1. Catalogs
  2. Elektra Elektronik GmbH & Co. Störcontroller KG
  3. Modular optical fiber telecontrol System

Modular optical fiber telecontrol System

Modular optical fiber telecontrol System

Modular optical fiber telecontrol System

Product catalog summary
Overview: The document describes the Modular Optical Fibre Telecontrol System, designed for uni or bi-directional point-to-point data transmission over optical fibres. It supports modular configurations with up to 32 I/O modules and can cover distances up to 30 km, depending on the fibre type used.
Specifications: The system supports both multimode (50/125 µm) and singlemode (9/125 µm) optical fibres, with respective wavelengths of 1300 nm and 1310 nm. The transmission range varies based on fibre type, connector, and splice losses, with singlemode supporting up to 30 km and multimode up to 22 km.
System Components: Each station requires a basic module, which includes an internal fibre optic modem, USB-B socket for diagnostics, I/O module with 8 relay outputs or binary inputs, and various sockets for system bus connections. Expansion modules can be added to increase I/O capacity.
Technical Data: The system is mounted on a C DIN rail and housed in ABS with IP 40 protection. It operates within a temperature range of -20°C to +60°C and supports a maximum humidity of 95% non-condensing. The system bus uses an RJ11 plug based on CAN-Bus, with a maximum distance of 10 m.
Electrical Specifications: The operating voltage is 24 V DC, with a range of 20 to 32 V DC. The basic module's power consumption is approximately 2.5 W, and it provides galvanic isolation between signal and supply voltage at 4 kVeff.
Compatibility and Standards: The system complies with various electromagnetic compatibility standards, including EN 61000-6-2 and EN 61000-6-4. It is recommended to use DC voltage for pulse inputs.
Modules and Accessories: The document lists various master and substation modules for both multimode and singlemode fibres, along with extension modules for digital and analog inputs/outputs. Accessories include connection cables, power supplies, and buffer chargers.
Important Notes: Older MFW extension modules without specific type designations are incompatible with the optical fibre modem basic modules.
See more

Catalog excerpts

Modular optical fiber telecontrol System-1

Modular optical fibre telecontrol system Point to point data transmission via optical fibre › Uni or bi-directional point to point data transmission › Modular configuration for up to 32 I/O modules › Distance up to 30 km dependent on optical fibre type › Optical fibre (Multimode 50/125 µm) or Singlemode (9/125 µm) › Extremely simple parameterization of the modules via DIP switches Data sheet MFW-LWL-

 Open the catalog to page 1
Modular optical fiber telecontrol System-2

modular optical fibre telecontrol system Functional description The fibre optic variant of the MFW modular telecontrol system was developed for data transmission on fibre optic cables. The use of optical fibres as transmission medium ensures a robust interference-free transmission over long distances. A separate fibre optic cable is used for each transmission direction. Two versions are available for coupling the different fibre optic cable types: 1. Multimode fibres with 50/125 µm or 62,5/125 µm core/cladding diameter. Wavelength 1300 nm 2. Single mode fibres with 9/125 µm core/cladding diameter....

 Open the catalog to page 2
Modular optical fiber telecontrol System-3

monitoring via optical fibre I/O unit (galvanically separated) Modem unit (optical fibre) CPU unit Alive relay Basic module with 8 digital inputs Terminal assignments I/O unit (galvanically separated) Antenna jack Modem unit (optical fibre) CPU unit Antenna jack Alive relay Basic module with 8 output relays Dimensional drawing Dimensions in mm Basic module

 Open the catalog to page 3
Modular optical fiber telecontrol System-4

modular optical fibre telecontrol system Technical data General data Mounting on C DIN rail TS35 acc. to EN60715 Housing / protection class ABS / IP 40 Connection terminals pluggable Conductor cross section rigid or flexible without wire end sleeves 0,2 ... 2,5 mm2 with wire end sleeves 0,25 ... 2,5 mm2 Operating and ambient temperature -20 °C ... + 60 °C Humidity maximum 95 % non-condensing Optical fibre Plugs sockets type SC-duplex acc. to norm IEC 60874-13 Signal delay < 100 ms Budget minimal/typical Singlemode-OF @1310 nm with 9/125 µm-OF 12 dB / 18 dB Multimode-OF @1300nm with 50/125 µm-OF...

 Open the catalog to page 4
Modular optical fiber telecontrol System-5

monitoring via optical fibre Technical data Basic modules with 8 relay outputs Power consumption (only basic module) maximum 3,5 W 2 Contact rating of the relay outputs* minimum 1,2 V / 1 mA (Suitable for controlling LEDs) maximum 250 V AC / 400 mA 250 V AC / 2 A (pure resistive load) 30 V DC / 2 A 110 V DC / 0,2 A 220 V DC / 0,1 A Total current 230 V AC maximum 8 A (pure resistive load) Counter frequency 12 Hz*2 Pulse width / Pause 40 ms*2 Galvanic isolation between output and supply voltage 4 kVeff Electromagnetic compatibility acc. to EN 61000-6-2 EN 61000-6-4 + A1 EN 61000-4-2 EN 61000-4-3...

 Open the catalog to page 5
Modular optical fiber telecontrol System-6

modular optical fibre telecontrol system Order identification Multimode 50/125 µm-Optical fibre @1300 nm, plugs SC-duplex acc. to norm IEC 60874-13 Master modules / Substation modules Article number Type 97BLEGANBBB3 MF-L1M1C-G8DEX-DIA-B-BB-3 97BLEGCNBBX3 MF-L1M1C-G8DAR-DIA-B-BX-3 97HLEGANBBB3 UF-L1M1C-G8DEX-DIA-B-BB-3 97HLEGCNBBX3 UF-L1M1C-G8DAR-DIA-B-BX-3 Module type / Process interface Master / 8 digital inputs 24 V Master / 8 relay outputs Substation / 8 digital inputs 24 V Substation / 8 relay outputs Singlemode 9/125 µm-Optical fibre @1310 nm, plug SC-duplex acc. to norm IEC 60874-13 Master...

 Open the catalog to page 6

Archived catalogs

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.