EMU-1415

EMU-1415

EMU-1415

Product catalog summary
Specifications:
  • Model: Electra Molins EMU-1415
  • Construction: Stationary / Automatic
  • Control Panel: AUT-MP12
  • Output:
    • Standby Service: 1,415 kVA / 1,132 kW
    • Prime Service: 1,280 kVA / 1,024 kW
  • Voltage: 400 V, 3 phases + N
  • Frequency: 50 Hz
  • Sound Level: 108 dBA (non-reverberant room), 120 dBA (exhaust pipe without silencer)
Procedures and Recommendations:
  • Outputs are based on ISO-8528-1 standards for 40ºC and 1000 m altitude.
  • Prime power allows a 10% overload for up to one hour every 12 hours.
  • Recommended average power usage:
    • 70% PRP in main service
    • 80% LTP in standby service
Dimensions and Consumption:
  • Dimensions: 4,810 x 2,050 x 2,320 mm
  • Weight: 10,100 kg (empty)
  • Fuel Tank Capacity: 3,000 l (optional)
  • Fuel Consumption: 222 l/h at 75% load
Engine Details:
  • Make and Model: Mitsubishi S12R-PTA
  • Type: Diesel 4 stroke
  • Cylinders: 12 in V-form
  • Cooling: Air
  • Oil Capacity: 180 l
Alternator Details:
  • Make and Model: Leroy Somer LSA 502 L7
  • Connection: Star
  • Insulation Class: H
  • Protection: IP-23
Batteries:
  • Quantity: 4
  • Connection: 2 parallel of 2 in series
  • Voltage: 24 V
  • Capacity: 210 Ah each
  • Type: Lead-acid
See more

Catalog excerpts

EMU-1415-1

Generating set technical data: Model Electra Molins EMU-1415 STATIONARY / AUTOMATIC FDRM OF CONSTRUCTION: STATIONARY / AUTOMATIC Brand of the Genset ELECTRA MOLINS Control panel type AUT-MP12 Output in standby service on mains failure 1.415 kVA 1.132 kW (LTP "Limited Time Power" according to norm ISO 8528-1) Output in prime service 1.280 kVA 1.024 kW (PRP "Prime Power" according to norm ISO 8528-1) Tolerance of the maximum active power (kW)_±3% Current intensity in standby service on mains failure 2.042 A Current intensity in prime service 1.848 A Precision of the voltage in steady state_±0,5% Frequency variation in steady state_±0,5% Engine heater output (only for automatic construction) 9.000 W Admissible first step load 720 kW Mean sound level at 1 m inside a non-reverberant room 108 dBA (The noise in a reverberant room increases 3-5 dB) Sound level at 1 m of the exhaust pipe without silencer 120 dBA Date: 01/11/2016. Electra Molins reserves the right to modify these specifications according to its own technical criteria.

 Open the catalog to page 1
EMU-1415-2

Page 2 of 2 Generating set technical data: Model Electra Molins EMU-1415 STATIONARY / AUTOMATIC Dimensions and Consumptions Length x Width x Height Weight empty of fuel Fuel tank capacity Specific fuel consumption Fuel consumption with 75% of load (849 kW) Diesel Engine Make of the engine and model Cycle MITSUBISHI S12R-PTA Diesel 4 stroke Cooling Nº and configuration of the cylinders Total swept volume Air aspiration Speed governor Air 12 in V-form 49,03 l Turbocharger with water-air cooler Electronic Total oil capacity Oil consumption at full load Capacity of the cooling circuit (40% antifreeze...

 Open the catalog to page 2
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.