General Overview
EL.CO. S.r.l. reserves the right to make changes to their products without prior notice. This document provides detailed information on solid-state relays and modular power controllers, specifically the MPCD series.
Solid-State Relays and Modular Power Controllers
The document outlines the specifications for solid-state relays and modular power controllers, including models with output currents of 10A, 25A, and 50A. Notably, models with 50A do not include an integrated fuse for output protection.
Technical Specifications
  • Display: Dual LED display with a main display of 4 digits (15.5 mm) and a secondary display of 4 digits (7 mm).
  • Inputs: Universal inputs supporting various thermocouples, infrared sensors, thermoresistances, and linear signals.
  • Accuracy: ±0.5% span ±1 digit, with specific accuracy for certain thermocouple types.
  • Power Supply: Options for 24V AC/DC or 100-240V AC.
  • Communication: RS485 serial port with MODBUS-RTU protocol.
  • Mounting: DIN rail mounting.
Functionalities
  • Control: Programmable PID or ON/OFF control with autotuning and self-tuning algorithms.
  • Alarms: Three programmable alarms for absolute, deviation, and band settings.
  • Set Points: Four selectable set points.
  • Communication: Standard TTL and optional RS485 with MODBUS RTU protocol.
  • Power Consumption: Maximum of 7 VA.
Wiring and Connections
The document includes wiring diagrams for connecting multiple modules using FLAT connectors A and B, with specific instructions for the RS485 serial port and digital input connections.
Dimensions and Weight
  • Models are available in different weights: 10A (1500g), 25A (1600g), and 50A (1900g).
  • Protection degree is IP 20.
Compliance
The products comply with the Low Voltage Directive 2006/95/EC and Electromagnetic Compatibility Directive 2004/108/EC.
See more

Catalog excerpts

MPCD-1

1 - RELÈ ALLO STATO SOLIDO 1 - SOLID-STATE RELAYS * Interfaccia utente integrata * Alimentazione 24V AC/DC o 100…240V AC * Ingresso universale programmabile per controllo temperatura * Ingresso digitale abilitazione controllore modulare di potenza * Possibilità di programmare il terminale 4 come : ingresso digitale o uscita logica 0…12V o alimentazione per trasmettitore * Regolazione PID o ON/OFF programmabile * Possibilità di programmare una uscita di allarme per mancanza carico o carico in corto ( LbA- Loop break alarm) * Fusibile integrato per protezione dell'uscita ( no su modelli da 50A) * Porta seriale RS485 con protocollo di comunicazione MODBUS-RTU * Possibilità di configurazione parametri con chiave di programmazione o da PC tramite software dedicato * Montaggio su guida DIN * Corrente uscita 10A, 25A, 50A * Tensione uscita da 48 a 450V AC *Integrated user interface * Power supply 24V AC / DC or 100 ... 240V AC * Programmable universal input for temperature control * Digital input enable modular power controller * Possibility to set the terminal 4 as: digital input or logic output 0 ... 12V or power supply for transmitter * PID control or ON / OFF programmable * Possibility to set one alarm output for no load or load in short (LbA-Loop break alarm) * Integrated fuse for output protection ( Not for models of 50A) * Serial port RS485 with MODBUS-RTU communication protocol * Possibility configuration of parameters by programming key or by PC with dedicated software * Din rail mounting * Output current 10A,25A,50A * Output Voltage from 48 to 450V AC ACCESSORI - ACCESSORIES ACCESSORI - ACCESSORIES FOR MODULAR POWER CONTROLLERSpag. 122 TABELLA SELEZIONE CONTROLLORE MODULARE DI POTENZA MODULAR POWER CONTROLLER SELECTION TABLE TIPO DI COMMUTAZIONE ZERO CROSSING ZERO CROSSIG COMMUTATION Corrente di uscita Output current Tensione di uscita Output voltage Tensione ingresso Input voltage Modello Model 50A 48-450VAC ** Per i modelli da 50A non è previsto il fusibile intregrato per la protezione dell'uscita ** For models of 50A is not provided the integrated fuse for output protection DATI TECNICI - TECHNICAL DATA Display / Display Display doppio a lED Display principale: 4 digit h 15.5 mm Display secondario: 4 digit h 7 mm Main display: 4 digit h 15.5 mm Secondary display: 4 digit h 7 mm Ingressi / Inputs Ingresso universale Universal inputs Accuratezza misura ± 0.5% span ±1 digit, (±1% span ±1 digit per T/C tipo S) ±0.5% span ±1 digit, (±1% span ±1 digit for T/C S type) Catalogo generale General catalogue EL.CO. S.r.l si riserva di apportare modifiche senza alcun preavviso. - EL.CO. S.r.l. Reserves the right to make changes without obligation of notice.

 Open the catalog to page 1
MPCD-2

1 - RELÈ ALLO STATO SOLIDO 1 - SOLID-STATE RELAYS DATI TECNICI - TECHNICAL DATA Ingressi Digitali DI1: Ingresso digitale abilitazione controllore modulare di potenza : programmabile ed è in alternativa alla OUT 4 Digital inputs DI: Digital input enable modular power controller DI2: programmable and is an alternative to OUT 4 Uscite / Outputs OUT2: relè SPST-NO 2A/240 VAC AC1 - 1A/240AC AC3 OUT3: relè SPST-NO 2A/240 VAC AC1 - 1A/240AC AC3 OUT4: programmabile: uscita in tensione per pilotaggio SSR 13v max @ 1ma, 10.5 min @ 22ma ±10% oppure alimentazione trasmettitore oppure 2° ingresso Digitale...

 Open the catalog to page 2
MPCD-3

1 - RELÈ ALLO STATO SOLIDO 1 - SOLID-STATE RELAYS DATI TECNICI USCITA - OUTPUT TECHNICAL DATA Modelli Models Tensione nominale Nominal voltage Range tensione di carico Load voltage range Picco ripetitivo allo stato di OFF Ripetitive peak off-state voltage Corrente uscita Output current Corrente di spunto non ripetitiva Non ripetitive surge peak I²t scelta fusibile I²t Rating Tempo critico salita tensione allo stato di off critical rateof rise of off-state voltage Caduta tensione in uscita Output voltage drop Perdita di corrente allo stato di off Off-stage leakage current Corrente minima di fuzionamento...

 Open the catalog to page 3
MPCD-4

■ RELE ALLO STATO SOUDO SCHEMI Dl COLLEGAMENTO - WIRING DIAGRAMS □11= liXife-JiO delate ibi Cifflfilktf* Dl i = CVjfla* input erubte modular etfwt* Connettori FLAT A e B : per il collegamento tra i moduli della porta seriale 485 e dell'in- gresso digitale abilitazione controllore modulare di potenza Se si collegano piii moduli attraverso i connettori FLAT Ae B, il collegamento della por- ta seriale RS485 e dell'ingresso abilitazione controllore modulare potenza pud essere fatto solo sul primo modulo (MASTER) FLAT connectors A and B : for the connection between the modules of the serial port 485...