Introduction
AC capacitors are utilized for enhancing power factor in fluorescent and gas discharge lamps, achieving a power factor greater than 0.9. These capacitors are produced using MKP technology with a low-loss dielectric made from pure polypropylene film, and they are free from PCB and other toxic substances.
Specifications
Designed for 250V, 50/60Hz networks, these capacitors have a test voltage of 2.15 UN ac and 3000V ac, with an operational temperature range from -40°C to +85°C. They include a discharge resistor that reduces voltage to less than 50V within 60 seconds, with a tolerance of ±10% (optional ±5%).
Standards and Approvals
Compliant with IEC/DIN EN 61048:2006 for safety and IEC/DIN EN 61049 for performance, these capacitors also have GOST and CQC approvals.
Design and Construction
Available with or without internal temperature fuses, these capacitors feature push-wire terminals and integrated discharge resistors. They are constructed with plastic or aluminum cans and can be mounted in various positions.
Operating Instructions
Safe operation requires adherence to specified electrical and thermal limits. Capacitors should not be exposed to dew or high humidity, with hermetically sealed options recommended for such conditions.
Procedures
Capacitors should be mounted using an M8 base mounting stud, with lateral clip options available. They can be installed in any position but should be kept away from heat and UV radiation. Special stabilized plastics are available for chemically exposed environments.
Standards and Compliance
RoHS compliance is confirmed for capacitors manufactured since October 2005, with no hazardous substances used. Fire load and disposal procedures are detailed, recommending recycling through professional centers.
Recommendations
Avoid overvoltage and excessive heat to prevent reduced service life. Specific guidelines for overvoltage durations are provided to prevent failure.
Safety and Disposal
Made from flame-retardant materials, capacitors are classified as non-hazardous for transport. Proper disposal methods are outlined, emphasizing use only for intended applications to avoid safety risks.
Key Data from Tables and Charts
Data includes relative humidity limits, operating temperature effects on service life, and overvoltage duration limits. A 10% increase in voltage or a 7°C increase in temperature can halve the expected lifetime of a capacitor.
Specifications and Safety Measures
Potential risks include overtemperature, overvoltage, incorrect application, and poor maintenance. Internal protective mechanisms have limits, and exceeding these can lead to failures.
Self-Healing Dielectric
Capacitors use self-healing dielectric structures that isolate short-circuit points, maintaining functionality. This ability diminishes with age and constant overload.
Temperature Fuse for Type A Capacitors
A thermal fuse is available for lighting capacitors without overpressure protection, melting at critical temperatures to prevent re-ignition.
Warnings and Recommendations
The safety system is effective only within permitted load limits. Strong overvoltages and external heat can cause rapid temperature and pressure increases, potentially leading to explosions.
Warranty Information
A two-year limited warranty covers defects from design, materials, or workmanship, excluding improper use, maintenance, or installation, and normal wear and tear.
Packing Details
Dimensions and packing details for various box types used for shipping capacitors are provided.
See more

Catalog excerpts

E05/E06 - Capacitors Type A for parallel compensation-1

E01/E02/E05/E06 AC CAPACITORS FOR PARALLEL COMPENSATION IN FLUORESCENT LIGHTING WECHSELSPANNUNGSKONDENSATOREN FUR DIE PARALLELKOMPENSATION IN FLUORESZENZLEUCHEN

 Open the catalog to page 1
E05/E06 - Capacitors Type A for parallel compensation-3

Capacitors for Fluorescent and Gas Discharge Lamps Compwsating capacitors in HKP-tedinology art AC capaotws teigned far hriliBt cwrucbon ol thi parti faclor of Uanstamers and majiwtic ballasts in dsdtarge bnps (ej. fluorescent lamps. halogen and mtal «pour Laraps. high-pressure mpcury voposr lafrɧs. sodium lamps] in mains wth a fr*qu«ncy of SO « 60 * Thts *Uws for an improvffunt of tto lununaiy s pcwer factor to cos <f * 0.9. The correction of The pemr factoi ol fluorescent tjmps an be effected in &call*d indrnduat andfaf group condensation AU cfacitors bsted in thts catatope are manufaetured...

 Open the catalog to page 3
E05/E06 - Capacitors Type A for parallel compensation-10

MOUNTING AND OPERATING INSTRUCTIONS VORSCHRIFTEN ZU BETRIEB UND EINBAU ZVGI: Mounting and Operating Instructions Safe opration of the capacitors can be expected only if ail electrical and thermal specifications as stated on the label, in the data sheets or catalogues and the following instructions are strictly observed. Vorschriften zu Betrieb und Einbau Grundsatzlich ist ein sicherer Betrieb der Kondensatoren nur ge-wahrleistet, wenn die elektrischen und thermischen Grenzwerte gemaB Typenschild, Datenblatt bzw. Katalog und die nachfolgenden Anweisungen eingehalten werden. Starkstromkondensatorer...

 Open the catalog to page 10
E05/E06 - Capacitors Type A for parallel compensation-11

Connection and fixation Anschluss und Befestigung The capacitors are fixed by an M8 base mounting stud. For lighting capacitors Die Befestigung erfolgt mit M8 Bodenschraube. Fur Leuchtkondensatoren in plastic can an alternative fixation with lateral clip is available. im Kunststoffbecher sin aufierdem Varianten mit seitlicher Befestigung (Seitenclip") erhaltlich. The following kinds of connection are available as standard. Please see the Im Standardsortiment sind die folgenden Anschlussarten verfugbar Details data charts on pages 6 - 8 for details on each type series. zu den einzelnen Baureihen...

 Open the catalog to page 11
E05/E06 - Capacitors Type A for parallel compensation-12

Piro I narl Brandiast E AU outer parts of our capacitors are made of flame-retardant material. However it must be considered in the application that the filling resins, oils, and winding elements are flammable. The energy content of an MKP capacitor is approx. 40 MJ/kg. Alle Kondensatoren sind ufierlich aus flammhemmenden Materialien ge-fertigt. Vergussstoffe, Ole und das Wickelmaterial sind jedoch brennbar. Dem ist beim Einbau Rechnung zu tragen. Die Brandlast eines MKP-Kon-densators betrgt ca. 40 MJ/kg. o o o o RoHS Compliance Einhaltung der RoHS-Richtlinie ✓ RoHS I2002/95/EC According to current...

 Open the catalog to page 12
E05/E06 - Capacitors Type A for parallel compensation-13

Important Remarks Wichtige Hinweise Safety ELECTRONICON will not indemnify or be responsible for any kind of damages to persons or property due to the improper application of any capacitors pur-chased from ELECTRONICON or its distributors. The capacitors should only be used for the application intended. Mind that electrical or mechanical misapplication of capacitors can become hazardous. Misapplied capacitors can explode or catch fire and cause bodily injury or property damage due to the expulsion of material or metal fragments. Please consult the detailed instructions for mounting and application...

 Open the catalog to page 13
E05/E06 - Capacitors Type A for parallel compensation-14

Important: ! Overvoltage has a dramatic effect on service Life and risk of faillie: on average, a 10% increase of the operating voltage halves the expected life-time, or in other words, doubles the failure rate of a capacitor (compare "FIT rate" in our brochure "Application Notes"). ! Subject to inductive components within the capacitor circuit, motor run capacitors and capacitors connected in series with luminaire ballasts, are exposed to voltages which permanently exceed the rated mains voltage. This, and the tolerances of all elements in the circuit as well as their drift due to ageing effects,...

 Open the catalog to page 14
E05/E06 - Capacitors Type A for parallel compensation-15

spcial compound Spezialverbindunc thermal l驩ment Thermoelement Temprature Fuse (type A capacitors] For lighting capacitors without overpressure protection, ELECTRONICON offers a thermal fuse which is integrated in the capacitor core and which responds to overtemperatures caused by electrical or thermal overload. The fuse element within the body melts when a critical temperature is re-ached. It melts into small open globules which are completely insulated from each other not only by the distance but also by a special insulating compound which appears at the point of meltdown. The thermal disconnection...

 Open the catalog to page 15
E05/E06 - Capacitors Type A for parallel compensation-16

In its Suidelines for the Prmntio ot Damage Caused lm*fi%$4the Association ot Getman Pioperly bsvers - VdS - tanmfc: "Capacilors vrrthout oveiprtssure break*action mechanism must be encapsulateri in li WWJHI* m⫩tal caw which prevents the gntion of inflammable ma* Only cepacirxs wiOi break-action mechanism aresi* table for lis* in sen-sitire envirment ta casa ot doubt regarding th* character ot the ambtenl conditions wcapacrtwswitti break-actio« Mechanism shouldbeused. Dm Vertet4 dtr deutschefi Sacܠwf»c*im*i sagt in seiner RichtlM» mSchadenvtrhtung duich eiektrache LeucMen smngemafl. Bei Konden-...

 Open the catalog to page 16
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.