1. Catalogs
  2. Elektro Mechanik
  3. FAULT INDICATOR TYPE EKL8000NG / EKL8001NG

FAULT INDICATOR TYPE EKL8000NG / EKL8001NG

FAULT INDICATOR TYPE EKL8000NG / EKL8001NG

FAULT INDICATOR TYPE EKL8000NG / EKL8001NG

Product catalog summary
General Description: The document describes an earth-fault and short-circuit indicator suitable for radial and ring networks. It requires solidly or low resistance-earthed networks for earth-fault detection. The system uses fibre optic cables for potential-free connections between sensors and the display unit. The sensors are divisible and can be retrofitted, with the short-circuit sensor applicable to both screened and unscreened cables, while the earth-fault sensor is for screened cables only. The EKL8001NG model includes two remote contact relays for separate fault indications.
Features and Options: The indicator provides permanent earth-fault indication via LED blinking, and a second short-circuit pass-through indication. It includes an optional reset input for 230 V AC recovery. External connectors are available for various functions, including SCADA remote contacts and external blinking lamps.
Specifications: The short-circuit trip current is adjustable between 200 to 1200 amps, and the earth-fault trip current between 10 to 100 amps. The response delay is adjustable from 40 to 160 ms. The indication unit is panel-mountable, with LEDs for short-circuit, earth-fault, and battery status. Reset options include manual, remote, timed, and automatic after 230 VAC recovery. The unit supports on-site function and battery tests via push-button.
Technical Data: The indication unit dimensions are 97 mm x 48 mm x 47 mm, with a protection class of IP40, while the short-circuit sensor is IP67. The operating temperature range is -25°C to +70°C, powered by a 3.6V lithium battery. SCADA contacts vary between models, with EKL8000NG having one NO and one NC, and EKL8001NG having two NO contacts. The sensors include three short-circuit sensors for single-core cables and one earth-fault sensor for three-core cables, with specified diameters and connection cable lengths.
See more

Catalog excerpts

FAULT INDICATOR TYPE EKL8000NG / EKL8001NG-1

FAULT INDICATOR General description The earth-fault and short-circuit indicator can be used in radial networks with one input and ring networks. For earth-fault de- tection, the network has to be solidly earthed or low resistance- The potential-free connections between the short-circuit sensors, the earth-fault sensor and the display unit are done by fibre opti- cal cables. The short-circuit sensor can be mounted on screened and unscreened cables. The earth-fault sensor must be mounted All sensors are divisible and can be retrofitted on the cable. The fault indicators of the NG-Series have a compact design with low installation depth. The earth-fault and short-circuit indicator type EKL8001NG is equipped with two remote contact relays to indicate earth-faults Permanent earth-faults: Indication of permanent earth-faults by double blinking of the earth- 2nd short-circuit pass-through: Indication of a second short-circuit passing through by double blin- king of the respective short-circuit LED. Optional reset input: For reset by recovering 230 V AC External connectors Optical terminal (triple): Optical terminal (single): Connectors to short-circuit sensors L1, L2, L3 Connector to earth-fault sensor Remote reset input External blinking lamp (Type BL3.1 and BL4.1) Reset input for recovering 230 V AC (not for supply) SCADA remote contact (NC) SCADA remote contact (NO) SCADA remote contact for earth-fault indication (NO) SCADA remote contact for short-circuit indication (NO) Reset Input Reset Input Blinking white - ^~|| I IEFI licl I NO- ELEKTRO-MECHANIK EM GMBH Document Rev. 3 Ringstr. 4 - D-42553 Velbert / Germany Page 1

 Open the catalog to page 1
FAULT INDICATOR TYPE EKL8000NG / EKL8001NG-2

DATA SHEET General data Subject short-circuit trip current (phase to phase) earth-fault trip current (phase to ground) response delay indication unit suitable for panel installation indication of a) short-circuit b) earth-fault c) battery a) one red LED for each phase b) one red LED for earth-fault c) one yellow LED a) manual by push-button b) connection for a potential-free remote reset c) time*: 1 / 2 / 4 / 8 (+/-1%) hours after fault d) self-acting after recovering of 230 VAC (the 230 VAC connector is only for reset, not for supply!) on site function test a) function test b) battery test by...

 Open the catalog to page 2
FAULT INDICATOR TYPE EKL8000NG / EKL8001NG-3

Indication unit type EKL8000 NG Erstellt am/von: yy. Kusserow/ drawing number: Ringstr. 4 - D-42553 Velbert / Germany

 Open the catalog to page 3
FAULT INDICATOR TYPE EKL8000NG / EKL8001NG-4

DATA SHEET ELEKTRO-MECHANIK EM GMBH Ringstr. 4 - D-42553 Velbert / Germany Tel: +49 2053 422890 - Fax: +49 2053 422899 www.emg-ger.com

 Open the catalog to page 4
FAULT INDICATOR TYPE EKL8000NG / EKL8001NG-5

Ringstr. 4 - D-42553 Velbert / Germany

 Open the catalog to page 5
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.