LAB-Series
8Pages

{{requestButtons}}

Catalog excerpts

LAB-Series - 1

Indication modules LED indication modules with collective contact › Indicator modules in panel mounting housing with 8, 16, 24, 32, 40 or 48 signal inputs › Available in 6 color variants, LED colors can be modified by the customer using exchangeable light pipes › Low power consumption (less than 1 W) › Wide range power supply and signal inputs (24 V - 230 V AC/DC) › Integrated lamp test button and connection option for external button › Easy configuration via DIP switch (NO / NC version, collective signal formation, inversion of collective signal) › Operation indication via OK LED › Labeling strips can be inserted in transparent window Datasheet SM-LA

Open the catalog to page 1
LAB-Series - 2

LED-signalling modules Device description The LAB signaling modules are compact indication units in a panel mounting housing with 8, 16, 24, 32, 40 or 48 signaling inputs. The units have an internal lamp test button and the connection for an additional external button. DIP switches are located under the front panel of the unit to configure the following functions: • Group-wise (groups of 8) switching between normally open and normally closed principle of the inputs • Group-wise (groups of 8) inclusion in the collective alarm • Inverting the collective alarm If the input of a group is...

Open the catalog to page 2
LAB-Series - 3

indication modules Technical Data Operation voltage USup DC voltage 24 – 230 V DC (- 15% / + 20%) AC voltage 24 – 230 V AC 50/60 Hz (-15% / + 10%) Bridging time during power failure USup < 110 V at least 10 ms res. 0,5 periods USup > 110 V at least 100 ms res.. 5 periods Alarm inputs Response delay Nominal voltage [V AC/DC] 24 - 230 Switching threshold for alarm* [V] +/- 20% On Off DC AC DC AC 16,5 14 13 13 Maximum permissible voltage [V AC/DC] * The switching thresholds refer to use at room temperature. Different voltages can be supplied on request. Power consumption Number of channels 8...

Open the catalog to page 3
LAB-Series - 4

LED-signalling modules Depth with front frame and terminals [mm] The specifications for AC voltage are given as effective values and refer to a sinusoidal AC voltage with a frequency of 50 / 60 Hz. All data refer to an ambient temperature of 25 °C.

Open the catalog to page 4
LAB-Series - 5

indication modules Terminal assignments Collective alarm Alarm inputs Alarm inputs Alarm inputs Alarm inputs Alarm inputs Alarm inputs Lamp test The alarm inputs 9 - 16 are not assigned for the LAB08. If the signal inputs are operated in normally closed mode, unused inputs must be connected to + or L.

Open the catalog to page 5
LAB-Series - 6

LED-signalling modules DIP-Switch After taking off the front frame and removing the front panel, DIP switches become visible. In the following figure, a LAB with 48 alarms is shown as a representative of all devices. Depending on the number of channels of the indication module, there are different numbers of DIP switches and they have the functions described in the tables below. Function with switch position „ON“ LAB 08 LAB 16 Alarm 1-8 is included in the collective alarm Alarm 1-8 is included in the collective alarm formation formation Alarm 9-16 is included in collective alarm formation...

Open the catalog to page 6
LAB-Series - 7

indication modules LAB 24 and LAB 32 Function with switch position „ON“ Alarm 1-8 is included in collective alarm formation Alarm 9-16 is included in collective alarm formation Alarm 9-16 is included in collective alarm formation Input 1-8 in normally closed principle Input 9-16 in normally closed principle Collective relay inverted No function Alarm 17-24 is included in collective alarm formation Input 17-24 in normally closed principle No function No function No function Alarm 1-8 is included in collective alarm formation Input 1-8 in normally closed principle Input 9-16 in normally...

Open the catalog to page 7
LAB-Series - 8

LED-signalling modules Number of alarm channels 8 alarm inputs 16 alarm inputs 24 alarm inputs 32 alarm inputs 40 alarm inputs 48 alarm inputs Operating and signalling voltage 24 - 230 V AC/DC (wide range) LED color group 1 (channels 1 - 8) R-red, G-green, Y-yellow, B-blue, W-white, A-orange LED color group 2 (channels 9 - 16) R-red, G-green, Y-yellow, B-blue, W-white, A-orange, O not available LED color group 3 (channels 17 - 24) R-red, G-green, Y-yellow, B-blue, W-white, A-orange, O not available LED color group 4 (channels 25 - 32) R-red, G-green, Y-yellow, B-blue, W-white, A-orange, O...

Open the catalog to page 8