Modular optical fiber telecontrol System
6Pages

{{requestButtons}}

Catalog excerpts

Modular optical fiber telecontrol System - 1

Modular optical fibre telecontrol system Point to point data transmission via optical fibre › Uni or bi-directional point to point data transmission › Modular configuration for up to 32 I/O modules › Distance up to 30 km dependent on optical fibre type › Optical fibre (Multimode 50/125 µm) or Singlemode (9/125 µm) › Extremely simple parameterization of the modules via DIP switches Data sheet MFW-LWL-

Open the catalog to page 1
Modular optical fiber telecontrol System - 2

modular optical fibre telecontrol system Functional description The fibre optic variant of the MFW modular telecontrol system was developed for data transmission on fibre optic cables. The use of optical fibres as transmission medium ensures a robust interference-free transmission over long distances. A separate fibre optic cable is used for each transmission direction. Two versions are available for coupling the different fibre optic cable types: 1. Multimode fibres with 50/125 µm or 62,5/125 µm core/cladding diameter. Wavelength 1300 nm 2. Single mode fibres with 9/125 µm core/cladding...

Open the catalog to page 2
Modular optical fiber telecontrol System - 3

monitoring via optical fibre I/O unit (galvanically separated) Modem unit (optical fibre) CPU unit Alive relay Basic module with 8 digital inputs Terminal assignments I/O unit (galvanically separated) Antenna jack Modem unit (optical fibre) CPU unit Antenna jack Alive relay Basic module with 8 output relays Dimensional drawing Dimensions in mm Basic module

Open the catalog to page 3
Modular optical fiber telecontrol System - 4

modular optical fibre telecontrol system Technical data General data Mounting on C DIN rail TS35 acc. to EN60715 Housing / protection class ABS / IP 40 Connection terminals pluggable Conductor cross section rigid or flexible without wire end sleeves 0,2 ... 2,5 mm2 with wire end sleeves 0,25 ... 2,5 mm2 Operating and ambient temperature -20 °C ... + 60 °C Humidity maximum 95 % non-condensing Optical fibre Plugs sockets type SC-duplex acc. to norm IEC 60874-13 Signal delay < 100 ms Budget minimal/typical Singlemode-OF @1310 nm with 9/125 µm-OF 12 dB / 18 dB Multimode-OF @1300nm with 50/125...

Open the catalog to page 4
Modular optical fiber telecontrol System - 5

monitoring via optical fibre Technical data Basic modules with 8 relay outputs Power consumption (only basic module) maximum 3,5 W 2 Contact rating of the relay outputs* minimum 1,2 V / 1 mA (Suitable for controlling LEDs) maximum 250 V AC / 400 mA 250 V AC / 2 A (pure resistive load) 30 V DC / 2 A 110 V DC / 0,2 A 220 V DC / 0,1 A Total current 230 V AC maximum 8 A (pure resistive load) Counter frequency 12 Hz*2 Pulse width / Pause 40 ms*2 Galvanic isolation between output and supply voltage 4 kVeff Electromagnetic compatibility acc. to EN 61000-6-2 EN 61000-6-4 + A1 EN 61000-4-2 EN...

Open the catalog to page 5
Modular optical fiber telecontrol System - 6

modular optical fibre telecontrol system Order identification Multimode 50/125 µm-Optical fibre @1300 nm, plugs SC-duplex acc. to norm IEC 60874-13 Master modules / Substation modules Article number Type 97BLEGANBBB3 MF-L1M1C-G8DEX-DIA-B-BB-3 97BLEGCNBBX3 MF-L1M1C-G8DAR-DIA-B-BX-3 97HLEGANBBB3 UF-L1M1C-G8DEX-DIA-B-BB-3 97HLEGCNBBX3 UF-L1M1C-G8DAR-DIA-B-BX-3 Module type / Process interface Master / 8 digital inputs 24 V Master / 8 relay outputs Substation / 8 digital inputs 24 V Substation / 8 relay outputs Singlemode 9/125 µm-Optical fibre @1310 nm, plug SC-duplex acc. to norm IEC 60874-13...