1. Catalogs
  2. Electromen
  3. EM-M17Bf/HZ converter

EM-M17Bf/HZ converter

EM-M17Bf/HZ converter

Product catalog summary
Technical Specifications:
  • Operating Voltage: 20...32 Vdc
  • Current Consumption: 50 mA max.
  • Linearity Error: 0.1% typical
  • Thermal Drift: < 100 ppm/°C
  • Transducer Supply: 15 Vdc, 8.5 Vdc (NAMUR)
  • Input Settings: Open collector NPN/PNP, NAMUR, pulse (isolated)
  • Input Range: 4...25 V
  • Input Impedance: Approx. 2 kohm
  • Frequency Ranges: 0...200, 500, 1000 Hz; 0...2, 5, 10, 20, 50 kHz
  • Output Filtering: 10 Hz (-3 dB)
  • Output Ranges: 0...10 V (RL > 1 kohm), 4...20 mA (RL < 500 ohm)
  • Adjustment Ranges: Gain ± 15%, Zero - 25%
  • Operating Ambient Temperature: 0...60 °C
Product Description:

The EM-M17b is a frequency-to-voltage/current converter that transforms applied frequency into a 0...10 V or 4...20 mA signal. It supports a wide range of frequency inputs, selectable via DIP-switches, and is compatible with most transducer types. The device can handle pulsed voltage signals and offers optical isolation for frequency inputs. It features a 2nd order filter to minimize frequency ripple and provides short circuit and overload protection. The converter is designed to operate over a wide voltage range and is protected against incorrect polarity.

Key Features:
  • Eight selectable frequency ranges
  • Isolated input for enhanced safety
  • High linearity for accurate signal conversion
  • Multiple input options including NPN, PNP, and NAMUR
  • Output options in mA or V
  • Effective output filtering
  • Protection against short circuits
  • Adjustable zero and gain settings
  • Rail mountable for easy installation
Additional Information:

The device dimensions are 79mm x 86mm with a housing width of 25mm. It includes various input modes and output modes, with specific settings for frequency and isolation. The converter is manufactured by ELECTROMEN Oy, located in Turku, Finland.

See more

Catalog excerpts

EM-M17Bf/HZ converter-1

EM-M17b F/UI -CONVERTER FEATURES: • Eight frequency ranges • Isolated input • High linearity • Various input options • Output signal mA or V • Good output filtering • Output short circuit protected • Adjustable zero & gain • Rail mountable EM-M17b converts applied frequency to 0...10 V or to 4...20 mA signal. Frequency range is selectable with DIP-switches. Converter can be used with most of the commonly available transducer types. Frequency can be applied also as a pulsed voltage signal. The frequency input can be isolated optically if transducer supply and SW1/1 is left open. Converted signal is filtered using a 2nd order filter so that the ripple of the incoming frequency is efficiently attenuated. The output of EM-M17b is both short circuit and overload protected. Operating voltage range is wide and the supply is protected against incorrect polarity.tttttttttttttttttttttt TECHNICAL DATA: Input settings Input range Input impedance Frequency ranges Output filtering Output ranges Adjustment ranges Oper. ambient temp. 20...32 Vdc 50 mA max. 0.1 % typical < 100 ppm/°C 15 Vdc 8.5 Vdc (namur) open collector NPN open collector PNP NAMUR pulse (isolated) 4...25 V appr. 2 kohm 0...200, 500, 1000 Hz 0...2, 5, 10, 20, 50 kHz 10 Hz ( -3 dB ) 0...10 V RL > 1 kohm 4...20 mA RL < 500 ohm Gain ± 15 % Zero - 25 % 0...60 °C SETTINGS OF EM-M17b FREQUENCY 1 2 3 4 5 6 7 8 INPUT MODE 1 2 3 200Hz 4 NPN OPEN-C 500Hz PNP OPEN-C 1kHz 86mm Operating voltage Current consumption Linearity error Thermal drift Transducer supply 79mm 2kHz NAMUR ISOL. IN 5kHz 10kHz 20kHz 50kHz Uout OUTPUT MODE Iout WIDTH OF THE HOUSING IS 25 mm SW1/4 OPEN COLLECTOR INPUT. 1.+ 2.SIGNAL 3.NAMUR INPUT. 1.+ 2.VOLTAGE INPUT (ISOLATED) 2. SIGNAL 3. GND 15/8.5V 1 VOLTAGE REGULATOR SENSOR VOLTAGE 4 +24V SW1/3 PULL UP/DOWN RES. 5 2 OUT IN GND (-IN) OPTO 3 SW1/2 ISOLATION SW1/1 F/U CONVERTER ZER0/GAIN U/I CONVERTER 6 GND OPEN FOR ISOL. ELECTROMEN Oy Vähäheikkiläntie 56B, 20810 Turku, FINLAND Tel. +358-2-4693050 Fax. +358-2-4693052

 Open the catalog to page 1
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.