Overview: This datasheet provides technical specifications and operational details for 3-phase voltage monitoring relays used in AC networks. The document covers various models designed for under voltage, over voltage, and absence of voltage supervision.
1. EUW3 - Under and Over Voltage Supervision:
  • The EUW3 model monitors three-phase networks for both under and overvoltage, with independently adjustable switching points to avoid range overlaps.
  • It detects phase asymmetry and failure, monitors phase sequence and neutral break, and uses LEDs for fault indication.
  • The relay is energized during normal operation and de-energizes upon fault detection, with adjustable response and drop-out delays to handle short disturbances.
  • The 11EUW3000S1 variant includes extended buffering to prevent relay triggering during short power failures.
2. Technical Data for EUW3:
  • Supply voltage: 230 V 50/60 Hz, with a range of 195-253 V.
  • Monitoring inputs cover 50-460 V, with a maximum input current of ≤ 0.5 mA.
  • Relay outputs support up to 4 A at 250 V AC/DC, with adjustable response delays.
  • Operating temperature ranges from -20°C to +60°C, with a maximum relative humidity of 75%.
3. EUW4 - Under Voltage Supervision:
  • The EUW4 model focuses on undervoltage monitoring, detecting phase asymmetry and failure, with adjustable or fixed switching thresholds.
  • It operates without additional auxiliary voltage, using the measuring voltages for power supply.
4. Technical Data for EUW4:
  • Monitoring inputs vary by model, with voltage ranges from 70-420 V.
  • Relay drops out upon undervoltage or phase failure, with response delays for different fault types.
  • Operating conditions are suitable for 3-phase networks with neutral or star points.
5. EUW4S - Monitoring for Absence of Voltage:
  • This model signals absence of voltage when all phase voltages fall below a set threshold, unaffected by neutral break.
  • Switching thresholds can be adjustable or fixed, depending on the variant.
6. Technical Data for EUW4S:
  • Supply/measuring voltage is 110 V AC, with a maximum of 150 V and a minimum of 18 V.
  • Response delay is less than 100 ms, with a load capacity of 3 A at 250 V AC/DC.
7. Ordering Codes and Dimensions:
  • Various models are available with different voltage ranges and features, identified by specific article numbers.
  • Dimensions and terminal assignments are provided for installation guidance.
See more

Catalog excerpts

EUW-Series-1

3-phase voltage monitoring relays 3-phase voltage supervision in AC networks › Under voltage supervision › Over voltage supervision › Monitoring for absence of voltage Datasheet IN-EUW-DB-UK-

 Open the catalog to page 1
EUW-Series-2

voltage monitoring in AC Networks EUW3 - Under and over voltage supervision › Voltage supervision per single phase › Switching thresholds adjustable › Monitoring for asymmetry, phase failure and phase sequence › LED operating display and signal contacts designed as potential-free double changeover contacts The EUW3 monitors three-phase networks for undervoltage and overvoltage, whereby both switching points can be set independently of each other. Here, range overlaps are to be avoided. Monitoring is performed separately for each phase, so that actual asymmetry or even phase failure is detected....

 Open the catalog to page 2
EUW-Series-3

voltage monitoring in AC Networks Technical Data EUW3 Article number Supply voltage UB Nominal voltage Voltage range Power consumption Buffer time for UB Min. charging time until buffer ready again Monitoring inputs Voltage range Max. input current Switching hysteresis Switching accuracy Monitoring criteria Relay outputs Voltage range Max. load current Response delay Displaying elements Ambient conditions Operation temperature Max. rel. humidity AC voltage resistance between measuring inputs and relay contacts as well as the open relay contacts EMC compatibility acc. to Mechanical data Connection...

 Open the catalog to page 3
EUW-Series-4

voltage monitoring in AC Networks EUW4 - Under voltage supervision › Voltage supervision per single phase › Switching thresholds adjustable or optionally fixed › Monitoring for asymmetry, phase failure and neutral conductor breakage › LED operating display and signal contacts designed as potential-free double changeover contacts The EUW4 monitors three-phase networks for undervoltage. The monitoring is not only carried out for the average value of the voltages, but separately for each phase. This detects an asymmetry of the phases or even a phase failure. The switching threshold is, depending...

 Open the catalog to page 4
EUW-Series-5

voltage monitoring in AC Networks Technical data EUW 4 Article number Monitoring inputs Voltage range ULxLy Power frequency Measuring voltage Switching point adjustment range max. power consumption Switching point hysteresis Switching point accuracy Monitoring criteria Relay drops out at Undervoltage, phase failure Undervoltage or failure of one phase Response delay (Phase failure / Neutral wire break) 50 ms 150 ms (Asymmetry of a phase of 20%) green LED for operating display - for 3-phase networks with neutral or star point - suitable for automatic switching on of safety lighting according to...

 Open the catalog to page 5
EUW-Series-6

voltage monitoring in ac networks EUW4S - Monitoring for absence of voltage › Switching threshold adjustable or optionally fixed › LED operation display › Signal contacts designed as potential-free double changeover contacts The voltage monitor monitors 110 V three-phase networks for absence of voltage.Only when the voltages of all phases fall below the US threshold is the absence of voltage signaled by the red operating indicator going out and the relay dropping. Neutral break has no effect on this signaling. The threshold US refers to the delta voltage ULxLy and, depending on the design variant,...

 Open the catalog to page 6
EUW-Series-7

voltage monitoring in ac networks Technical Data EUW4SA1S/2S Article number Supply/measuring voltage (Chained voltage ULxLy, RMS) maximum minimum Switching threshold US Hysteresis Response delay Load capacity of the relay contacts Maximum switching voltage Power consumption Environmental conditions Operating ambient temperature Storage temperature Relative humidity AC voltage resistance between measuring inputs and relay contacts AC voltage resistance of the opened Relay contacts EMC compatibility according to Mechanical data Terminals Dimensions (H x B x T) [mm] Mounting Weight Safety class...

 Open the catalog to page 7
EUW-Series-8

voltage monitoring in ac networks Dimensional drawing and terminal assignment Measuring voltage Operating voltage Dimensions in mm Subject to technical changes without prior notice Ordering codes Low- and high-voltage supervision Article number Short description 11EUW3000U 50 … 460 V 50/60 Hz, switching points adjustable 11EUW3000S1 50 … 460 V 50/60 Hz, switching points adjustable, extended buffer time of the operating voltage Low-voltage supervision Article number 11EUW4000Q 11EUW4000U 11EUW4000U2 11EUW4SA0S Short description 80 … 120 V 50/60 Hz, switching points adjustable 270 … 420 V 50/60...