfi / 6 V / 100 mA Mechanical endurance Switching frequency, mechanical Response time (all NO closed) Drop-out time** (NC closed) Bounce time of NO contact Bounce time of NC contact_ >10 x 106 operations 15 Hz typically 15 ms typically 4 ms typically 6 ms typically 12 ms NO > 10g NC > 6g NO > 5g NC > 1,5g *Guided values Resistance to short circuiting contacts 1000 A SCPD 10 A gG / gL (pre-fuse) Excitation Voltage Range Ambient temperature Standard Coils for Direct Current Thermal Resistance (other voltages on request) Temperature limit for coil Mounting position Mounting distance Test method Solder bath temperature **without spark suppression Tests, Regulations, Standards Fire protection requirements_ Options, Accessories none available Ambient Temperature °C ^ 1) Max. excitation voltage with contact load: <6 A 2) Min. excitation voltage (guaranteed values) without previous operation Single relay on print, no heat accumulation due to surrounding components with self-heating, duty cycle 100%. Coil voltage Solder terminals Type designation