Drop-flap Fault Annunciator
8Pages

{{requestButtons}}

Catalog excerpts

Drop-flap Fault Annunciator - 1

Parameterisable compact fault annunciator with permanent display FSM 10 Drop-flap fault annunciator › Permanent display even on power failure › Compact module for 10 alarms › Supply and alarm signal voltage 12 V...250 V AC/DC › Indication with 10 green indicating discs with green LED › Live contact and nonvolatile history- / eventmemory ( time resolution 5 ms ) › 4 output relays and 4 programmable buttons, 6 functional inputs › 2 parameterisable collective reports and internal horn › Parameterisation via DIP switches or PC programm › Pluggable connection terminals ( Screw- or spring cage terminals ) › Marker strips pocketable into transparent window

Open the catalog to page 1
Drop-flap Fault Annunciator - 2

FSm 10 drop-flap fault annunciator Functional description The compact FSM 10 drop-flap fault annunciator is installed in a housing for panel-mounting according to DIN 43781. It has 10 green indicating discs, each featuring a LED for displaying the signals. With very compact design, the fault annunciator offers energy-independent long-term storage of active signals via bi-stable mechanical indicating elements. No battery backup is required. The messages are clearly visible at any time irrespective of lighting conditions. The integrated event memory, which can be read via the serial...

Open the catalog to page 2
Drop-flap Fault Annunciator - 3

AN ANNUNCIATOR FROM THE MSM PRODUCT FAMILY In order to adapt the fault annunciator to a wide range of different applications, the following parameter can be modified • delay times for each individual alarm input • NC or NO processing for each individual alarm input • assignment of the inputs to the two reporting groups • definition of the reporting procedure for the reporting groups • definition of the key functions and function inputs • assignment of relay function to the outputs (e.g. ^\.2, horn 1, horn 2, alive message) • horn sounding duration with automatic acknowledgement Appearing...

Open the catalog to page 3
Drop-flap Fault Annunciator - 4

FSm 10 drop-flap fault annunciator Collective report Collective report static / parallel to input The collective report is set by the first upcoming alarm and is still active as long as there is an alarm lining up. It is reset automatically without acknowledgement when all alarms have gone. static / parallel to output The collective report is set when an alarm is upcoming and only resets if all alarms have been gone and been acknowledged. Horn will be retriggered, even if there are messages already lining up. Horn will only be retriggered, if no messages are longer present manual (...

Open the catalog to page 4
Drop-flap Fault Annunciator - 5

an annunciator from the MSM product family Type Article no. Supply voltage Rated voltage Range 110 V AC/DC 55 ... 130 V AC/DC approx. 70 kΩ 220 V AC/DC 150 ... 260 V AC/DC approx. 200 kΩ Insulation of the supply voltage against all other voltages Voltage of the reporting and function inputs Rated voltage Range Input resistance Other voltages can also be supplied on demand. Power consumption Response delay Horn sounding duration with automatic acknowledgement Load capacity of relay contacts minimum maximum LED flashing frequency Flashing Slow flashing Insulation voltage Reporting and...

Open the catalog to page 5
Drop-flap Fault Annunciator - 6

FSM 10 DROP-FLAP FAULT ANNUNCIATOR Protection class at the front Protection class at the rear Connection terminals Cross-section rigid or flexible without wire sleeves with wire sleeves Permissible relative humidity Noise immunity IP 54; IP 65 with transparent protective cover = 75% on average over the year (group F DIN 40040) The information given for alternating voltages are refering to a sinusoidal alternating voltage with a frequency of 50/60 Hz and all information on an ambient temperature of 25°C, otherwise noted. Terminal assignments

Open the catalog to page 6
Drop-flap Fault Annunciator - 7

an annunciator from the MSM product family Dimensional drawing Dimensions in mm Subject to technical changes without prior notice Ordering codes Standard devices Article No Type Supply and signalling voltage 12 V AC/DC 24 V AC/DC 48 V AC/DC and 60 V DC 110 V AC/DC 220 V AC/DC Parameterisation cable for MSM-family Transparent protection cover DCF77-Active antenna CAN-Bus connecting cable CAN-Bus connecting cable Cable length 1.5 m IP 65 Cable length 2.5 m (FSM 10 - FSM 10), length 20 cm (FSM 10 - FSM 10), length 50 cm

Open the catalog to page 7
Drop-flap Fault Annunciator - 8

FSm 10 drop-flap fault annunciator Do you need alternative fault annunciators or operation indicators ? LED - indication modules • • • • • • • Compact module in a 96 x 96 mm housing for panel mounting 8 or 16 channels with exchangeable LED’s Several alarm voltages in a range from 24 V up to 230 V Integrated lamp test push button Collective report optional Front panel marking: transparent window for slide-in labels Low built-in depth BSM - Panel mounting basic fault annunciators • • • • • • • • Devices with 8, 16, 32 and 48 Signal inputs Sealed front, protection class IP 54 Integrated...

Open the catalog to page 8