SIF3 Series

SIF3 Series

Product catalog summary
Overview: The document provides technical specifications for the SIF3 Series relays by ELESTA GmbH, highlighting their features, dimensions, electrical and mechanical data, and compliance with standards.
Features: The SIF3 Series relays are equipped with forcibly guided contacts as per IEC 61810-3, suitable for print mounting, and allow SMD placement under the relay. They have a compact height of 10.9 mm and a contact assembly of 2 NO + 1 NC.
Dimensions: The relays have specific pin dimensions and recommended PCB drilling guidelines. The height is noted as 10.9 mm, and care should be taken not to drill under the relay if SMD is mounted.
Coil Data: At 20°C, the nominal power is 0.60 W, with a holding power of 0.18 W. The coil limit temperature is 120°C, and various nominal voltages are specified with corresponding pick-up and drop-out voltages, currents, and resistances.
Insulation Data: The rated insulation voltage is 250 VAC, with double or reinforced insulation. The test voltage is 4,000 Vrms for 1 minute, and the insulation resistance is a minimum of 100 MΩ.
Mechanical Data: The mechanical lifetime is at least 10 million operations, with a maximum switching frequency of 15 Hz. The response time for NO contacts is typically 12 ms, and the drop-out time for NC contacts is 5 ms.
Other Data: The relays operate within an ambient temperature range of -40°C to +70°C, with a thermal resistance of 60 K/W. They are approved by cULus and TÜV, with a flammability class of UL 94 V-0.
Contact Data: The contact material is AgCuNi with a gold layer. The rated switching power is 2,500 VA, with a maximum switching voltage range of 5 to 250 V DC/AC. The electrical life is 100,000 operations at 0.1 Hz.
Compliance and Approvals: The relays comply with IEC 61810-1 and UL 508 standards, with specific switching capacities for AC and DC applications.
See more

Catalog excerpts

SIF3 Series-1

Contact data Circuit diagram (top view) - Relay with forcibly guided contacts according to IEC 61810-3 - Application type A - Protective separation (see insulation data) - Suitable for print mounting - SMD placement under the relay possible - Height only 10,9 mm - Contact assembly SIF212: 2 NO + 1 NC Contact material AgCuNi + 0,2, ..., 0,4 μm Au Type of contact Single contact with notched crown Rated switching power 2 500 VA 250 V / 10 A / AC-1 (max.) Electr. life time (0,1 Hz, rel. duty cycle 10%) 100 000 Inrush current 30 A for 20 ms Switching voltage range 5, ..., 250 V DC / AC Switching current range* 3 mA, ..., 10 A Switching power range* 40 mW, ..., 2 500 W (VA) Contact resistance as new (max.) 100 mΩ Short circuit resistance of NO contacts** 1 000 A with pre-fuse SCPD 10 A gG / gL (fuse) Short circuit resistance of NC contacts** 1 000 A with pre-fuse SCPD 6 A gG / gL (fuse) Insulation data * Reference values ** Prospective short-circuit current Electrical life (NO contacts) Rated insulation voltage (IEC 60664-1) 250 VAC Double or reinforced insulation - Air and creepage distance (min.) 5,5 mm - Test voltage 4 000 Vrms / 1 min Open contact: Test voltage* 1 500 Vrms / 1 min Creepage resistance CTI 175 Pollution degree 2 Overvoltage category III Insulation resistance (min.) 100 MΩ - Test voltage 500 VDC * Initial value Mechanical data * do not drill under the relay if SMD is mounted ** open vent stack Pin dimension b Pin dimension c Pin dimension d Recommended drilling on PCB Nominal power (typ.) Holding power (typ.) Coil limit temperature Switching capacity (IEC 61810-1) AC-1: 240 V / 10 A MAX AC-15: 240 V / 5 A MAX DC-1: 24 V / 10 A MAX DC-13: 24 V / 5 A / 0,1 Hz MAX Switching capacity (UL 508) Continuous current per contact at load of: 1 contact 2 contacts Contact load limit curve (DC) Mechanical lifetime (min.) 10 x 106 operations Switching frequency (max.) 15 Hz Response time (NO closed) (typ.) 12 ms Drop-out time (NC closed) (typ.)* 5 ms Bounce time (typ.) NO: 1,5 ms / NC: 15 ms Shock resistance (16 ms) (min.) NO: 15g / NC: 6g Vibration resistance (10-200 Hz) (min.) NO: 10g / NC: 2g Weight approx. 18 g Mounting position any Mounting distance (min.) 5 mm * without coil wiring  Other data Ambient temperature Thermal resistance Protection class Solder bath temperature Test method (heating) Approvals Flammability class UL File Excitation voltage range Options, Accessories Other coil designs possible Coils accord. to EN 50155 (railway applications) possible Type designation Number of contacts NO Number of contacts NC Connection technology Nominal coil voltage Options Test conditions: - Graph 1: Contact current 6 A MAX - Graph 2: without previous operation - Free-standing relay on PCB - Duty cycle 100% ELESTA GmbH, Heuteilstrasse 18, CH - 7310 Bad Ragaz, Switzerland -40 °C, ..., +70 °C 60 K / W RT II 270 °C / 5 s A (group assembly) cULus, TÜV UL 94

 Open the catalog to page 1
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.