EMU-1000

EMU-1000

EMU-1000

Product catalog summary
Specifications Overview:
Model: EMU-1000
Construction: Stationary / Automatic
Brand: Electra Molins
Control Panel: AUT-MP12
Standby Output: 1,000 kVA / 800 kW
Prime Output: 910 kVA / 728 kW
Voltage: 400 V, 3 phases + N
Frequency: 50 Hz
Power Factor: 0.8 - 1
Speed: 1,500 rpm
Sound Level: 105 dBA (non-reverberant room), 120 dBA (exhaust without silencer)
Performance and Tolerances:
Standby Current: 1,443 A
Prime Current: 1,313 A
Voltage Precision: ±0.5%
Frequency Variation: ±0.5%
Admissible Load: 466 kW
Engine Heater Output: 4,500 W
Operating Conditions:
Max Continuous Power: Variable load at 40ºC and 1000 m altitude
Overload Capacity: 10% for 1 hour every 12 hours
Recommended Power Usage: 70% PRP in main service, 80% LTP in standby
Dimensions and Fuel:
Dimensions: 4,250 x 1,840 x 2,327 mm
Weight: 8,000 kg (empty)
Fuel Tank: 990 l
Specific Fuel Consumption: 0.26 l/kW-h
Fuel Consumption at 75% Load: 156 l/h
Engine Details:
Engine Make/Model: Mitsubishi S12A2-PTA2
Type: Diesel 4-stroke
Cylinders: 12 in V-form
Volume: 33.93 l
Cooling: Air
Turbocharger: Water-air cooler
Oil Capacity: 120 l
Oil Consumption: 1 l/h
Cooling Circuit Capacity: 100 l
Alternator Details:
Alternator Make/Model: Leroy Somer LSA 493 L10
Connection: Star
Insulation Class: H
Voltage Regulator: AREP R450
Short-Circuit Current: 3 In for 10 seconds
Protection: IP-23
Batteries:
Quantity: 4
Connection: 2 parallel, 2 series
Voltage: 24 V
Capacity: 210 Ah each
Type: Lead-acid
See more

Catalog excerpts

EMU-1000-1

Generating set technical data: Model Electra Molins EMU-1000 STATIONARY / AUTOMATIC FDRM OF CONSTRUCTION: STATIONARY / AUTOMATIC Brand of the Genset ELECTRA MOLINS Control panel type AUT-MP12 Output in standby service on mains failure 1.000 kVA 800 kW (LTP "Limited Time Power" according to norm ISO 8528-1) Output in prime service 910 kVA 728 kW (PRP "Prime Power" according to norm ISO 8528-1) Tolerance of the maximum active power (kW)_±3% Current intensity in standby service on mains failure 1.443 A Current intensity in prime service 1.313 A Precision of the voltage in steady state_±0,5% Frequency variation in steady state_±0,5% Engine heater output (only for automatic construction) 4.500 W Admissible first step load 466 kW Mean sound level at 1 m inside a non-reverberant room 105 dBA (The noise in a reverberant room increases 3-5 dB) Sound level at 1 m of the exhaust pipe without silencer 120 dBA Date: 01/11/2016. Electra Molins reserves the right to modify these specifications according to its own technical criteria.

 Open the catalog to page 1
EMU-1000-2

Page 2 of 2 Generating set technical data: Model Electra Molins EMU-1000 STATIONARY / AUTOMATIC Dimensions and Consumptions Length x Width x Height Weight empty of fuel Fuel tank capacity Specific fuel consumption Fuel consumption with 75% of load (600 kW) Diesel Engine Make of the engine and model Cycle MITSUBISHI S12A2-PTA2 Diesel 4 stroke Cooling Nº and configuration of the cylinders Total swept volume Air aspiration Speed governor Air 12 in V-form 33,93 l Turbocharger with water-air cooler Electronic Oil consumption at full load Capacity of the cooling circuit (40% antifreeze cooling liquid)...

 Open the catalog to page 2
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.