Overview: This document provides technical specifications for various external and split current transformers compatible with the ECT Electrex series, including Femto D4 ECT, Atto D4 ECT, Femto ECT net, Libra ECT, and Lyra ECT. These transformers are designed for high accuracy, even at low currents, making them suitable for power quality management.
Specifications:
  • ECT TA 100A 13mm: Nominal current of 100A, internal window diameter of 13mm, accuracy of 0.5%, frequency range of 50-60 Hz, turns ratio of 1000, plastic case, and external dimensions of 37mm diameter and 13.5mm height.
  • ECT TA 100A 19mm: Similar specifications to the 13mm version but with a 19mm internal window diameter.
  • ECT TA 200A 20mm: Nominal current of 200A, internal window diameter of 20mm, accuracy of 0.5%, frequency range of 50-60 Hz, turns ratio of 2000, plastic case, and external dimensions of 44mm diameter and 18mm height.
  • ECT TA 400A 30.5mm: Nominal current of 400A, internal window diameter of 30.5mm, accuracy of 0.5%, frequency range of 50-60 Hz, turns ratio of 4000, plastic case, and external dimensions of 60mm diameter and 17mm height (23mm including brackets).
Split Current Transformers:
  • ECT CTS 16-100A: Nominal current of 100A, internal window diameter of 16mm, accuracy of 0.5%, frequency range of 50-60 Hz, turns ratio of 1000, plastic case, and dimensions of 30mm width, 56mm height, and 29mm depth.
  • ECT CTS 24-200A: Nominal current of 200A, internal window diameter of 24mm, accuracy of 0.5%, frequency range of 50-60 Hz, turns ratio of 2000, plastic case, and dimensions of 44mm width, 76mm height, and 33mm depth.
  • ECT CTS 36-400A: Nominal current of 400A, internal window diameter of 36mm, accuracy of 0.5%, frequency range of 50-60 Hz, turns ratio of 4000, plastic case, and dimensions of 55mm width, 92mm height, and 38mm depth.
Additional Components:
  • Short-Circuitable Terminal Box: Designed for ../1A, ../5A, and ECT type CTs with an enclosure size of 40x60x20 mm.
Ordering Information: Each transformer and component is associated with a specific code for ordering purposes, such as PFAE000-01 for the ECT TA 100A 13mm transformer.
Note: Specifications are subject to change without prior notice.
See more

Catalog excerpts

ECT CT  -1

Current transformers for the Femto D4 ECT, Atto D4 ECT, Femto ECT net, Libra ECT and Lyra ECT series External current transformers, closed or split type, compliant with the Femto D4 ECT, Atto D4 ECT, Femto ECT net, Libra ECT e Lyra ECT series. The high accuracy, even at low currents / powers, makes possible to be used also for the management of the Power Quality. ECT TA 100A 13mm: external current transformer to be used exclusively with the ECT Electrex series: Femto D4 ECT, Atto D4 ECT, Femto ECT net, Libra ECT and Lyra ECT. Plastic shell. Internal window diameter: 13 mm. ECT TA 400A 30,5mm: external current transformer to be used exclusively with the ECT Electrex series: Femto D4 ECT, Atto D4 ECT, Femto ECT net, Libra ECT and Lyra ECT. Plastic shell. Internal window diameter: 30,5 mm. ECT TA 200A 20mm: external current transformer to be used exclusively with the ECT Electrex series: Femto D4 ECT, Atto D4 ECT, Femto ECT net, Libra ECT and Lyra ECT. Plastic shell. Internal window diameter: 20 mm. ECT CTS 16-100A: Split current transformer to be used exclusively with the ECT Electrex series: Femto D4 ECT, Atto D4 ECT, Femto ECT net, Libra ECT and Lyra ECT. Plastic shell. Equipped with a snap-on and screw-free closing system. Internal window diameter 16 mm. Protection on secondary circuit opening.

 Open the catalog to page 1
ECT CT  -2

ECT CTS 24-200A: Split current transformer to be used exclusively with the ECT Electrex series: Femto D4 ECT, Atto D4 ECT, Femto ECT net, Libra ECT and Lyra ECT. Plastic shell. Equipped with a snap-on and screw-free closing system. Internal window diameter 24 mm. Protection on secondary circuit opening. Short-Circuitable Terminal Box: with short-circuitable terminal box for ../1A, ../5A and ECT type CT. Enclosure size: 40x60x20 mm. ECT CTS 36-400A: Split current transformer to be used exclusively with the ECT Electrex series: Femto D4 ECT, Atto D4 ECT, Femto ECT net, Libra ECT and Lyra ECT. Plastic...

 Open the catalog to page 2

Archived catalogs

  1. Flash D6

    4  Pages

  2. X3M-96

    8  Pages

  3. X3M

    8  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.
About DirectIndustry
DirectIndustry is a marketplace that offers B2B players a complete experience, from product sourcing to purchase. DirectIndustry is an entity of VirtualExpo Group.