1. Catalogs
  2. Elektro Mechanik
  3. REMOTE INDICATION INTERFACE TYPE RIS-FR

REMOTE INDICATION INTERFACE TYPE RIS-FR

REMOTE INDICATION INTERFACE TYPE RIS-FR

REMOTE INDICATION INTERFACE TYPE RIS-FR

Product catalog summary
Overview: The document provides technical specifications for the Remote Indication Interface Type RIS-FR, designed for use with overhead lines. It is used to retrofit up to nine fault indicators (type FLA3.1) with SCADA contacts for remote indication systems.
Specifications:
  • Mappings: Two mapping options are available: one contact per indicator for phase-specific fault indication, or contacts grouped to indicate permanent/temporary faults and voltage events.
  • Reset and Test Inputs: Remote reset and test inputs are available, allowing all FLA3.1 indicators within range to be reset or tested remotely.
  • Power Supply: The interface is self-powered by lithium batteries, with optional external power supplies (12-48V DC or 115V/230V AC). Battery life is a minimum of 10 years with 30 faults per year without external supply.
  • Dimensions: Housing dimensions are 130 mm (height) x 178 mm (width) x 52 mm (depth). Circuit board dimensions are 88 mm (height) x 168 mm (width).
  • Protection Class: The housing is IP65 rated, suitable for surface installation.
  • Communication: Utilizes a 433MHz radio interface for communication with FLA3.1 indicators.
  • Operating Temperature: The device operates within a temperature range of -20°C to +70°C.
Functional Features:
  • SCADA Contacts: Nine potential-free NO contacts for FLA3.1 indicators, with contact types depending on the remote function of the FLA3.1.
  • Battery Status: Includes a potential-free NO contact for low battery status, a battery status LED, and a battery test button.
  • Testing and Resetting: Features buttons to test all FLA3.1s in range and to reset them.
  • Connectors: Includes connectors for FLA3.1 IDs 1 to 9, low battery status, external reset, external test, and external power supply.
Compliance: The device undergoes internal type tests according to IEEE 495-2007 standards.
See more

Catalog excerpts

REMOTE INDICATION INTERFACE TYPE RIS-FR-1

REMOTE INDICATION INTERFACE TYPE RIS-FR The remote indication interface type RIS-FR is used to retrofit up to 9 fault indicators type FLA3.1 with potential free SCADA con- tacts. These contacts can be used to connect the short-circuit indicators type FLA3.1 with an existing wire or wireless remote indication system. The nine contacts dedicated for the fault indicators can be assig- Mapping 1: One contact per indicator. This allows the remote indication of faults per phase. Mapping 2: The contacts are assigned to remotely indicate permanent and temporary faults as well as voltage on/off events. The indicators are grouped in bundles The type of contact depends on the configuration of the fault in- (Please refer to the instruction manual for detailed information about the two mappings and the contact types.) The type RIS-FR is also providing remote reset and test inputs. By closing one of these contacts (e.g. by a remote controlled relay contact), all FLA3.1 in range of the RIS-FR will perform a reset resp. test. figure 1: RIS-FR housing figure 2: RIS-FR circuit board The remote indication interface type RIS-FR consists of a circuit board, which can be retrofitted into an existing housing of a remote indication device. Alternatively the board can be provided inside a sepa- thium batteries and can optional- ly be equipped with the external lifetime of the batteries depends (minimum life time: 10 years with 30 faults a year without external Please note: Short-circuit indi- cators type FLA3 are also fully compatible with the RIS-FR. Short Circuit indicators type FLA3.1 short range radio signal Remote Indication Interface type RIS-FR -retrofitted circuit board- Existing remote indication system figure 3: function of RIS-FR ELEKTRO-MECHANIK EM GMBH Document Rev. 7 Ringstr. 4 - D-42553 Velbert / Germany Page 1

 Open the catalog to page 1
REMOTE INDICATION INTERFACE TYPE RIS-FR-2

DATA SHEET Subject dimensions: housing height: 130 mm width: 178 mm depth: 52 mm dimensions: circuit board protection class: housing suitable for surface installation on site function test a) battery test b) test all FLA3.1 in range c) reset all FLA3.1 in range 433MHz radio interface for communication with FLA3.1 internal type tests operation temperature range power supply a) 3 pcs. lithium batteries (LiSOCl2) type AA / 3.6V/2.6Ah b) optional: 12 - 48 VDC c) optional: 115V AC / 230V AC SCADA contact a) 9 potential free NO contacts for 9 FLA3.1s Contact type depends on the FLA3.1’s remote function:...

 Open the catalog to page 2
REMOTE INDICATION INTERFACE TYPE RIS-FR-3

Ringstr. 4 - D-42553 Velbert / Germany

 Open the catalog to page 3
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.