Technical Specifications:
  • Operating Voltage: 20 to 32 V
  • Current Consumption: Maximum 70 mA
  • Linearity Error: Less than 0.1%
  • Thermal Drift: Less than 50 ppm/°C
  • Output Ranges: 0 to 1 V, 0 to 5 V, 0 to 10 V (RL > 1 kohm); 0 to 20 mA, 4 to 20 mA (RL < 700 ohm)
  • Input Ranges: 0 to 1 V (Rin 50 kohm), 0 to 5 V (Rin 250 kohm), 0 to 10 V (Rin 500 kohm), 0 to 20 mA, 4 to 20 mA (Rin 50 ohm)
  • Frequency Response: 0 to 1 kHz, 0 to 20 Hz
  • Adjust Ranges: Gain ± 20%, Zero ± 20%
  • Isolation Voltage: 1000 V
  • Operating Ambient Temperature: 0 to 60 °C
Product Overview:

The EM-M11A is a versatile multiscale galvanic signal isolator and conditioner designed for automation applications. It features easy range setting via DIP-switches and offers two signal frequency limits (1 kHz or 20 Hz). The module provides galvanic isolation up to 1000 V across input, output, and supply partitions. Adjustments for gain and zero are straightforward and independent, allowing for up to 25 input/output signal combinations.

Key Features:
  • Three-way isolation
  • Multiple operating ranges
  • Two selectable frequency ranges
  • DIP-switch configurable
  • Isolation up to 1000 V
  • Adjustable zero and gain
  • Short circuit protection
  • Rail mountable
Design and Installation:

The EM-M11A is designed for easy installation on a DIN rail, with a housing width of 25mm. The module includes a dual DC/DC converter and is protected by isolation borders, ensuring reliable performance in various industrial environments.

See more

Catalog excerpts

EM-M11AI/A/mA converter-1

EM-M11A MULTISCALE GALVANIC SIGNAL ISOLATOR AND CONDITIONER FEATURES: • Three way isolated • Multiple operating ranges • Two frequency ranges • Dip-switch settable • Isolation up to 1000 V • Adjustable zero and gain • Short circuit protected • Rail mountable EM-M11A is a multiscale conditioner and isolator module for the commonly used signals in automation. The range setting is easily done with DIP-switches and signal frequency limit can be set to 1 kHz or 20 Hz. Every partition (INPUT, OUTPUT, SUPPLY) is galvanically isolated up to 1000 V. Gain and Zero are easy to adjust and there is no mutual effect between these adjustments. The number of possible input/output signal combinations are up to 25 because any of the selectable input ranges can be combined with any of the output ranges. + Adjust ranges Isolation voltage Oper. ambient temp. OUT 4 + SETTABLE INPUT AMP. SETTABLE OUTPUT STAGE IN TECHNICAL DATA: Operating voltage Current consumption Linearity error Thermal drift Output ranges 0...1 V 0...5 V 0...10 V 0...20 mA 4...20 mA Input ranges 0...1 V 0...5 V 0...10 V 0...20 mA 4...20 mA Frequency response 1 2 Rin 5 _ RL 20...32 V 70 mA max < 0.1 % < 50 ppm/°C RL RL RL RL RL > > > < < 1 kohm 1 kohm 1 kohm 700 ohm 700 ohm Rin 50 kohm Rin 250 kohm Rin 500 kohm Rin 50 ohm Rin 50 ohm 0...1 kHz 0...20 Hz gain ± 20 % zero ± 20 % 1000 V 0...60 °C 3 6 + DUAL DC/DC CONVERTER POWER STAGE DASHED LINES ARE FOR ISOLATION BORDERS 79mm SETTING MAP OF EM-11A 4...20mA 0...20mA 0...1V 86mm 0...5V 0...10V DC...1kHz DC...20Hz INPUT SET FILTER OUTPUT SET DIN-MOUNTING RAIL WIDTH OF THE HOUSING IS 25mm ELECTROMEN Oy Vähäheikkiläntie 56B, 20810 Turku, FINLAND Tel. +358-2-4693050 Fax. +358-2-4693052